ioLogik 2500 Series
Configuration Library
4-22
Modbus/TCP Master
The ioLogik 2500 supports a Modbus/TCP Master function that acts as a Modbus/TCP master for monitoring
the data from two connected Modbus/TCP slave devices. The collected data can be used by Click&Go Plus or
in an upper level system after the data is transmitted via a Modbus, AOPC, SNMP, or RESTful API
connection. The data can also be recorded locally using the Data Logging function.
Device
Configure the connected Modbus/TCP slave device settings.
•
Enable Data Collection: Check to enable Modbus data collection
•
Device Name: Name the slave device (e.g., Flow Meter)
•
IP Address: Fill in the IP address of the slave device
•
Port: Fill in the Modbus communication port of the slave device (default: 502)
•
Delay between polls: Set the delay time between polls (default: 502)
Click the Advanced button to display the advanced fields for timeout/retry settings. Refer to the
connection cycle diagram below for details.
•
Connection Timeouts: Modbus initial connection timeout
•
Reconnect Delay: Delay time between timeout and start slave device reconnection
•
Reconnect Cycles: Set reconnect times for each slave device reconnection cycle
•
Cycle Delay: Delay time between each reconnection cycle
•
Polling Timeouts: Set timeout to trigger a polling retry for polling command