ioLogik 2500 Series
Configuration Library
4-20
I/O Type
Select the type of data you would like to record. Choose from DI, Counter, DO, Pulse, AI, Internal Register,
Virtual Channel, Serial Tag, and RSSI (cellular models only).
Select All/Unselect All
You may select all channels, or deselect all channels.
Apply to All
You can apply one parameter to all channels. For example, if you can change On Change from disabled to
enabled and then click Apply to All, all AI channels will be enabled.
Update Method
•
On Change for DI/DO/Pulse/System Tags: The ioLogik will update the tag value to MX-AOPC UA
Server whenever the tag status changes.
•
On Change for AI Tag: If the AI is configured to update on change, the percentage settings represent
the percentage of the full analog range. For example, if the AI is configured to 0 to 10 V, “On Change
1%” means the ioLogik will update to the MX-AOPC Server every time there is 0.1 V change.
•
Interval for Counter/AI/RTD/TC/IR/FIR/VC/Serial Tags: The ioLogik will update the tag value to
MX-AOPC UA Server when the interval time elapses. The interval time can be configured to between 1
and 65535 seconds; the default is 5 seconds.
NOTE
A shorter interval time may cause a large number of data packets to be generated, resulting in higher data
fee if you are using a pay-by-packet connection plan. The ioLogik might also experience higher system
loading and unstable performance.
SNMP
The ioLogik supports SNMP (Simple Network Management Protocol) v1, v2c, and v3 to monitor network and
I/O devices with SNMP Network Management software. It is useful in building automation and telecom
applications. Use these fields to enable SNMP and set the read and write community strings for SNMPv1 and
SNMPv2c, or use authentication for SNMPv3.