ioLogik 2500 Series
Overview
1-8
Flow Control: None, RTS/CTS, XON/XOFF
Baudrate: 300 to 115200 bps
Protocols: Modbus/RTU (master/gateway), serial tunnel mode (client/server)
Physical Characteristics
Wiring: I/O cable, 14 AWG (max.)
Dimensions: 61 x 157 x 115 mm (2.4 x 6.18 x 4.53 in)
Weight: Under 1265 g (2.79 lb)
Mounting: DIN rail (standard), wall (optional)
Storage
Expansion Slot: Up to 32 GB microSD™ memory card (SDHC compatible)
Note: For units operating in extreme temperatures, industrial-grade, wide-temperature SD cards are
required.
Environmental Limits
Operating Temperature:
Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -30 to 70°C (-22 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Shock: IEC 60068-2-27
Vibration: IEC 60068-2-6
Altitude: Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
Safety: UL 508
EMC: EN 61000-6-2/6-4
EMI: CISPR 32, FCC Part 15B Class A
EMS:
IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power 2 kV
IEC 61000-4-6 CS: 3 V
IEC 61000-4-8
Radio: R&TTE: EN 62311, EN 300 328, EN 301 489-1, EN 301 489-17, EN 301 893; NCC; VCCI
Hazardous Location: Class 1 Division 2; ATEX Zone 2
Green Product: RoHS, CRoHS, WEEE
Note: Please check Moxa’s website for the most up-to-date certification status.
Warranty
Warranty Period: 5 years
Details: See www.moxa.com/warranty
ioLogik 2512 HSPA/GPRS/WLAN Specifications
Inputs and Outputs
Digital Inputs: 8 channels
Configurable DIOs (by software): 8 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP) and Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open