Ax350_04a_oi_e.doc / May-18
Seite 53 / 54
6.6
Technical specifications
6
7
Technical Specifications:
Connections:
Connector type:
screw terminal, 1.5 mm² / AWG 16
Power supply (DC):
Input voltage:
Protection circuit:
Consumption:
Fuse protection:
18 … 30 VDC
reverse polarity protection
approx. 100 mA (unloaded)
extern: T 0,5A
Power supply (AC):
(Option AC)
Input voltage:
Power consumption:
Fuse protection:
115…230 VAC, 50…60 Hz)
approx. 3 VA (unloaded)
extern: T 0,1 A
Encoder supply:
DC version:
Output current:
approx. 1 V lower than the power supply voltage
max. 250 mA
AC version (AC350):
Output current:
approx. 24 V (± 15%)
150 mA until 45°C / 80 mA by more than 45°C
Reference output:
Output voltage:
Accuracy:
Load:
10 V
± 0.1 %
max. 10 mA
Analog inputs:
Number of inputs:
Configuration:
Voltage input:
Current input:
Resolution:
Accuracy:
2
current or voltage operation
-10 … +10 V (Ri
≈
50 kOhm)
0 … 20 mA / 4 … 20 mA (Ri
≈
100 Ohm)
16 bit
± 0,1 %
Control inputs:
Number of inputs:
Format:
Frequency:
Load:
3
HTL, PNP (Low 0 … 3 V, High 9 … 30 V)
max. 10 kHz
max. 2 mA / Ri > 15 kOhm / 470 pF
Analog output:
(Option AO/AR)
Configuration:
Voltage output:
Current output:
Resolution:
Accuracy:
Reaction time:
current or voltage operation
-10…+10 V (max. 2 mA)
0/4… 20 mA (burden: max. 270 Ohm)
16 Bit
± 0,1 %
< 150 ms
Control outputs:
(Option AO/AR/CO/CR)
Number of outputs:
Format / level:
Output current:
Reaction time:
4
5 … 30 V (depends on the Com+ voltage), PNP
max. 200 mA
< 1 ms
Relay outputs:
(Option RL)
Number of outputs:
Configuration:
AC-Switching capacity:
DC-Switching capacity::
Reaction time:
2
potential free changeovers
max. 250 VAC / 3 A / 750 VA
max. 150 VDC / 2 A / 50 W
< 20 ms
Serial interface:
(Option AO/AR/CO/CR)
Format (Option A0/CO):
Format (Option AR/CR)
Baudrate:
RS232
RS485
9600, 19200 or 38400 baud
IO-Link:
(Option IO)
Module / Revision:
Bitrate:
Port Class:
Device / V1.1
COM 3
Typ A