AX34509b_e.doc / Mrz-16
Page 8 / 38
2.5.
Serial RS232 / RS485 interface (AX 348 only)
Ex factory the unit is set to RS232 communication. This setting can be changed to RS485
(2-wire) by means of an internal DIL switch. To access the DIL switch, you must remove the
screw terminal connectors and the backplane. Then pull the board to the rear to remove the
PCB from the housing.
ON DIP
DIL-Switch
Removal of the back plane
Location of the DIL switch
Never set DIL switch positions 1 and 2 or DIL switch positions 3 and 4 to “ON”
at the same time!
After setting the switch, shift the print carefully back to the housing and avoid
damage of the front pins for connection to the front keypad plate.
2
3
5
RxD
RxD
TxD
TxD
GND
Screen
PC
AX 348
9
(Sub-D-9)
10
8
Connection of the RS232 interface
PLC
AX 348
9
10
A(+)
B(-)
A(+)
B(-)
Connection of the RS485 interface