6.5.2.
Operational Parameters for configuration of the interface:
Menu
Setting Range
Default
Serial Timer:
Setting 0,000 allows manual activation of a serial data
transmission at any time. All other settings specify the cycle
time for automatic transmission, when the interface is set to
"Printer Mode"
0,000
0,010 sec
…
9.999 sec
0,100 sec
Between two transmission cycles the unit will allow a pause
depending on the baud rate. The minimum cycle times for
timer transmissions are shown in the table.
Baud Rate
Minimum Cycle Time [ms]
600
384
1200
192
2400
96
4800
48
9600
24
19200
12
38400
6
Serial Mode:
PC:
Operation according to communication profile
(see 6.5.3)
Print1:
Transmission of string type 1 (see 6.5.4)
Print2:
Transmission of string type 2 (see 6.5.4)
Serial Register-Code:
100
...
120
101
Specifies the register code of the data to be transmitted.
The most important register codes are:
Register
S-Code
ASCII
Actual display value
101
:1
Analogue input A *)
106
:6
Analogue input B *)
107
:7
Display channel A
113
;3
Display channel B
114
;4
Display channel [A,B] combined
115
;5
*) Normalized analogue input values, scaling 0 ... 10 000 for 0% to 100% of full scale input signal