Installation
30
68P81096E37-N
06/28/05
The station is to be connected to a battery supply that is in accordance with
the applicable electrical codes for the end use country; for example, the Na-
tional Electric Code ANSI/NFPA No.70 for the U.S.
Cables are supplied with the charging option.
Do not make connections directly
from the station to the storage battery
. Connect as shown in Figure 10.
CAUTION
!
Figure 10. Making Connections to Storage Battery
DC input Connector located at rear of
the station for hooking up the
Battery
backup system
.
Required input power:
• Voltage - 14.2 Vdc Low Power (LP)
28.4 Vdc High Power (HP)
• Current - 11.5 Amps LP
13.0 Amps HP
Both positive and negative terminals must be
protected with appropriate fast acting fuses.
Secondary circuitry must be SELV type and be
installed nearby, preferable in the same building.
All installations shall be carried out by trained
service personnel only.
Connector ESD cover
must be in place when
Battery Backup cable
is not in use – to
prevent exposure to
live contacts.
CAUTION
!