McTi-24 T1 Facility Distance Compensation
Each McTi-24 board is equipped with a bank of dip switches (SW2) which allows
compensation for the cable length between the originating T1 facility or repeater and
the McIAS unit. The illustration below indicates the location of this switch bank and
the available cable lengths.
CAUTION:
The components on the assembly are sensitive to electrostatic discharge
(ESD). Use an ESD protected environment and procedure when working
with the boards.
T1 Cable Distance Compensation
One Way Distance
Between McIAS
and Switch
(in feet)
SW2 Dip Switch Settings
1
2
3
0 - 110 *
111 - 220
221 - 330
331 - 440
441 - 550
551 - 660
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
* Factory setting (minumum distance compensation).
Loopback requires minimum distance compensation.
NOTE: All other settings on SW2 must remain in the default position (all OFF).