05. TROUBLESHOOTING

INSTRUCTIONS FOR FINAL CONSUMERS / SPECIALIZED TECHNICIANS

Anomaly

Procedure

Behavior

Procedure II

Discovering the origin of the problem

• Barrier

doesn't work

• Make sure you have 

230V power supply 

connected to

automation and if 

the fusible working 

properly.

• Still not working

• Consult a qualified

technician.

1

 • Remove the barrier top cover;

2

 • Measure the 24V output of the transformer to detect the fault location;

A) Has 24V:

1

 • Verify the control board supplies of the barrier to detect if the fault is in the motor or in the control board. Replace the damaged component or send it 

to the services for diagnosis and repair.

B) Has not 24V:

1

 • Verify the 230V input of the transformer. If have 230V the problem is in the transformer. If haven't 230V, the problem should be in the fusible, electric 

cables or in the power supply. Verify all the systems.

• Verify the STOP 

• Still not working

• Consult a qualified

technician.

1

 • Take a start in remote control to open and verify the behavior of the LEDs;

2

 • Check the LED signs and the limit switches connections. If everything is corrected and there is no micro acted, the LEDs have to be on. Check all the 

photocells circuit connections to the barrier;

3

 • In the E menu, make sure the STOP is enabled (page 7B). If enabled and the circuit is not closed, the barrier will not work.

• Barrier

doesn’t move

but makes

noise

• Unlock the barrier 

and move by hand to 

check for mechanical 

problems.

• The barrier is 

stuck?

• Consult an experienced

barrier expert.

1

 • Check all motion axis and associated motion systems related with the barrier, to find out what is the problem. Also check that the springs are in good 

condition and can support the barrier.

• The barrier moves

easily?

• Consult a qualified

technician

1

 • Turn off the barrier from control board and test it on directly to a 24V battery to find out if it is damaged;

2

 • If the barrier runs, the problem is in the control board. Remove it and send it to the technical services for diagnosis;

3

 • If the barrier does not work, remove the motor and send it to the technical services for diagnosis.

• Barrier 

opens but 

doesn’t close

1 • Check if there is 

any obstacle in front 

of the photocells;

2 • Make sure if the

photocells are 

working. Put your 

hand in front and 

check that the relay 

makes the same noise.

3 • Check if any of 

the control devices  

of the barrier are 

jammed and sending 

permanent signal to 

control unit;

4 • Check the Security 

Band connection.

• Barrier opened but

didn’t close again.

• Consult a qualified

technician

1

 • Verify if the display is connected to confirm the existence of power supply;

2

 • Verify if the photocells are powered in control board output;

3

 • Access the menu on the display and disable the photocells and the STOP;

4

 • Check limit switch connections. If the 2 LEDs are turned off, it means that the barrier can not operate because have the limit switches actuated.

5

 • Try to close;

A) Closed:

1

 • Problem is in one of these two systems. Activate the photocells and check that the barrier closes. If close, problem will be in the STOP. Ative tin the 

menu and try to close the barrier to be sure.

B) Doesn't closed:

1

 • Problem is in the barrier or in the control board. Give an order to the barrier close while measuring the control board power output to the barrier. 

If you have 24V, the control board is working and the problem is in the barrier.

2

 • If it has not current, the problem is in the control board.

• Barrier 

doesn’t make 

complete 

route

• Unlock the barrier 

and move by hand to

check for mechanical

problems.

• Encountered

problems?

• Consult an experienced

barrier expert.

1

 • Check all motion axis and associated motion systems related with the barrier, to find out what is the problem. Also check that the springs are in good 

condition and can support the gate.

• The barrier moves

easily?

1 • Re-program the limit 

switches;

2 • Consult a qualified

technician

1

 • Verify if the tests to the barrier were well made;

2

 • Change the strength of F menu until the barrier move the gate without changing the direction;

3

 • This adjustment should be made to in case the barrier find an obstacle do an inversion;

4

 • If even at maximum power level (F9) is still the problem, test the barrier directly connected to a 24V battery to see if it has the power to open / 

close the barrier completely;

5

 • Change the strength in the F menu until the barrier move the without changing the direction;

Содержание SIGMA 4M

Страница 1: ...v1 0 REV 12 2019 SIGMA EN USER INSTALLER S MANUAL SIGMA...

Страница 2: ...le in countries with recycling systems This marking on the product or literature indicates that the product and electronic accessories eg Charger USB cable electronic material controls etc should not...

Страница 3: ...y persons with experienced in terms of usage of the product in a safe manner and who understands the risks and dangers involved Children shouldn t play with the product or opening devices to avoid the...

Страница 4: ...mrequiresanyrepairormodification unlocktheautomatism turn off the power and do not use it until all safety conditions have been met In the event of tripping of circuits breakers of fuse failure locate...

Страница 5: ...lashlight 2 FALK remote controls Unlock key Barrier Gate Key MF30 Photocells User Manual Bar mounting accessories Barrier fixing plate Barrier Fixed support for bar Barrier bar SIGMA is an electromech...

Страница 6: ...the opening maneuver PERMANENT BLUE LIGHT During the pause time while open FLASHES RED LIGHT During the closing maneuver PERMANENT YELLOW LIGHT When the barrier is closed and the twilight sensor dete...

Страница 7: ...The map shown is for a standard installation however we do not provide all components see kit composition on page 4B If you need other accessories please contact us 1 Sigma 2 Bar 3 Bar Extension 4 Pho...

Страница 8: ...Move the cover lever to the right as shown to unlock the cover Remove Side Profiles Do the same with the side and chrome profiles to fully release the inside of the barrier If you already have a shoe...

Страница 9: ...izontal Once the cement has dried remove the upper females to apply the barrier Route the electrical cables to connect the engine to the accessories and power supply Leave cables of a length that ensu...

Страница 10: ...ed position 3 Disconnect the bar from any power supply These safety steps ensure that the springs are at the lowest point of tension and that the bar will not come down close by itself REMOVE LEVER SP...

Страница 11: ...nto the side hole and replace the bolt and female bolt NOTE Fully tighten the bolt and then unscrew it 1mm to loosen slightly Retighten the motor tip to the lever in one of the holes on the other side...

Страница 12: ...vided in the package Keep the attached cables inside the bar cover and secure the cover to the barrier with the two remaining screws Apply the label to hide the screws 4 2 3 REVERSE BAR SUPPORT 1 Make...

Страница 13: ...ned to the height of the bar you will have to adjust the arm height To do this follow these steps Drill two holes in the installation location to secure the support with screws and dowels Loosen the s...

Страница 14: ...ith pliers so that it does not rotate and then tighten the adjusting female until each spring is stretched the distance mentioned in the table on page 14 Once the spring s are stretched unlock the mot...

Страница 15: ...5 mm 1 mm MOTOR Hole Hole Hole 3 Hole 3 Hole 3 Hole 3 Hole 3 BAR WITH RUBBER 6000 5500 5000 4500 4000 3500 SPRING 1 Big Hole Hole 3 Hole 3 Hole 3 Hole 3 Hole 3 Hole 3 Adjustment 15 mm 1 mm 20 mm 1 mm...

Страница 16: ...shaft inward Place the bar in a horizontal closed position After adjusting the screw tighten the locking female until it touches the center lever to lock the screw in this position 1 3 2 4 Lock femal...

Страница 17: ...the connectors top of the barrier Route the power cables coming from the ground through the pipe When the power cable reaches the barrier surface connect the wires to the connector on the electronics...

Страница 18: ...frame Use the slots on the top and bottom plates of the chassis to guide the side profiles and keep them in this position 1 2 APPLY COVER Connect the flashing light LEDs plug with the connection plug...

Страница 19: ...ule Barrier cover LED Strip Flashing Light Engine SIGMA Barrier Transformer Control board MC61 BR Barrier Interior Limit Switch Brown Blue Black Red Red Green Yellow Black Color wires Color wires Engi...

Страница 20: ...COM NC NO 1 2 1 2 3 4 COM NC NO 1 2 EN 04 CONNECTIONS PHOTOCELL CONNECTIONS AND SAFETY BAND Control board MC61 BR Barrier Interior Control board MC61 BR Barrier Interior Blue Red Green Yellow Brown Wh...

Страница 21: ...nosis Barrier opens but doesn t close 1 Check if there is any obstacle in front of the photocells 2 Make sure if the photocells are working Put your hand in front and check that the relay makes the sa...

Отзывы: