56
Troubleshooting
Problem:
Cannot connect to the controller via EIA-485
Solution:
Check the following:
• The RS-232 port is not in use. The EIA-485 and RS-232 ports cannot be used simultane-
ously. Only one port can be used at a time.
• The RSC-1 adapter used to connect the PC to the EIA-485 network shows a green LED
and pulses red when a connection is attempted. See the RSC-1 documentation for more
information.
• Each controller or device on the EIA-485 network has been programmed with a unique
MODBUS ID.
• A serial cross-over (Null Modem) cable is used for the connection between the PC and the
Morningstar RSC-1 485 Adapter. A straight-through serial cable will not work.
• Power is supplied to the 4-wire bus on the Power/Ground lines. The bus requires voltage
in the range: 8 - 16 Vdc.
• All bus connections are secure and each terminal is wired in parallel: line A to line A, line B
to line B, etc.
Problem:
Cannot connect to the controller via Ethernet
Solution:
see the
TriStar MPPT Networking Companion Document
, available on our website.
Содержание TriStar TS-MPPT-30
Страница 2: ...Dimensions in Inches Millimeters...