22
Installation
Step 6 - Grounding and Ground Fault Interruption
WARNING:
This unit is not provided with a GFDI device. This charge controller must be used with an
external GFDI device as required by the Article 690 of the National Electrical Code for
the installation location.
NOTE:
Conductors identifi ed by the color combination green/yellow shall only be used for earthing
conductors.
AVERTISSEMENT :
L’appareil n’est pas fourni avec un dispositif GFDI. Ce contrôleur de charge doit être
utilisé avec un dispositif GFDI externe tel que requis par l’Article 690 du Code électrique
national de la région de l’installation.
Use a copper wire to connect the grounding terminal in the wiring box to earth ground. The
grounding terminal is identi
fi
ed by the ground symbol shown below that is stamped into the wiring
box just below the terminal:
Figure
3-4.
Ground
Symbol
Do not connect the system negative conductor to this terminal. NEC requires the use of an exter-
nal ground fault protection device (GFPD). The TriStar MPPT does not have internal ground fault
protection. The system electrical negative should be bonded through a GFPD to earth ground at
one (and only one) location. The grounding point may be located in the solar circuit or the battery
circuit.
The minimum size of the copper grounding wire:
• TS-MPPT-45 10 AWG (6 mm
2
)
• TS-MPPT-60 8 AWG (10 mm
2
)
WARNING: Risk of Fire
DO NOT bond system electrical negative to earth ground at the controller. Per NEC
requirements, system negative must be bonded to earth ground through a GFPD at only
one point.
AVERTISSEMENT : Risque d’incendie
NE LIEZ PAS le côté négatif du système à la mise à la terre au niveau du contrôleur.
Selon les exigences du CNE, le côté négatif du système doit être mis à la terre par un
GFPD à un seul point.