Installation
EcoBoost MPPT Operator’s Manual
13
12
3.0
Switches 2, 3: System Voltage
Three (3) system voltage configurations are available as
shown in the table below:
System Voltage
Switch 2
Switch 3
Auto
OFF
OFF
12
OFF
ON
24
ON
OFF
NOTE:
Before connecting the battery, measure the open-circuit
voltage. It must be over 10 volts to start the controller. If the
system voltage Settings Switches are set to Auto-detect, battery
voltage over 15.5V will be detected as a 24V nominal battery,
and the unit will charge accordingly. The 12/24V auto selection is
only done at start-up, and the detected system voltage will never
change during operation.
Generally, the specfic system voltage is known, and it is best
to set DIPs 2,3 accordingly; the auto-detect setting should
be used only in rare circumstances.
Switches 4, 5, 6: Battery Type Selection
Preset EcoBoost MPPT battery charging options are shown
in table 3-1 below. All voltage settings listed are for nominal
12 volt batteries.
Multiply the voltage settings by two (2) for 24 volt systems.
NOTE:
These settings are general guidelines for
use at the operator’s discretion. The
EcoBoost MPPT can be programmed to satisfy a wide range
of charging parameters. Consult the battery manufacturer for
optimal battery charge settings.
DIP
Switch
Settings
4-5-6
Battery
Type
Absorp.
Stage
(volts)
Float
Stage
(volts)
Equalize
Stage
(volts)
Absorp.
Time
(mins)
Equalize
Time
(mins)
Equalize
Timeout
(mins)
Equalize
Equalize
Equalize
Interval
(days)
Equalize
Interval
(days)
Equalize
Interval
(days)
off-off-off 1 - Sealed*
14.00
13.50
150
off-off-on 2 - Sealed*
14.15
13.50
14.40
150
60
120
28
off-on-off 3 - Sealed*
14.30
13.50
14.60
150
60
120
28
off-on-on 4- AGM/Flooded
14.40
13.50
15.10
180
120
180
28
on-off-off 5 - Flooded
14.60
13.50
15.30
180
120
180
28
on-off-on 6 - Flooded
14.70
13.50
15.40
180
180
240
28
on-on-off 7 - L-16
15.40
13.40
16.00
180
180
240
14
on-on-on 8 - Custom
Custom
Custom
Custom
Custom
Custom
Custom
Custom
Custom Custom
Custom
* “Sealed” ba
tt
ery type includes gel and AGM ba
tt
eries
Custom
LVD
(volts)
LVR
(volts)
Custom
12.30
13.80
12.10
13.60
11.90
13.40
11.50
13.00
11.70
13.20
11.30
12.80
11.50
12.60
Table 3.1. Battery charging settings for each selectable battery type
Switch 7: Battery Equalization
Mode
Switch 7
Manual Equalization
OFF
Auto Equalization
ON
Switch 8: Reserved for Future Use