3.4.11 Recommended Cable Routing
-
Cables should be routed within the enclosure in accordance with the following diagrams. Ensure
that power-limited cables are routed separately from AC Mains and non power-limited cables.
-
The diagrams below show typical arrangements for the DXc1 (small enclosure), DXc2 (medium
enclosure) or DXc4 (medium enclosure) including recommended top-face knockouts.
Figure 23 - DXc1 - Recommended Cable Routing
Figure 24 - DXc2/4 - Recommended Cable Routing
Key:
PL
= Power Limited Wiring (i.e. AUX, Sounders, Inputs,
Loops and RS485)
NPL = Non-Power Limited Wiring (i.e. Relays)
M
= Mains Wiring
CAUTION: A BATTERY CHARGER FAULT indication is given if the thermistor lead is disconnected.
The thermistor is calibrated for use only with the panel Base PCB with which it is
supplied. DO NOT use the thermistor with any other panel as this may reduce the
capacity / life of the batteries.
3.5
Keyswitch Option
-
The diagram opposite shows the location for
the Keyswitch option.
-
The position is identical for all models; it is
fitted to the right of the panel status LEDs.
-
The Keyswitch option comes as a complete
assembly including cable and two keys.
-
The Keyswitch is mounted onto the hinged
fascia/ display plate and plugs directly into a
connector, J1, on the Display PCB.