Morley-IAS
996-203-000-2, Rev. 02
A5 - 3
-
Click on ‘Comms’ menu, select ‘Port’ to check that the correct port is selected.
-
If the USB to Serial Adapter Kit lead (PN: 020-891) is being used this will have been configured to
use a specific port when the driver software was installed. This is a quick way of checking that the
configured port has the black circle alongside. If this lead is not being used but the earlier type of
communications lead is being used (PN: 795-080) instead, ensure that the port selected is the
physical port being used at the back of the PC.
-
Then, from the ‘Flash’ menu select the ‘Start’ option.
-
The panel software upgrade now starts. When finished, the following typical screen will be displayed:
Note:
If the upgrade utility reports that there is a problem communicating with the fire panel, first
check that the correct comm port is selected. If this does not resolve the problem and the
USB to Serial Adapter Kit lead is being used, disconnect the lead at the panel end and try
again. The jumper link, J1, MUST be in the ENABLE position to perform this procedure - as
confimation of this, the LCD remains blank.