30
The Interface Solution Experts
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
Table 8
. Device Status Bytes Table
Bit
0
1
2
3
4
5
6
7
Primary Variable Out of Limits. The process applied to the sensor for the Primary Variable is beyond
the operating limits of the device.
Non-Primary Variable Out of Limits. The process applied to a sensor, other than that of the Primary
Variable, is beyond the operating limits of the device.
Command
#48,
Additional Status
Information
,
may be requried to identify the variable.
Analog Output Saturated. The analog and digital outputs for the Primary Variable are beyond their limits
and no longer represent the true applied process.
Analog Output Current Fixed. The analog and digital outputs for the Primary Variable are held at
the requested value. They will not respond to the applied process.
Additional Status Available. More status information is available than can be returned in the Field Device
Status.
Command
#48,
Additional Status
Information
may be required to identify the variable.
Cold Start. Power has been removed and reapplied resulting in the reinstallation of the setup information. The
first command to recognize this condition will automatically reset this flag. This flag may also be set following a
Master Reset or a Self Test.
Configuration Changed. A write or set command has been executed.
Device Malfunction. A hardware error or failure has been detected by the device. Further information
may be available through
Command
#48,
Additional Status
Information.
Type
Error
Error
Error
Error
Error
Error
Error
Error
Description
ERROR HWARE
ERROR EEROM
ERROR CALIB
ERROR CKSUM
ERROR BLANK
ERROR RANGE
ERROR DZERO
ERROR CONFG
ERROR SWARE
RJC BROKE
ERROR INSAT
ERROR F END
ERROR
Error Condition
Hardware failure
EEPROM failure
Calibration data bad
Configuration or calibration data checksum mismatch
EEPROM blank
Process variable out of range (< -99999 or > +99999)
Maths division by zero error
Configuration information bad
Software watchdog failure
RJC Broken
Input saturation condition
Front-end comms error condition
Other or combination of errors
Displayed Message
Table 9.
Process Variable Error Displayed Messages
TDZ
2
Displayed Error
Messages
The TDZ
2
will need to be sent back to Factory for
repair is any of the messages shown in Table 9. are