SDY

The Interface Solution Experts   9

PC-Programmable Signal 

Isolator/Converter with Display

Note:

 

File names must follow the DOS convention.

 

Eight-character maximum, all lower case, no suffix.

 

 

The Configuration Program adds

 

a suffix to the file name automatically.

3.  Use the Explorer-like interface to designate 

the location on the PC drive for the file to be 

saved.

4.  Click on “Save”
5.  Click “Yes” to save the named file to disk.

 

The left side of the screen will now show the 

name of the file entered in Step 2 resident on 

disk.

Using a Configuration File

 

Already on Disk

To download or edit a previously saved 

Configuration File you can use the “File” button 

on the SDY Configuration Screen to bring up a file 

from your hard disk.

To use a configuration file already on disk:

1.  From the Configuration Program Main Screen, 

click on the “File” button to bring up the File 

Management portion of the program.

2.  Use the Explorer-like file display to locate 

the file to be retrieved, and click on the file to 

highlight it.

3.  Click on the “Quit File” button.

 

 

The Configuration Screen will change to show 

the parameters entered into the retrieved file.  

The parameters can now be edited and/or 

downloaded into the memory of a connected 

SDY.

Saving the SDY Configuration

 

File to Disk

This is an optional procedure.  You do not have 

to save the file to disk in order to download the 

file into SDY memory.  Use this procedure to save 

information on the configuration of your SDY for 

downloading into other SDY transmitters, or for 

record-keeping purposes, etc.

To save the SDY configuration files to disk:

1.  Click on the “File” button.  This brings up an 

Explorer-like window on the left area of the 

screen.

2.  Enter the file name that you wish to save in 

the “Selected File Name” box.

 

This will cause the “Prog” button to become 

available.  Click “Prog”, and the software will 

download the parameters on the PC into the 

nonvolatile memory of the connected SDY. 

 

Status of the downloading is shown in the 

upper left corner of the screen.  When 

completed, the program beeps.

Note:

 

Changing the settings on the Configuration 

Screen does not change SDY parameters 

until

 the Configuration File is downloaded to 

SDY memory as described in Step 3 above. 

 

Any time the SDY settings are changed, the 

configuration date will change to reflect the 

date the new settings were entered.

Printing Saved Configurations

1.  Click on the “File” button. This brings up an 

Explorer-like window on the left area of the 

screen.

2.  Navigate to the save file you want to print and 

click on it.

3.  Click on the “Print” button.

Note:

 

Printing saved configurations must be done 

when the Explorer-like file window is up. 

Содержание SDY

Страница 1: ...a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual SDY PC Programmable Signal Isolator Converter with Display No 235 770 00G...

Страница 2: ...tion File from an SDY 10 Setting Output Damping 10 Trimming SDY Output 10 Scaling the SDY Output 11 Setting the Display 11 Trimming the Input 12 Creating a Custom Linearization Table 12 Installation 1...

Страница 3: ...ile 2 wire loop powered PC Programmable Signal Isolator Converter that accepts current or voltage input and provides an isolated proportional 4 20mA output See Figure 1 for a list of accommodated inpu...

Страница 4: ...asured across 250 resistor Power Supply Effect 0 002 of span per 1V change Over Voltage Performance Continued Protection 48V maximum on output 48V reverse polarity protection on output Maximum Input O...

Страница 5: ...DN mounting will fit the TS 32 DIN rail and the TS 35 DIN rail FL Mounting flanges on HP suitable for relay track or screw mounting FLD Mounting flanges on HP suitable for 3 relay track mounting A suf...

Страница 6: ...nit tagging input type and range settings and output zero span trim Prior to shipment our team of skilled technicians subjects every SDY to rigorous testing Every product Moore Industries manufactures...

Страница 7: ...26 CAUTION MOORE INDUSTRIES ISOLATING CABLE PROVIDES A GALVANIC BARRIER BETWEEN THE TRANSMITTER AND THE PC CONFIGURING IT IT IS NOT NECESSARY TO USE AN ISOLATING CABLE BUT FAILURE TO DO SO MAY RESULT...

Страница 8: ...tion of the screen will be blank and the Communication indicator will show steady ON as opposed to blinking During setup the SDY tests the availability of COM Ports 1 through 4 in your system The firs...

Страница 9: ...DY Saving the SDY Configuration File to Disk This is an optional procedure You do not have to save the file to disk in order to download the file into SDY memory Use this procedure to save information...

Страница 10: ...e box to the right of the Damping sec area and type in a number between 0 and 20 032 This number is the number of seconds that the sensor s value will be averaged over Trimming SDY Output The SDY has...

Страница 11: ...u in Figure 4 and the radio button on Figure 5 both have Input selected then Display Zero will match Input Zero and Display Full will match Input Full Figure 5 Use the Display radio button to switch f...

Страница 12: ...the table fields to set values for input and output from the transmitter s intended application Use the Up Down Left and Right arrow keys on the PC keyboard to move the cursor among the cells in the t...

Страница 13: ...points but the first and last points in the curve always default to the 0 and 100 input scale input range If you decide not to use all 85 points you must change the number of points in the Points fie...

Страница 14: ...Ground Wiring Practices Moore Industries recommends the following ground wiring practices Any Moore Industries product in a metal case or housing should be grounded The protective earth conductor must...

Страница 15: ...Display Figure 12 Connecting the HP Housed SDY PS PS 1 2 3 4 SDY 10 278 MA 10 42Vdc POWER SOURCE CURRENT METER CALIBRATED 0 50mA CURRENT SOURCE I I CALIBRATED 0 10V VOLTAGE SOURCE V V PS PS 1 2 3 4 SD...

Страница 16: ...ions of the explosion proof BH housing for the SDY unit 84mm 3 30 in 118mm 4 65 in 130 mm 5 12 in 112mm 4 40 in 82 6 mm 3 25 in 64mm 2 50 in INSTRUMENT TAG 116 mm 4 56 in 27mm 1 05 in CONDUIT FITTING...

Страница 17: ...le Signal Isolator Converter with Display FRONT VIEW SIDE VIEW 61mm 2 4 in 83mm 3 25 in 62mm 2 45 in 64mm 2 50 in 66mm 2 58 in 76mm 3 00 in 43mm 1 70 in 18mm 70 in PS PS 1 2 3 4 SDY 16 203 MA Figure 1...

Страница 18: ...Ex nA IIC Ex nA IIC When installed as Division 2 equipment the SDY shall be mounted within a tool secured enclosure which meets the requirements of ANSI ISA 61010 1or C22 2 No 1010 1 and be capable of...

Страница 19: ...ons Zone 0 Ex ia IIC The SDY shall be installed in an enclosure which maintains an ingress protection rating of at least IP20 The communications port shall be programmed through Moore Industries Cable...

Страница 20: ...led and supplied with the correct power SDY transmitters begin to operate Depending upon environmental conditions they can be expected to continue to operate unattended for extended periods of time Ma...

Страница 21: ...he installation diagram for the SDY carrying the intrinsically safe option It also includes guidelines for setting up zener barriers necessary in these types of applications These diagrams must be use...

Страница 22: ...SDY 22 The Interface Solution Experts PC Programmable Signal Isolator Converter with Display...

Страница 23: ...SDY The Interface Solution Experts 23 PC Programmable Signal Isolator Converter with Display...

Страница 24: ...SDY 24 The Interface Solution Experts PC Programmable Signal Isolator Converter with Display...

Страница 25: ...ginal Buyer only and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This p...

Отзывы: