SDY

The Interface Solution Experts   13

PC-Programmable Signal 

Isolator/Converter with Display

5.  Use the “Restore” button to revert to the table 

stored in the SDY’s memory.

Caution: 

Restoring the configuration file erases any values 

in the table, overwriting them with whatever is 

stored in the most recent file.

6.  Use the “EGU” field to set the Engineering 

units of the readout from the main window 

when connected to the Configuration 

Program.

7.  Set the “Output Format” field to the desired 

resolution using the pull-down menu.

8.  Enter the number of points to use to constitute 

the Linearization Table in the “Points” field.

The Rules for Custom Linearization:

•  The difference between any consecutive 

values in the table (in either column) 

must be less than 50% of the entire 

configured range.

•  One “Output EGU” value per “Input mV” 

value only.

•  It is not necessary to use all 85 

available points, but the first and last 

points in the curve always default to the 

0% and 100% input scale (input range).

•  If you decide not to use all 85 points, 

you must change the number of points 

in the “Points” field to the number you 

wish to use.

Note:

 

Moore Industries suggests filling in the EGU 

(Engineering Units), then the number of points, and 

finally the values in the table.

9.  When the table is complete, click on the 

“QuitTabl” button and answer “Yes” to the 

following dialog (or something similar).

Figure 8.  Save File Dialog Box

 

  

10.  Click on the “Prog” (Program) button to 

download the linearization table settings into 

the transmitter memory.

CAUTION:

 

Any time a connected SDY is “programmed” 

by downloading a Configuration File into memory, 

ALL of the configuration parameters resident

 

in the transmitter memory at the time of the 

download are OVERWRITTEN. 

 

This includes things like: tag name, calibration 

date, trim values, etc. 

 

Once a transmitter’s memory is “erased”

 

in this fashion, the old operating parameters 

are unrecoverable, and will have to be 

regenerated from scratch if needed again.

Содержание SDY

Страница 1: ...a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual SDY PC Programmable Signal Isolator Converter with Display No 235 770 00G...

Страница 2: ...tion File from an SDY 10 Setting Output Damping 10 Trimming SDY Output 10 Scaling the SDY Output 11 Setting the Display 11 Trimming the Input 12 Creating a Custom Linearization Table 12 Installation 1...

Страница 3: ...ile 2 wire loop powered PC Programmable Signal Isolator Converter that accepts current or voltage input and provides an isolated proportional 4 20mA output See Figure 1 for a list of accommodated inpu...

Страница 4: ...asured across 250 resistor Power Supply Effect 0 002 of span per 1V change Over Voltage Performance Continued Protection 48V maximum on output 48V reverse polarity protection on output Maximum Input O...

Страница 5: ...DN mounting will fit the TS 32 DIN rail and the TS 35 DIN rail FL Mounting flanges on HP suitable for relay track or screw mounting FLD Mounting flanges on HP suitable for 3 relay track mounting A suf...

Страница 6: ...nit tagging input type and range settings and output zero span trim Prior to shipment our team of skilled technicians subjects every SDY to rigorous testing Every product Moore Industries manufactures...

Страница 7: ...26 CAUTION MOORE INDUSTRIES ISOLATING CABLE PROVIDES A GALVANIC BARRIER BETWEEN THE TRANSMITTER AND THE PC CONFIGURING IT IT IS NOT NECESSARY TO USE AN ISOLATING CABLE BUT FAILURE TO DO SO MAY RESULT...

Страница 8: ...tion of the screen will be blank and the Communication indicator will show steady ON as opposed to blinking During setup the SDY tests the availability of COM Ports 1 through 4 in your system The firs...

Страница 9: ...DY Saving the SDY Configuration File to Disk This is an optional procedure You do not have to save the file to disk in order to download the file into SDY memory Use this procedure to save information...

Страница 10: ...e box to the right of the Damping sec area and type in a number between 0 and 20 032 This number is the number of seconds that the sensor s value will be averaged over Trimming SDY Output The SDY has...

Страница 11: ...u in Figure 4 and the radio button on Figure 5 both have Input selected then Display Zero will match Input Zero and Display Full will match Input Full Figure 5 Use the Display radio button to switch f...

Страница 12: ...the table fields to set values for input and output from the transmitter s intended application Use the Up Down Left and Right arrow keys on the PC keyboard to move the cursor among the cells in the t...

Страница 13: ...points but the first and last points in the curve always default to the 0 and 100 input scale input range If you decide not to use all 85 points you must change the number of points in the Points fie...

Страница 14: ...Ground Wiring Practices Moore Industries recommends the following ground wiring practices Any Moore Industries product in a metal case or housing should be grounded The protective earth conductor must...

Страница 15: ...Display Figure 12 Connecting the HP Housed SDY PS PS 1 2 3 4 SDY 10 278 MA 10 42Vdc POWER SOURCE CURRENT METER CALIBRATED 0 50mA CURRENT SOURCE I I CALIBRATED 0 10V VOLTAGE SOURCE V V PS PS 1 2 3 4 SD...

Страница 16: ...ions of the explosion proof BH housing for the SDY unit 84mm 3 30 in 118mm 4 65 in 130 mm 5 12 in 112mm 4 40 in 82 6 mm 3 25 in 64mm 2 50 in INSTRUMENT TAG 116 mm 4 56 in 27mm 1 05 in CONDUIT FITTING...

Страница 17: ...le Signal Isolator Converter with Display FRONT VIEW SIDE VIEW 61mm 2 4 in 83mm 3 25 in 62mm 2 45 in 64mm 2 50 in 66mm 2 58 in 76mm 3 00 in 43mm 1 70 in 18mm 70 in PS PS 1 2 3 4 SDY 16 203 MA Figure 1...

Страница 18: ...Ex nA IIC Ex nA IIC When installed as Division 2 equipment the SDY shall be mounted within a tool secured enclosure which meets the requirements of ANSI ISA 61010 1or C22 2 No 1010 1 and be capable of...

Страница 19: ...ons Zone 0 Ex ia IIC The SDY shall be installed in an enclosure which maintains an ingress protection rating of at least IP20 The communications port shall be programmed through Moore Industries Cable...

Страница 20: ...led and supplied with the correct power SDY transmitters begin to operate Depending upon environmental conditions they can be expected to continue to operate unattended for extended periods of time Ma...

Страница 21: ...he installation diagram for the SDY carrying the intrinsically safe option It also includes guidelines for setting up zener barriers necessary in these types of applications These diagrams must be use...

Страница 22: ...SDY 22 The Interface Solution Experts PC Programmable Signal Isolator Converter with Display...

Страница 23: ...SDY The Interface Solution Experts 23 PC Programmable Signal Isolator Converter with Display...

Страница 24: ...SDY 24 The Interface Solution Experts PC Programmable Signal Isolator Converter with Display...

Страница 25: ...ginal Buyer only and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This p...

Отзывы: