10   The Interface Solution Experts

PC-Programmable Signal 

Isolator/Converter with Display

Loading a Configuration File From 

a Connected SDY

To edit or view a Configuration File in the nonvolatile 

memory of a connected unit, you can use the “Get 
Setup” function of the Configuration program.

Note:

 

Whenever a unit is correctly connected to your 

PC, the “SDY Status” section of the Configuration 

Screen will show the configuration data already 

stored in unit memory.

To load a configuration file from a SDY, connect a 

powered SDY and click “Get Setup”.

 

The editable fields of the SDY Configuration Screen 

will change to match the data shown in the “Status” 
portion of the screen.

Setting Output Damping

To lessen the impact of your sensor’s step increases 

and decreases, you may want to set the damping 

time, which will cause the SDY to average out 

fluctuations over the set amount of time.

 

Setting the damping time is simple; simply click

on the damping value bar under the “Output”

portion of the screen (in the bottom-right corner),

or click on the box to the right of the

“Damping(sec)” area and type in a number

between 0 and 20.032. This number is the number

of seconds that the sensor’s value will be

averaged over.

Trimming SDY Output

The SDY has a function that allows precise control

over its output. Note that to activate this function, a

unit must be connected in the setup to a current

meter, as shown in Figure 2.

 

To trim SDY output:

1. Set all unit parameters on the SDY 

Configuration Screen as required for your 

intended application. Click “Stop” to stop 

measurement.

2. Click “Out Trim”.

3. Select and move the “Output Zero” or the 

“Output Full” slide bar to adjust the SDY output.  

  Monitor the output with a calibrated current 

meter or with a voltmeter measuring the drop 

across a precision, 250 Ohm resistor

 

(see Figure 2).

4. When both zero and full scale have been 

adjusted to satisfaction, press “Quit Trim”, then 

“Prog” to program the SDY with the new trim 

values.

Note: 

 

Changing the settings shown on the screen in 

“Trim” mode DOES NOT CHANGE THE UNIT’S 

OPERATING PARAMETERS, it only updates 

the screen. The settings are saved to nonvolatile 

memory by using the “Prog” function.

The “SDY Status” area of the

Configuration Screen will reflect the new

output settings being downloaded into unit

memory.

Содержание SDY

Страница 1: ...a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual SDY PC Programmable Signal Isolator Converter with Display No 235 770 00G...

Страница 2: ...tion File from an SDY 10 Setting Output Damping 10 Trimming SDY Output 10 Scaling the SDY Output 11 Setting the Display 11 Trimming the Input 12 Creating a Custom Linearization Table 12 Installation 1...

Страница 3: ...ile 2 wire loop powered PC Programmable Signal Isolator Converter that accepts current or voltage input and provides an isolated proportional 4 20mA output See Figure 1 for a list of accommodated inpu...

Страница 4: ...asured across 250 resistor Power Supply Effect 0 002 of span per 1V change Over Voltage Performance Continued Protection 48V maximum on output 48V reverse polarity protection on output Maximum Input O...

Страница 5: ...DN mounting will fit the TS 32 DIN rail and the TS 35 DIN rail FL Mounting flanges on HP suitable for relay track or screw mounting FLD Mounting flanges on HP suitable for 3 relay track mounting A suf...

Страница 6: ...nit tagging input type and range settings and output zero span trim Prior to shipment our team of skilled technicians subjects every SDY to rigorous testing Every product Moore Industries manufactures...

Страница 7: ...26 CAUTION MOORE INDUSTRIES ISOLATING CABLE PROVIDES A GALVANIC BARRIER BETWEEN THE TRANSMITTER AND THE PC CONFIGURING IT IT IS NOT NECESSARY TO USE AN ISOLATING CABLE BUT FAILURE TO DO SO MAY RESULT...

Страница 8: ...tion of the screen will be blank and the Communication indicator will show steady ON as opposed to blinking During setup the SDY tests the availability of COM Ports 1 through 4 in your system The firs...

Страница 9: ...DY Saving the SDY Configuration File to Disk This is an optional procedure You do not have to save the file to disk in order to download the file into SDY memory Use this procedure to save information...

Страница 10: ...e box to the right of the Damping sec area and type in a number between 0 and 20 032 This number is the number of seconds that the sensor s value will be averaged over Trimming SDY Output The SDY has...

Страница 11: ...u in Figure 4 and the radio button on Figure 5 both have Input selected then Display Zero will match Input Zero and Display Full will match Input Full Figure 5 Use the Display radio button to switch f...

Страница 12: ...the table fields to set values for input and output from the transmitter s intended application Use the Up Down Left and Right arrow keys on the PC keyboard to move the cursor among the cells in the t...

Страница 13: ...points but the first and last points in the curve always default to the 0 and 100 input scale input range If you decide not to use all 85 points you must change the number of points in the Points fie...

Страница 14: ...Ground Wiring Practices Moore Industries recommends the following ground wiring practices Any Moore Industries product in a metal case or housing should be grounded The protective earth conductor must...

Страница 15: ...Display Figure 12 Connecting the HP Housed SDY PS PS 1 2 3 4 SDY 10 278 MA 10 42Vdc POWER SOURCE CURRENT METER CALIBRATED 0 50mA CURRENT SOURCE I I CALIBRATED 0 10V VOLTAGE SOURCE V V PS PS 1 2 3 4 SD...

Страница 16: ...ions of the explosion proof BH housing for the SDY unit 84mm 3 30 in 118mm 4 65 in 130 mm 5 12 in 112mm 4 40 in 82 6 mm 3 25 in 64mm 2 50 in INSTRUMENT TAG 116 mm 4 56 in 27mm 1 05 in CONDUIT FITTING...

Страница 17: ...le Signal Isolator Converter with Display FRONT VIEW SIDE VIEW 61mm 2 4 in 83mm 3 25 in 62mm 2 45 in 64mm 2 50 in 66mm 2 58 in 76mm 3 00 in 43mm 1 70 in 18mm 70 in PS PS 1 2 3 4 SDY 16 203 MA Figure 1...

Страница 18: ...Ex nA IIC Ex nA IIC When installed as Division 2 equipment the SDY shall be mounted within a tool secured enclosure which meets the requirements of ANSI ISA 61010 1or C22 2 No 1010 1 and be capable of...

Страница 19: ...ons Zone 0 Ex ia IIC The SDY shall be installed in an enclosure which maintains an ingress protection rating of at least IP20 The communications port shall be programmed through Moore Industries Cable...

Страница 20: ...led and supplied with the correct power SDY transmitters begin to operate Depending upon environmental conditions they can be expected to continue to operate unattended for extended periods of time Ma...

Страница 21: ...he installation diagram for the SDY carrying the intrinsically safe option It also includes guidelines for setting up zener barriers necessary in these types of applications These diagrams must be use...

Страница 22: ...SDY 22 The Interface Solution Experts PC Programmable Signal Isolator Converter with Display...

Страница 23: ...SDY The Interface Solution Experts 23 PC Programmable Signal Isolator Converter with Display...

Страница 24: ...SDY 24 The Interface Solution Experts PC Programmable Signal Isolator Converter with Display...

Страница 25: ...ginal Buyer only and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This p...

Отзывы: