background image

XG0128

Page 8

M38ODV-ST Direct Vented Fireplace

Finishing Around the Fireplace

Combustible mantels and mouldings may be safely installed over the top
and on the front of the fireplace provided that they do not project
beyond shaded area shown in 

Figure 11a

. Side wall clearances are 0".

Combustible surrounds may be installed with 0" clearance to the side of
the fireplace as shown in 

Figure 11b

.

Fireplace Facing

When selecting the finish material for your fireplace, it is important to
remember the following: 

TRIMS MUST NOT BE OBSTRUCTED IN

ANY WAY - to do so restricts the air supply for the control
compartments and heat exchanger it also prevents access for
servicing controls.

The face of the fireplace may be painted to match the room decor,
provided you use a heat-resistant paint.  Decorative facing must not
extend past the fireplace opening at all, because it will interfere with the
access to retainers for removal of glass door.

Mantels & Surrounds

NOTE:

 National Canadian Gas Association mantel test requirements

are for fire hazard prevention to combustible materials.

New technology, to meet consumer and government demands for the
wise use of energy, has prompted us to manufacture many models of
fireplaces which are hot, fuel and energy efficient.

Please be aware; temperatures over the mantel will rise above normal
room temperature and walls above fireplace may be hot to touch.

We recommend careful consideration be given to the effects of
elevated mantel temperatures which may be in excess of product
design, for example: candles, plastic or pictures. This can cause
melting, deformation, discoloration or premature failure of T.V. and
radio components.

Figure 11b.

 Combustible surrounds.

Figure 11a.

 Combustible mantles and facings.

Painting:

Special care is recommended by the Master Painters and Decorators
Association, when painting the fireplace surrounds, to select and apply
a quality 

Alkyd sealer

 prior to the applying of latex paints.  This is to

prevent leaching of water from evaporation and causing a brownish
staining effect to paint over coats.

Combustible construction
allowed in shaded area.

1 1/2" clearance to combustibles
(0" to standoffs on sides)

16
15
14
13
12
11
10

9
8
7
6
5
4
3
2
1
0

8

9

10

11

12

6

7

4

5

2

3

0

1

See fig. 11a/b for

shelf clearances

Installation

Installation

Installation

Installation

Installation

Installation Of Vertical Vent DV

„

Vertical Terminations must be installed:

minimum 2' (two feet) above the highest point where
vent passes through the roof.

minimum 6' (six feet) from a mechanical air inlet

minimum 18" (1 1/2 feet) from a parapet wall.

„

Maximum vent height is 30 feet above fireplace.
Note: Flame characteristics will change if the maximum vent height
is used.

„

Minimum clearances 2" from vent to all combustible materials must
be maintained.

A - Termination

PVTK-1

B - Flex sections

PFL-1 (12" section)

PFL-2 (24" section)

PFL-3 (36" section)

PFL-4 (48" section)

C - Solid sections

PEXT-1 (12" section)

PEXT-2 (24" section)

PEXT-3 (36" section)

PEXT-4 (48" section)

D - Support Ring & Plate

PSPXT-7 (8" dia.)

E - Firestop

PS-8 (8" dia.)

F - Roof Flashing

PRF-7 (1/12 - 7/12 pitch)

PRF-12 (7/12 - 12/12 pt.)

Содержание M38ODV-ST

Страница 1: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety ...

Страница 2: ...unit employs the optional Fan Kit it must be grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 1987 A manufactured mobile home OEM installation in the United States must conform with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or when such a standard is not applicable the Standard for Manufactur...

Страница 3: ...r any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance Figure 2a Framing dimensions 38 C C 17 1 8 Ø8 Ø5 For protection against freezing temperatures it is recommended that outer walls of the chase be insulated with a vapour barrier This will reduce the possibility of a cold air convection current on the ...

Страница 4: ...alshutoffvalveduringanypressuretestingof the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Installation Vent Installation Thissectioncoverstheinstallationofdirectventingandterminations For a detailed diagram of allowed termination locations see Appendix B InstallationRequirements The M38ODV ST fireplace uses premium venting components with 5 inner dia 8 outer di...

Страница 5: ... 12 12 MOSR 1 Frame the termination opening to 12 x 12 2 Fasten the MSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MSR frame as shown here and attach by screwing through the four pilot holes in the termination PTKOG 1 Ensure that the two long mounting brackets are facing the bottom of the termination See inset This will provide more heat p...

Страница 6: ...ableinstallation ExampleB AcceptableInstallation If the vertical dimension from the hearth is 66 and the horizontal run to the wall flange of the vent termination is 30 this would be anacceptableinstallation ExampleC UnacceptableInstallation If the vertical dimension from the floor of the fireplace is 48 and the horizontal run to the wall flange of the vent termination is 84 this would NOT be an a...

Страница 7: ...llation 48 Hearth Flex Section Termination Exterior Wall 126 30 Max Solid Section w 90 Elbow Heat Shield Hearth Flex Section Solid Section w 90 Elbow Termination Exterior Wall 126 150 max Heat Shield Heat Shields Due to high flue temperatures heat shields are required on all M38ODV ST installations at the point where the venting passes through the wall to connect to the termination Using the heat ...

Страница 8: ... effects of elevated mantel temperatures which may be in excess of product design forexample candles plasticorpictures Thiscancause melting deformation discoloration or premature failure of T V and radiocomponents Figure 11b Combustible surrounds Figure 11a Combustible mantles and facings Painting Special care is recommended by the Master Painters and Decorators Association whenpaintingthefireplac...

Страница 9: ... slots in the bottom door rail See figure 14 Ensure that a good seal is maintained Figure 14 Installing Glass Door Glass door and frame Door surround Tab B Slot A Magnet Pull bottom of door surround outwards and upwards Machine Screws Door Rail Tabs Installation Figure 12b Completed Installation Figure 12a Log Installation Installing the Logs and Embers Bottom Logs The M38ODV ST is supplied with f...

Страница 10: ...ent The M38ODV ST is equipped with an adjustable burner allowing you to raise or lower the flames To adjust the flames locate the black knob marked Hi Lo in the centre of the gas control valve See Figure 15 The front burners are not adjustable To raise the flame height turn the black knob located behind the lower trim counterclockwise To lower the flame height turn clockwise ...

Страница 11: ...er s instructions To Turn Off Gas To Appliance Operation Model M38ODV ST 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Replace trim 1 Turn off remote switch 2 Removelowertrim 1 STOP Read the safety information above on this label 2 Removelowertrims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including ...

Страница 12: ...fully and clean it with non abrasive glass cleaners One of the most effective products is Kel Kem Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a white substance on combustion chamber walls This can easily be removed by following the steps described above Use a vacuum cleaner or whisk broom to keep the control compart ment burner and firebox free from ...

Страница 13: ...Page 13 XG0128 M38ODV ST Direct Vented Fireplace Appendix A Spare Parts Accessories 2 3 ...

Страница 14: ...liancesaredesignedtoburngasonly Burningconventionalfireplacefuelssuchaswood coaloranyothersolidfuelwillcausedamagetotheGasAppliance willproduceexcessivetemperaturesandwillresultinafirehazard Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobligation andpurchaser sexclusiveremedyunderthisWarranty underanyotherwarranty expressed orimplied orincontract tortorotherwise sha...

Страница 15: ...Page 15 XG0128 M38ODV ST Direct Vented Fireplace Notes ...

Страница 16: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0128 Rev 0102 2005 ...

Отзывы: