M38ODV-ST Direct Vented Fireplace

Installation

Top Vent Venting Runs

Before you install any venting, you must determine whether the venting
run will be acceptable. Unacceptable venting can affect the fireplace's
combustion.

„

for installations with horizontal venting runs of 0-16 feet, use the
vent graph, as described below

„

the maximum horizontal vent run is 16 feet.

The Venting Graph

Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the from the fireplace flue
collar to the wall flange of the termination. Plot on the Venting Graph
(Fig. 4) with an 'X'.

If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 72", and the horizontal
run to the wall flange of the vent termination is 120", this would be
an acceptable installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 66" and the horizontal
run to the wall flange of the vent termination is 30", this would be
an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 48" and
the horizontal run to the wall flange of the vent termination is 84",

this would NOT be an  acceptable installation.

Installation Of  Top Vent DV

A complete 

M38ODV-ST

 vent system may comprise up to six different

types of components:

A - Termination

PTO-3 (3" length)

PTO-3F (3" length)

B - Stucco Kits

MSR (stucco frame)

MOSR (stucco can)

C - Flex sections

PFL-1 (12" section)

PFL-2 (24" section)

PFL-3 (36" section)

PFL-4 (48" section)

D - Solid sections

PEXT-1 (12" section)

PEXT-2 (24" section)

PEXT-3 (36" section)

PEXT-4 (48" section)

E - 90° elbow

PEL-90

     90° elbow

PEL-90

     90° elbow

PEL-90

F - Offset Box

DVST-CNT

Figure 4.

 Venting Graph.

Height to center

of vent pipe.

Hearth

1

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9 10 11 12 13 14 15 16

Vent may not terminate

in shaded area.

Vent  

terminate

in this area.

may

Vent Rise (feet)

Vent Run (feet)

Содержание M38ODV-ST

Страница 1: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety ...

Страница 2: ...unit employs the optional Fan Kit it must be grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 1987 A manufactured mobile home OEM installation in the United States must conform with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or when such a standard is not applicable the Standard for Manufactur...

Страница 3: ...r any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance Figure 2a Framing dimensions 38 C C 17 1 8 Ø8 Ø5 For protection against freezing temperatures it is recommended that outer walls of the chase be insulated with a vapour barrier This will reduce the possibility of a cold air convection current on the ...

Страница 4: ...alshutoffvalveduringanypressuretestingof the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Installation Vent Installation Thissectioncoverstheinstallationofdirectventingandterminations For a detailed diagram of allowed termination locations see Appendix B InstallationRequirements The M38ODV ST fireplace uses premium venting components with 5 inner dia 8 outer di...

Страница 5: ... 12 12 MOSR 1 Frame the termination opening to 12 x 12 2 Fasten the MSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MSR frame as shown here and attach by screwing through the four pilot holes in the termination PTKOG 1 Ensure that the two long mounting brackets are facing the bottom of the termination See inset This will provide more heat p...

Страница 6: ...ableinstallation ExampleB AcceptableInstallation If the vertical dimension from the hearth is 66 and the horizontal run to the wall flange of the vent termination is 30 this would be anacceptableinstallation ExampleC UnacceptableInstallation If the vertical dimension from the floor of the fireplace is 48 and the horizontal run to the wall flange of the vent termination is 84 this would NOT be an a...

Страница 7: ...llation 48 Hearth Flex Section Termination Exterior Wall 126 30 Max Solid Section w 90 Elbow Heat Shield Hearth Flex Section Solid Section w 90 Elbow Termination Exterior Wall 126 150 max Heat Shield Heat Shields Due to high flue temperatures heat shields are required on all M38ODV ST installations at the point where the venting passes through the wall to connect to the termination Using the heat ...

Страница 8: ... effects of elevated mantel temperatures which may be in excess of product design forexample candles plasticorpictures Thiscancause melting deformation discoloration or premature failure of T V and radiocomponents Figure 11b Combustible surrounds Figure 11a Combustible mantles and facings Painting Special care is recommended by the Master Painters and Decorators Association whenpaintingthefireplac...

Страница 9: ... slots in the bottom door rail See figure 14 Ensure that a good seal is maintained Figure 14 Installing Glass Door Glass door and frame Door surround Tab B Slot A Magnet Pull bottom of door surround outwards and upwards Machine Screws Door Rail Tabs Installation Figure 12b Completed Installation Figure 12a Log Installation Installing the Logs and Embers Bottom Logs The M38ODV ST is supplied with f...

Страница 10: ...ent The M38ODV ST is equipped with an adjustable burner allowing you to raise or lower the flames To adjust the flames locate the black knob marked Hi Lo in the centre of the gas control valve See Figure 15 The front burners are not adjustable To raise the flame height turn the black knob located behind the lower trim counterclockwise To lower the flame height turn clockwise ...

Страница 11: ...er s instructions To Turn Off Gas To Appliance Operation Model M38ODV ST 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Replace trim 1 Turn off remote switch 2 Removelowertrim 1 STOP Read the safety information above on this label 2 Removelowertrims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including ...

Страница 12: ...fully and clean it with non abrasive glass cleaners One of the most effective products is Kel Kem Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a white substance on combustion chamber walls This can easily be removed by following the steps described above Use a vacuum cleaner or whisk broom to keep the control compart ment burner and firebox free from ...

Страница 13: ...Page 13 XG0128 M38ODV ST Direct Vented Fireplace Appendix A Spare Parts Accessories 2 3 ...

Страница 14: ...liancesaredesignedtoburngasonly Burningconventionalfireplacefuelssuchaswood coaloranyothersolidfuelwillcausedamagetotheGasAppliance willproduceexcessivetemperaturesandwillresultinafirehazard Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobligation andpurchaser sexclusiveremedyunderthisWarranty underanyotherwarranty expressed orimplied orincontract tortorotherwise sha...

Страница 15: ...Page 15 XG0128 M38ODV ST Direct Vented Fireplace Notes ...

Страница 16: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0128 Rev 0102 2005 ...

Отзывы: