H*38DF PRC Panorama Indoor Gas Fireplace
Page 10
XG0211 - 151126
Installation
Section 3-2:
INSTALLING A ROOF MOUNTED DIRECT VENT
TERMINATION (PVTK-1)
This section applies to installations where the direct vent termi-
nation will be roof mounted.
Section 3-2-1:
VENTING LAYOUT
Selection of components and details of venting lay out should
adhere to the following guidelines:
The maximum termination point is 32’ above the fireplace
(NOTE: if the maximum termination height is used, the flame
pattern may be affected).
The Vertical termination must be a minimum 2’ higher than
where the termination exits the roofing materials, (asphalt
shingles, cedar shakes, etc). This distance should be
measured from the high side of the roof slope where the
flue flashing intersects the roofing materials. (see
Figures
9 to 9c
).
Termination location must be a minimum 6’ from a mechanical
air inlet.
For a more detailed diagram of allowed termination locations,
see
Appendix A
.
A maximum of two offsets (each offset is made up of 2-90°
bends) may be made for vertical vent runs.
Firestops must be installed as required by National & local
codes.
Ensure all horizontal runs are supported with a minimum
of 3 supports per 10’ of venting.
Install all roof flashing and storm collars as shown.
Figure 9. Top vent, Roof mounted termination with no offset in vent run.
Figure 9a. Top vent, Roof mounted with 1 offset (1 offset= two 90° bends).
Figure 9b. Top vent, Roof mounted with 2 offsets (1 offset= two 90° bends).
Roof mounted Terminations
The following details are some possible configurations for Roof
mounted terminations.
Support ring
Support plate
Firestop
32’ max.
2’ min.
Obstacle
PVTK1
Termination
Support ring
Support plate
Firestop
32’ max.
2’ min.
PVTK1
Termination
Support straps
or
support plate & ring
2’ min.
Firestop
Firestop
Firestop
32’ max
Support plate
& ring
Obstacle
PVTK1
Termination