3.13 Range Expander of X-3000-ce-UW
1/3/02 53
Pneumatic Diagram
Parameter Setting and Adjustment
To set up parameters in the range expander menu, go to range expansion
[Range
Exp.]
under the setup menu and do the following:
1.
[RE Source]
(range expander source)
Select one of three modes of operation for the range expander:
Note:
The factory recommends the following setup:
• X-3000-ce-UW=
[OUTPUT]
or
[DIA.]
• D-3000-ce-UW=
[DIA.]
Note:
All remaining range expansion parameters must be set in
Tension off
mode.
2.
[Ranges]
Select the number of ranges in your system:
2, 3 or 4.
3. [Start No.]
Select the starting range number:
1, 2, 3 or 4.
This is the range used after a range expander reset, which occurs after the following
three conditions:
• Power has been applied to the controller
• Tension has been switched on (new roll)
• Controller has performed a splice operation.
Typical pneumatic connection
[NONE]
Range expander not used
[DIA]
Range expander runs under diameter control
[OUTPUT]
Range expander runs under output pressure control
1
Air supply, 6-8 bar
2
Air filter
3
I/P converter, 0-6 Bar
4
Emergency stop valve
5
Manometer
6
Range 1 valve
7
Range 2 valve
8
Range 3 valve
9
Range 4 valve
1
2
3
4
5
6
7
8
9
Y1
Y2
Y3
Y4
Y5
Brake
5u
0.3u
PR006.dsf