34 1/3/02
3 lnstallation and Setup
3.
[Softs Time]
(
Time delay to stop)
If a stop signal is used and there is a delay between the time that the stop signal has
been activated and the time that the machine reaches zero speed, enter the time as
follows.
To set the correct time:
a)
Run machine at maximum speed.
b)
Measure time from activation of stop to zero speed.
c)
Enter this time + 0.2 seconds in this parameter.
Note:
If this time is longer than 10 seconds, use a zero speed signal.
d)
Enter a short time when using a zero speed signal: minimum value is 0.1
seconds
4.
[Hold level]
(
Hold level)
When
[
Softstart]
signal is set high (Active high = +24 VDC), the controller
stores the output level, but continues to regulate until the
[Softs Time]
has run
out. If the time is set to the minimum value of 0.1 seconds, the output will change to
hold level after 0.1 seconds. (Hold level = stored level +%.) If a longer time is set up,
the output will change after that time. In hold mode, the output is at a constant hold
level.
To keep the roll in the same position in hold mode, the stored level is increased by
[Hold level]
to create a holding output.
Hold level
= Stored level.
Example of the output level in hold mode:
Hold Mode Menu: Hold level 100% =>
Stored level
Hold Mode Menu: Hold level 150% =>
Stored level + 50%
Diagnostic
Password
Setup Menu
Mode Menu
Run Mode
Amplifier
0/4mA
Language
Gain
Ratio
P Level
D Level
Softs Menu
Start Out
Softs Lev.
Softs Time
Hold Level
Anti Menu
Anti.Src.
Anti Max
Anti Min
Anti Slope
Splce Menu
Splice Src
Splice Del
Splice Lev
Splice Tim
WebBr Menu
Webbr Lev.
Webbr Time
Range Exp.
RE Source
Ranges
Start No.
Dn Level
Up Level
Range Time
Brake Menu
Range Dia Menu
Dia. Menu
Diamet.Src
P/Rev Roll
mm/Pulse
Min Diam.
Max Diam.
Fac. Diam
DF AutoSet
New Roll D
Diameter
Output2 Menu
Out2 Src
Out2 Slope
Out2 Scale
Out2 Off