![molex Brad HarshIO 600 Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/molex/brad-harshio-600/brad-harshio-600_user-manual_1824127038.webp)
HarshIO 600
•
38
•
IP67 MDR for EtherNET/IP
Assembly #101
– Input Process & Error Status Data
Input Process Data (56 bytes)
Bit
Offset (in byte)
7
6
5
4
3
2
1
0
00
C7
C6
C5
C4
C3
C2
C1
C0
01
PS7
PS6
PS5
PS4
PS3
PS2
PS1
PS0
02
CS7
CS6
CS5
CS4
CS3
CS2
CS1
CS0
03
reserved
OLUL
OVUL
UVUL
reserved
OLUB
OVUB
UVUB
04
reserved reserved reserved reserved
OTP3
OTP2
OTP1
OTP0
05
reserved reserved reserved reserved
MDR S3
MDR S2
MDR S1
MDR S0
06
MDR TD0
07
MDR TD1
08
MDR TD2
09
MDR TD3
10
MDR OS0
11
MDR OS1
12
MDR OS2
13
MDR OS3
Input data, information & Error status
Cx:
Channel (x = Channel number) as digital input - Pin2/Pin4
1: input activated
0: input disactivated
PSx:
Port Status (x = Port number) - state of the pin1 (L+)
1: Overload / short detected
0: No error
CSx:
Channel Status (x = Channel number)
– State of the Digital Output – Pin2/Pin4
1: short circuit detected
0: No error
UVx:
Under Voltage (x = UL or UB)
1: Under voltage detected
0: No error
OVx:
Over Voltage (x = UL or UB)
1: Over voltage detected
0: No error
OLx:
Over Load (x = UL or UB)
1: Over load detected
0: No error
OTPx:
Over Temperature (x = MDR port number)
This
error status indicates when one of the module’s port reaches the temperature >85°.
It is cleared when the port cools to the temperature <70°.
1: Over temperature detected
0: No error
Note!
If the temperature reaches 85° too frequently, the back label may be degraded due
to altered resin. But there is no negative impact. The module will keep operating
accurately
.
Содержание Brad HarshIO 600
Страница 10: ...HarshIO 600 10 IP67 MDR for EtherNET IP Overview The HarshIO module is consisted of three main parts ...
Страница 16: ...HarshIO 600 16 IP67 MDR for EtherNET IP ...
Страница 54: ...HarshIO 600 54 IP67 MDR for EtherNET IP Figure 13 7 ...
Страница 55: ...HarshIO 600 55 IP67 MDR for EtherNET IP Figure 13 8 ...