HarshIO 600
•
37
•
IP67 MDR for EtherNET/IP
EtherNet/IP Assembly instances
The I/O process data are available through the EtherNet/IP assembly instances. Below the list according to the
connection type.
Input
Assembly
Data length
(bytes)
Output
Assembly
Data length
(bytes)
Configuration
Assembly
Data length
(bytes)
EDS entry
Exclusive Owner
Digital I/O
101
14
103
16
105
2 (or 0 )
Exclusive Owner
Digital I/O & Diagnostic
102
90
104
17
105
2 (or 0 )
Exclusive Owner with Diagnostic data
Input Only
Digital Input
101
14
198
0
105
2 (or 0 )
Input Only
Digital Input & Diagnostic
102
90
198
0
105
2 (or 0 )
Input Only with Diagnostic data
Listen Only
Digital Input
101
14
199
0
105
2 (or 0 )
Listen Only
Digital Input & Diagnostic
102
90
199
0
105
2 (or 0 )
Listen Only with Diagnostic data
Note!
If your EtherNet/IP scanner configuration tool does not support the management of
EDS files, you may have to configure manually the assembly numbers to access
the process data.
– Example of HarshIO assembly setting
in Rockwell Automation RSLogix 5000 software
–