HarshIO 600
•
28
•
IP67 MDR for EtherNET/IP
Use of the rotaries
3 decimal rotary switches are located under the window and oriented as shown below.
“
x100 x10 x1
” labels
are printed below of the rotary (PCB silkscreen).
Note!
The module window shall be screwed with a torque of 0.3 Nm to ensure a correct
sealing to achieve IP67 rating and shall be closed during working operation.
The user shall check regularly that the torque of module window is respecting the
screwing value 0.3 Nm
The rotary switch position is only read at the boot of the HarshIO module. Any modification of the position will
require a power cycle (ON
OFF
ON) or a reset of the module The HarshIO module is out-of-box configured
with rotary position 000. This configuration corresponds to stored IP address mode 500 with DHCP mode
activated. When connecting to a network with a DHCP server, an IP address is automatically assigned to the
module. Assigning an IP address using 0xF5 TCP/IP Object allows defining permanently this IP address for
the following module startup. No rotary switches modification would be required. To change or set the IP
address, the operator has the possibility to use one of the following methods:
Mode
x100
rotary
x10
rotary
x1
rotary
Descriptions
Static Address
x
[0 to 2]
y
[0 to 9]
z
[1 to 9]
Overwrite the 4th byte of the IP address stored in non-volatile
memory.
IP Address: 192.168.1.xyz (xyz from 1 to 254) IP mask:
255.255.255.0 Gateway: 192.168.1.1
Note!
If the IP address is 192.168.1.1
then the gateway will be 0.0.0.0
Note!
When using static IP address mode,
the IP address is stored in the Flash memory
of the module.
DHCP Mode
(based on MAC
address)
4
0
0
HarshIO module gets its IP address, IP mask address and
gateway address according DHCP method based on MAC
address. It will send the DHCP request indefinitely until
receiving an IP
DHCP Mode
(based on Client
ID=”BRAD_xy”)
4
y
[0 to 9]
z
[1 to 9]
HarshIO module gets its IP address, IP mask address and
gateway address according DHCP method based on Client
ID=”BRAD_xy”.
It will send the DHCP request indefinitely until receiving an IP
(yz) in the range from 1 to 99 can be allocated
x100
x10
x1
Содержание Brad HarshIO 600
Страница 10: ...HarshIO 600 10 IP67 MDR for EtherNET IP Overview The HarshIO module is consisted of three main parts ...
Страница 16: ...HarshIO 600 16 IP67 MDR for EtherNET IP ...
Страница 54: ...HarshIO 600 54 IP67 MDR for EtherNET IP Figure 13 7 ...
Страница 55: ...HarshIO 600 55 IP67 MDR for EtherNET IP Figure 13 8 ...