All XVC-100 Series devices are mounted from the front, i.e. in a control
panel. The devices are fastened from the rear with the fixing clamps
supplied.
All XVC-100 Series devices can be operated at an ambient temperature of
up to 60°C (
"
Section 11 ). The ambient temperature stated applies to the
area in the direct vicinity of the lower connectors if the device is mounted
vertically with unimpeded air convection and a maximum operating height of
2000m above sea level.
The device can be mounted in an enclosure if the permissible ambient
temperature is observed. Provide a wall clearance of at least 50 mm on all
sides of the housing, so that sufficient air circulation is ensured. A minimum
clearance of 75 mm from active elements such as load current supply,
transformers etc. must be ensured.
Avoid the exposure of the membrane keyboard and display to direct
sunlight. The radiation from the sun (UV component) reduces the lifespan of
the LCD display.
The following must be ensured in order to prevent the
device from overheating during operation:
-
The cooling slots must always be free in order
to ensure the proper cooling of the system.
-
Avoid the exposure of the front and the display
to direct sunlight.
-
The mounting angle must not exceed ± 35°
from the vertical
Mounting in compliance with degree of protection IP65
requires the use of the conter frame .
Ensure that the seal is fitted correctly on the front
panel.