5.8 C
ONNECTION OF THE DIGITAL INPUT
- C
ONNECTOR
X 3
Connector Assignment for X 3
Connector X 3 - digital input
12-pole, WAGO multi-connector system MINI, RM 3.5 mm,
734-142
Counterpart: WAGO 734-112
Pin
No.
Assignment Function
1
I1.0/Cnt 0 Digital input 0 / Counter0 input
2
I1.1/Up-Dn Digital input 1 / Counter0 Up/Down
3
I1.2/Cnt 1 Digital input 2 / Counter1 input
4
I1.3/Up-Dn Digital input 3 / Counter1 Up/Down
5
I1.4/Int 0 Digital input 4 / Interrupt0 input
6
I1.5/Int 1 Digital input 5 / Interrupt1 input
7
I1.6/Incr A Digital input 6 / Incr. Ch A
8
I1.7/Incr B Digital input 7 / Incr. Ch B
9
I2.0/Incr N Digital input 8 / Incr. zero mark
10
I2.1/Incr Na Digital input 9 / Incr. zero mark active
11
0V
Signal Ground (ground potential)
12
0V
Signal Ground (ground potential)
X 3 input level
Function:Digital Inputs
Ten digital inputs are provided. These inputs enable 24 volt digital sensors,
counters and incremental encoders to be connected.
The input is designed for 24VDC. (
"
Section 11).
The digital inputs are not isolated, the input voltage refers to
ground (GND).
The debouncing of inputs is implemented via the software.
This function must be activated if required. (see also
Description of the function block libraries for XVC-100)