5.7 C
ONNECTION OF THE DIGITAL OUTPUT
- C
ONNECTOR
X 2
Connector Assignment for X 2
Connector X 2 - digital output
9-pole, WAGO multi-connector system MINI, RM 3.5 mm,
734-139
Counterpart: WAGO 734-109
Pin No.
Assignment Function
1
Q1.0
Digital output 0
2
Q1.1
Digital output 1
3
Q1.2
Digital output 2
4
Q1.3
Digital output 3
5
Q1.4
Digital output 4
6
Q1.5
Digital output 5
7
Q1.6
Digital output 6
8
Q1.7
Digital output 7
9
24VDC
+24VDC supply for DIG_OUT0-7
X 2 output level
Eight digital outputs are provided for 24VDC actuators. The power supply is
fed via a separate pin and is common for all outputs. Each output is
protected against short-circuits and reverse polarity. In the event of a fault,
this is detected by the output driver.
The load current for each digital output is 0.5A (
"
Section 11)
The digital outputs are not isolated.
It must be ensured that there is a good connection
between the reference potential (GND) for the
digital outputs and the GND of the XVC-100.
All 8 outputs are switched off if one of the outputs
has an overload! The overload is indicated and can
be read in the PLC user program.
The outputs can be used for switching inductive
loads. An external free-wheeling circuit must be
implemented for large inductances. (
"
Section11
).
Überwachung
+24VDC
DO_0
Last
=
Erde
GND Erde (Gehäuse)
Ground (housing) Ground
Load
Monitoring
1
9
For Immediate Delivery call KMParts.com at (866) 595-9616