XVC-100
Text Display PLC
Device Description XVC-100
Commissioning
Subject to technical modifications
Doc No. 92 23 100000 (06/2002)
© by Moeller GmbH
26
5.10 C
ONNECTION OF THE
CAN
INTERFACE
- C
ONNECTOR
X 6
The communication interface is defined in accordance with the CiA CAN
Specification V2.0 part B. The fully-integrated CAN unit supports the sending
and receiving of frames with an 11-bit Identifier. The type of configuration
selected depends on the software protocol. The baud rate can be selected in
a wide range, and only the standard CiA baud rates are implemented. The
XVC-100 is the master on the CAN bus.
CAN connector X 6
Sub-D 9 Pole male
Connect
or
Pin No.
Assignment Function
1
-
2
CAN LOW Negative data signal
3
GND
Signal Ground (ground potential)
4 -
5 -
6
GND
Signal Ground (ground potential)
7
CAN HIGH Positive data signal
8 -
9 -
Case
Case
Cable
shield
The CAN interface is not isolated.
The terminating resistor must be implemented externally,
e.g. in the connector, and is not part of the device.
The CAN connector is not provided with a supply for
third-party devices.
A detailed description of the wiring is provided in the
“XSoft” system description
5
9
4
8
3
7
2
6
1