![Moeller XVision XVC-100 Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/moeller/xvision-xvc-100/xvision-xvc-100_manual_1819399020.webp)
XVC-100
Text Display PLC
Device Description XVC-100
Commissioning
Subject to technical modifications
Doc No. 92 23 100000 (06/2002)
© by Moeller GmbH
20
5.6 C
ONNECTION OF THE DIGITAL INPUT
/
OUTPUT
- C
ONNECTOR
X 1
Connector Assignment for X 1
Connector X 1 - digital input / output
10-pole, WAGO multi-connector system MINI, RM 3.5 mm,
734-140
Counterpart: WAGO 734-110
Pin No.
Assignment Function
1
I0.0/Q0.0
Digital input/output 0
2
I0.1/Q0.1
Digital input/output 1
3
I0.2/Q0.2
Digital input/output 2
4
I0.3/Q0.3
Digital input/output 3
5
I0.4/Q0.4
Digital input/output 4
6
I0.5/Q0.5
Digital input/output 5
7
I0.6/Q0.6
Digital input/output 6
8
I0.7/Q0.7
Digital input/output 7
9
24VDC
+24VDC supply for DIG_I/O0-7
10
0V
Signal Ground (ground potential)
X 1 input / output level
24 VDC sensors and actuators can be connected to the digital
inputs/outputs. The inputs/outputs are configured in the user PLC program.
All inputs/outputs are outputs in their default configuration.
The input is designed for 24VDC. (
"
Section11).
The load current for each digital output is 0.5A
The digital inputs/outputs are not isolated.
All outputs are switched off if one of the outputs has an
overload! The overload is indicated and can be read in
the PLC user program.
All inputs/outputs are outputs in their default
configuration.
The outputs can be used for switching inductive loads.
An external free-wheeling circuit must be implemented
for large inductances. (
"
Section 11
).
+24VDC
DIO_0
Last
=
Erde
GND
GND
Erde (Gehäuse)
1 10
Ground (housing) Ground
Load
For Immediate Delivery call KMParts.com at (866) 595-9616