01/08 AWB2190-1430GB
Setting the functions with DIP
switches/jumpers
63
Activate phase reversal switch (pole 7)
Table 5:
Phase reversal and reversing function
Configure external outputs (pole 5 – 6, 8)
The RA-MO...4 provides two external inputs for connecting light
barriers, sensors, etc. Add-on functions are:
• Quick stop with a light barrier for both directions
• Quick stop and interlocked manual mode with both light
barriers for clockwise rotation (from version 2.2)
• Quick stop with one light barrier per direction of rotation
• Interlocked manual operation with one light barrier per
operating direction
• When using break contacts, inversion of the signals for internal
processing.
You can configure the external inputs through pins 5, 6 and 8 of
the DIP switch:
Table 6:
Sensors
Table 7:
Setting quick stop and interlocked manual mode
h
For this setting, the jumper on the right must be in its left
position (
a
fig. 64).
j
Danger!
Safety risk! The jumper positions and the setting of DIP
switch pole 7 must be changed only by trained persons
and only in accordance with this manual. Incorrect
settings will cancel the reversing starter’s interlock or
reverse the operating direction.
h
From version 2.2: If DIP switch pole 7 is set to 1 on a DOL
starter, the contactor is no longer actuated. DOL starters
work only with DIP switch pole 7 in position 0.
pole 7
Configuration
0
Reversing starter (factory setting)
1
Reversing starters and phases L1 and L3 reversed (phase
reversal)
pole 5
Configuration
0
Sensor signals through AS-Interface®, no add-on function
(factory setting)
1
When using sensors with break contacts:
Signals are inverted for internal processing; the original
signals are sent through AS-Interface®.
h
On RA-MO version 1.x only pole 6 has a function.
pole
Configuration for RA-MO from version…
6
8
V 2.2
V 2.1
V 1.x
0
0
No add-on function (factory setting)
1
0
For jumper setting
“reversing starter”:
A
column …V2.1
Quick stop
I3 enabled.
I3 is assigned to
both operating
directions, I4 has
no add-on function;
typical application
example: chain
discharger
–
With jumper setting DOL
starter:
Quick stop and interlocked
manual operation (edge-
controlled only), I3 and I4
enabled. I3 and I4 are
assigned to operating
direction FWD; typical
application: vertical sorter
with > 360° eccentric
0
1
Quick stop, I3 and I4 enabled.
I3 is assigned to operating direction FWD,
I4 is assigned to operating direction REV;
Typical application: Vertical sorter with
< 360° eccentric
–
1
1
Quick stop and interlocked manual operation, I3 and I4
enabled. I3 is assigned to operating direction Forward, I4 to
operating direction Reverse; typical example: Vertical sorter
with < 360 ° eccentric
Содержание Rapid Link
Страница 10: ...01 08 AWB2190 1430GB 6 ...
Страница 40: ...01 08 AWB2190 1430GB 36 ...
Страница 48: ...01 08 AWB2190 1430GB 44 ...
Страница 70: ...01 08 AWB2190 1430GB 66 ...
Страница 145: ...01 08 AWB2190 1430GB Parameterization with DrivesSoft 141 Figure 134 Example acceleration time ...
Страница 146: ...01 08 AWB2190 1430GB 142 ...
Страница 162: ...01 08 AWB2190 1430GB 158 ...