
First version
Rev 1.00
22 Sep 2016
Helios User Manual
35
Settings used to write command (0x8 = Open Cover) to the Helios:
Analyzing the data from the Helios:
An example of data read from the Helios is shown below. This first example shows data when the Helios has close to
zero incident power on the sensor, and no energy pulse has been measured recently. No commands have been sent
since the last power up. Other examples will be shown further below.
The data in EtherNet/IP Mode is “Little-Endian”, meaning the order of the bytes within a 2-byte or 4-byte integer has
the least significant byte at the end.
Example data:
Here is the data shown above (in Hex):
8E 00 00 00
02 01 80 96 98 00 10 27 00 00 10 27 64 00 E0 2E 64 00 3C 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 2A 00 00
00 1E 00 01 00 10 27 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
A full analysis of how to translate this data is shown above, see the “Registers and Commands” chapter.