MKS 937B Series Скачать руководство пользователя страница 44

937B Controller Instruction Manual 

pg. 44 

 

6.6.3  Power (including degas) Control of a Sensor using Serial 

Communication Commands 

Power to sensors can also be turned ON/OFF via serial communications. Commands for this are given in 
Section 9 under each gauge type.

 

Degas of a HC sensor can also be controlled via serial commands. The commands are given in Section 
9.8. 

6.7 

Leak Testing Using the 937B Controller

 

 

6.7.1  Leak test principle applied for the 937B

 

 

The Series 937B Controller offers a simple and inexpensive method for locating leaks in high vacuum 
systems. It is not intended to replace mass spectrometer leak detectors. Under ideal conditions, a Pirani 
sensor can detect leaks as small as 1x10

-4 

Torr l/s and the cold/hot cathode sensor can be used to 

detect leaks as small as 1x10

-7 

Torr l/s. 

 

The principle for detecting a leak with the 937B controller is based on the gas dependency of the 
pressure reading for the Pirani/Convection, hot or cold cathode. When different gases (such as helium or 
argon) enter into the vacuum system, a change in gas composition will lead to a ch

ange in “indicated 

pressure

”, indicating a leak in the system. For heat loss sensors this is due to thermal conductivity 

differences between gases and with hot or cold cathode sensors it is due to the difference in the 
ionization probability in the gases. 

 

Leak Test Mode will work with all sensors except the capacitance manometer, which is not gas 

dependent. The leak test mode and bar graph will not be displayed if the 937B Controller detects 
that the requested sensor for leak testing is a capacitance manometer. 

 

6.7.2 

Procedures for a leak test with the 937B 

 

1.  With the Controller ON, use the UP or DOWN keys to select the desired sensor (

must be a gas 

dependent sensor such as a Pirani, Convection Pirani, CC, or HC

) with the assistance of the 

Green LED. 

2.  Pump down the system and make sure the system is stabilized. 

3.  Press the LEAK CHECK key to display the leak bar graph on the LCD screen. Once the Leak 

Check is pressed, the pressure for the corresponding leak checking channel will turn blue. 

4.  Press BEEPER to provide audible assistance for leak checking. 

5.  Slowly and methodically probe with a small amount of leak checking gas such as He or Ar (

the 

probe gas must be different from the gas inside the chamber

). Flooding the leak with gas or 

moving the gas quickly past the leak can decrease effectiveness of the search since system time 
lags may be significant. 

6.  24-segment, centered-zero bar graph shows pressure changes in the system with greater 

sensitivity than the numerical display. The more the bars showing on the graph, the larger the 
leak size. The black bar at the center is zero. The green bar indicates a relatively slow leak, while 
the red bar indicates a large leak in the vacuum system. 

7.  If the pressure has drifted during the leak checking process, press the ZERO key to set the bar 

graph and beeper for a new background pressure. 

8.  To exit the leak checking mode, press the LEAK CHECK key. 

 

Содержание 937B Series

Страница 1: ...Series 937B Vacuum System Controller Operation and Maintenance Manual Instruction Manual p n 100016467 Rev F August 2020...

Страница 2: ...using Front Panel Control Button 42 6 6 2 Power including degas Control of a Sensor via 37 pin AIO D sub Connector 43 6 6 3 Power including degas Control of a Sensor using Serial Communication Command...

Страница 3: ...nd Installing AIO Module 87 10 3 Removing and Installing Profibus Control Module 88 10 4 Mounting the Controller 89 10 5 AC Power Cord 90 11 Maintenance and Service of MKS Vacuum Sensors 91 11 1 422 4...

Страница 4: ...ll advise you if the hazardous materials document is required When returning products to MKS be sure to package the products to prevent shipping damage Shipping damage on returned products due to inad...

Страница 5: ...erly Ground the Controller This product is grounded through the grounding conductor of the power cord To avoid electrical shock plug the power cord into a properly wired receptacle before connecting i...

Страница 6: ...voltages when on High voltage is present in the cable and a Cold Cathode sensor when the Controller is turned on Use the proper power source This product is intended to operate from a power source th...

Страница 7: ...2 to 100 of the measurement range of the head e g 1 Torr head is 2 0 x 10 3 to 1 0 x 10 0 Torr Allowed range within which a control sensor may switch on a Cold or Hot Cathode Pirani 5 0 x 10 4 to 9 5...

Страница 8: ...p for each channel up to two 2 wide range combination logarithmic outputs Output impedance 100 ohms Number of channels Up to 6 Front panel controls Power ON OFF switch keypad for setup and operationa...

Страница 9: ...and the total current requirement of operating sensor s must be 1 amp or less Pressure measurement ranges CC Cold Cathode 1 0 x 10 11 to 1 0 x 10 2 Torr 1 3 x 10 11 to 1 3 x 10 2 mbar 1 3 x 10 9 to 1...

Страница 10: ...at constant temperature CM 0 25 of indicated pressure at constant temperature Calibration gas CC HC Nitrogen Argon Pirani CP Air nitrogen Argon Helium CM Any gas independent Installation orientation C...

Страница 11: ...HC Pirani 0 to 50 C 32 to 122 F CP 10 to 50 C 50 to 122 F CM 0 to 50 C 32 to 122 F Maximum sensor bakeout temperature without cables CC Series 431 250 C 482 F when backshell subassembly removed otherw...

Страница 12: ...i BA 3x10 10 Torr Dimensions CC Series 431 and 422 2 2 6 3 in 56 160 mm Series 423 2 6 3 4 in 66 86 mm Mini BA 1 12X2 37 in 28 60 mm with 2 3 4 CF flange LPN 3 3X1 0 in 83 mm 25 with 2 3 4 CF flange c...

Страница 13: ...Power is OFF to HC CC CP PR sensor WAIT CC and HC startup delay Low EMIS The HC OFF due to low emission current CTRL OFF The HC or CC are turned OFF by the control channel or sensor PROT OFF The HC or...

Страница 14: ...button Pressure Range Convection Pirani Pirani Hot Cathode Cold Cathode Torr PatchZ Default HighR PatchZ Default HighR PatchZ Default HighR PatchZ Default HighR 103 X X0E 03 X XE 03 ATM ATM 102 X X0E...

Страница 15: ...cation Response Format CM and Piezo Diff Baratron Pirani Convection Hot Cathode Cold Cathode X XXXE X X XXXE X X XXE XX X XXE XX X XXE XX X XXE XX X XXE X Table 2 3 937B Serial Communication Response...

Страница 16: ...937B Controller Instruction Manual pg 16 3 Feature Control Locations and Dimensions Figure 3 1 937B Front Panel Figure 3 2 937B Rear Panel Example...

Страница 17: ...ndicating Active Channel 3 Liquid Crystal Display 4 Push Buttons for Menu Navigation 5 Power Switch 6 AIO Module 7 AC Power Inlet 8 RS232 485 Communication Port 9 Relay Output Port 10 Analog Output Po...

Страница 18: ...ormal pressure situations and initiating appropriate security measures using the relay set points Controlling system pressure by using the analog output as the input to an automatic pressure controlle...

Страница 19: ...sor combinations the Series 937B Vacuum System Controller can accommodate many unique requirements and applications It is designed with versatility and ease of use in mind with a large LCD screen that...

Страница 20: ...e is a longer time delay 100 msec due to the signal processing by the microprocessor There are also combined logarithmic analog outputs available By combining the sensors with different measurement ra...

Страница 21: ...ht arrow keys to lock or unlock the front panel controls or to display the lock status The front panel can also be locked or unlocked with serial communications commands See RS232 RS485 Communications...

Страница 22: ...play of a single channel is also available to ensure the pressure readings can be seen at a distance To enter this mode 1 While in the standard display mode press the UP or DOWN arrow key to select th...

Страница 23: ...for the controller and modules In addition the logarithmic linear analog output for individual channels and combined logarithmic analog output can be scaled by setting the DAC parameters Figure 6 3 93...

Страница 24: ...UP or DOWN arrow key to change the parameter value i e to change Pascal to mBar 4 Pressing the ENTER key at this point will restore the original parameter If the cursor is moved away from the paramet...

Страница 25: ...asting only 4 Baud Rate This sets the baud rate for serial communication Valid values are 9600 19200 38400 57600 115200 The default value is 9600 5 Command Mode This allows the use of either 937B or o...

Страница 26: ...usting the DAC parameter To view or modify the DAC parameter press SYSTEM SETUP and move the cursor to Set DAC Parameter Select Edit and press ENTER The DAC parameters used in scaling the logarithmic...

Страница 27: ...0V linear output is needed at a pressure different from that given above it can be entered via serial communication using the DLAn and DLT commands outlined in Section 9 14 14 FV firmware version Info...

Страница 28: ...d control channel selection are accomplished using Channel Setup Figure 6 7 shows the channel setup parameters for all of the sensors and devices operated by the 937B controller The default values are...

Страница 29: ...937B Controller Instruction Manual pg 29 Figure 6 7 937B Channel Setup Setting Parameters their Default Values and Ranges...

Страница 30: ...lect the correct voltage Press ENTER to save the setting either 10 or 5 V 3 Range The full scale pressure range of the capacitance manometer needs to be set Capacitance manometers with full scale rang...

Страница 31: ...r Autozeroing Capacitance Manometers The Capacitance Manometer and the reference auto zero sensor must be connected to the same chamber at all times 6 Manual Zero This allows for manual zeroing of the...

Страница 32: ...t to 0 9xSet point if DIR is set to BELOW the hysteresis is automatically set to 1 1xSet point To modify the hysteresis move the cursor to the hysteresis value and press ENTER Use the UP or DOWN arrow...

Страница 33: ...l NO Sensor Figure 6 9 Pirani Convention Pirani Setup Information Screen 1 Sensor The Sensor Type Convection Pirani or Pirani is often auto detected during the initial power up If the sensor type is a...

Страница 34: ...is over 1x10 2 Torr 6 ATM Value The entered value is used for the atmospheric reading of the Pirani CP when an ATM Cal is performed The default value is 760 Torr Recall that elevation and weather will...

Страница 35: ...PR CP gauges is 0 9xSet point when DIR is set to ABOVE the minimum hysteresis is 1 1xSet point when DIR is set to BELOW 13 Power Control of a Convection Pirani or Pirani Sensor Pirani or Convection P...

Страница 36: ...until the delay has expired The delay can be adjusted from 3 to 300 seconds and the default value is 3 seconds When the AO delay is active WAIT will be displayed on the front panel rather than a pres...

Страница 37: ...to stay in the activated closed state regardless of pressure and set point values CLEAR forces the relay to stay in the deactivated open state regardless of pressure and set point values ENABLE the re...

Страница 38: ...t locations For example when the PR CP CM is installed on the foreline between the mechanical and turbo pumps monitoring the mechanical pump pressure and the CC is installed on the high vacuum chamber...

Страница 39: ...ay 01 SET Dir Ch SET SP BELOW Hyst Enable 1 0E 06 9 0E 07 BELOW CLEAR 3 0E 05 3 3E 05 Relay 04 Relay 03 BELOW ENABLE 2 0E 08 1 8E 09 BELOW CLEAR 5 0E 07 5 5E 07 Filament 1 30 EC 20 uA DG Time Sensitiv...

Страница 40: ...orr and automatically switched to 1 mA when pressure is below 1x10 4 Torr 6 Protect SP The Protect Set Point is turns off the hot cathode operating voltages based on its own pressure readings The Prot...

Страница 41: ...thode from operating at high pressure extending the service life The adjustable Control SP range depends upon the sensor used for control 2x10 3 to 1x10 2 Torr for a Convection Pirani or Convectron 5x...

Страница 42: ...int before using the front panel key to switch the sensor 3 The Sensor ON OFF key switches the corresponding sensor ON and OFF When a Hot Cathode is turned ON the filament power may turn OFF automatic...

Страница 43: ...or removing ground from the pin turns the gauge power back ON Sensor power is turned ON when a rising edge is detected Any of the three turn ON OFF methods can be over ridden by the other For instance...

Страница 44: ...itance manometer which is not gas dependent The leak test mode and bar graph will not be displayed if the 937B Controller detects that the requested sensor for leak testing is a capacitance manometer...

Страница 45: ...lecular weight and that of the system gas The type of vacuum pump used can also affect the accuracy of the leak test For moderate size leaks pump down the system with a high vacuum pump such as a diff...

Страница 46: ...correct on automated gas delivery systems 7 2 Installing Cold Cathode Sensors Verify that the vacuum port to which the CC sensor is mounted is electrically grounded It is essential for personnel safet...

Страница 47: ...conductive all metal clamp to ensure the sensor body is grounded If the I Mag Sensor has a CF flange remove the magnet first to allow clearance for bolt installation To remove the magnet undo the two...

Страница 48: ...seal is not recommended for high vacuum as outgassing and or permeation through the elastomer can cause errors in pressure measurement A sensor with a KF flange and elastomer O ring seal is suitable...

Страница 49: ...chamber or manifold pressure Install the sensor away from pumps and gas sources for the most representative data Place the sensor in a location with minimal vibration 7 4 2 Preventing Contamination in...

Страница 50: ...can blow the sensor out of a compression fitting damaging equipment and possibly injuring personnel Do not use a compression mount quick connect to attach the sensor to a system in positive pressure...

Страница 51: ...ment of operating sensor s must be 1 amp or less See an MKS Baratron instruction manual for complete information on using these capacitance manometers The Series 937B Controller also supports the gas...

Страница 52: ...ub Connector on CM Module 7 6 Series 902B Piezo The Controller also supports the gas independent Series 902B Piezo resistive gauges The 9 pin versions can be operated off the Capacitance Manometer mod...

Страница 53: ...ess a pressure signal results in a relay activation time delay of between 50 to 100 msec 8 1 1 Pin Out for the 937B Relay Output Table 8 1 identifies the pins for the 25 pin D connector on the AIO Pow...

Страница 54: ...the measured pressure is lower than the set point For example using relay activation in the BELOW mode a normally closed isolation valve can be opened only when the pressure is below its set point Si...

Страница 55: ...reduce relay contact life In these situations an arc suppression network shown schematically in Figure 8 2 is recommended Figure 8 2 Relay Arc Suppression Network The values of the capacitance C and...

Страница 56: ...processing However the buffered output from a hot cathode sensor at pin 1 3 or 5 in the table 8 2 is a microprocessor formed output This is because the hot cathode sensor uses different emission curr...

Страница 57: ...937B Controller Instruction Manual pg 57 Figure 8 3 Buffered Analog Output for Cold Cathode Sensors 431 422 423 in N2...

Страница 58: ...8 1 0E 04 9 3297 4 0E 09 4 6807 1 5E 04 9 4255 6 0E 09 4 8991 2 0E 04 9 4826 8 0E 09 5 0452 3 0E 04 9 5605 1 0E 08 5 1579 4 0E 04 9 6076 1 5E 08 5 3563 6 0E 04 9 6708 2 0E 08 5 4924 8 0E 04 9 7034 3 0...

Страница 59: ...937B Controller Instruction Manual pg 59 Figure 8 4 Buffered Analog Output for Hot Cathode Sensors...

Страница 60: ...937B Controller Instruction Manual pg 60 Figure 8 5 Buffered Analog Output for a 345 Pirani Sensor...

Страница 61: ...1 3751 1 6066 6 0E 02 1 9652 1 6162 1 9148 8 0E 02 2 2254 1 8213 2 1788 1 0E 01 2 4526 2 0015 2 4131 1 5E 01 2 9255 2 3794 2 9143 2 0E 01 3 3095 2 6885 3 3370 3 0E 01 3 9177 3 1815 4 0419 4 0E 01 4 3...

Страница 62: ...V p 9 3 V V 9 72 V 20 p 1 103 Torr 8696 0 3 2 10 34 1 621 9 621 9 4123 V V p Argon 0 63 V 7 79 V 1 10 4 p 20 Torr 1 3961 0 63 63 663 1 2 V p 7 79 V V 8 05 V 30 p 1 103 Torr 729 0 4 2 10 464 5 9386 7...

Страница 63: ...937B Controller Instruction Manual pg 63 Figure 8 6 Buffered Analog Output for the 317 Convection Pirani Sensor or 275 Convectron Sensor...

Страница 64: ...02 1 2884 1 0782 1 1755 8 0E 02 1 4465 1 1985 1 3147 1 0E 01 1 5870 1 3066 1 4398 1 5E 01 1 8866 1 5399 1 7110 2 0E 01 2 1371 1 7370 1 9427 3 0E 01 2 5480 2 0637 2 3341 4 0E 01 2 8825 2 3318 2 6645 6...

Страница 65: ...10 372 5 503 8 503 8 5 399 V V p p 300 Torr 9177 0 512 3 exp V p Argon 0 56 V 7 00 V 1 10 4 p 60 Torr 002 1 2 1 3205 0 083 51 6 3 V p 7 00 V V 7 4 V 60 p 300 Torr 3 2 10 789 3 042 7 042 7 2 411 V V p...

Страница 66: ...Buffered Capacitance Manometer Analog Output Pressure Torr 10 4 10 3 10 2 10 1 100 101 102 103 104 Output Voltage V 0 01 0 1 1 10 0 1 Full Scale Range Torr 1 0 10 100 1000 10 000 Figure 8 7 Buffered...

Страница 67: ...are available These can provide a wider pressure range coverage since the combination output combines the measurement ranges of multiple gauges When Capacitance Manometers are used in combination no s...

Страница 68: ...t be assigned as the middle pressure range sensor Middle in Figure 8 8 When a Pirani or Convection Pirani is used in combination only HC CC can be assigned to the low pressure range sensor Only capaci...

Страница 69: ...inear analog output when the sensor power is turned OFF or the combined analog output is disabled Analog Out Volts Linear Out volts Log Linear Out Volts 937B Power OFF 0 0 0 CP Convectron channel OFF...

Страница 70: ...in 9 3 to 9 14 Response Responses as described in 9 3 to 9 14 For example to query pressure on channel A1 use 003PR1 FF and the corresponding response is 003ACK7 602E 2 FF Here aaa 003 Command PR1 Re...

Страница 71: ...FF or HC PR CP power is OFF RP_OFF HC and CC power is turned OFF from rear panel control WAIT CC or HC startup delay LowEmis HC OFF due to low emission CTRL_OFF CC or HC is OFF in controlled state PRO...

Страница 72: ...the current setting value For CC and HC only BELOW can be selected NAK162 For CC and HC as the relay direction is fixed to BELOW ENm m 1 to 12 SET ENABLE or CLEAR SET ENABLE or CLEAR Query or set stat...

Страница 73: ...ds 9 6 Convection Pirani Convectron and Pirani Control Commands Command Parameter Response Function ATMn n 1 to 6 d ddE ee ambient pressure d ddE ee Send an atmospheric pressure to perform ATM calibra...

Страница 74: ...and 1 2 CSP to 0 03 Torr for Capacitance Manometer Default value is 1 5X the control set point value CSEn n 1 3 5 A1 B1 A2 B2 C1 C2 OFF A1 B1 A2 B2 C1 C2 OFF Query enable disable the control channel s...

Страница 75: ...1 A2 B2 C1 C2 OFF Query enable disable the control channel status for an HC sensor on channel n CTLn n 1 3 5 AUTO SAFE OFF AUTO SAFE OFF AUTO HC CC can be turned ON OFF by the controlling sensor PR CP...

Страница 76: ...Enable MT T1 T2 T3 T4 Display the sensor module type T1 T2 T3 CC HC CM PR FC NC NC no connection T4 NA PF for PROFIBUS PC STn n A B C S1S2 Display the connected sensor type on the specified module A B...

Страница 77: ...C offset parameter B Default value is 7 2 Use n 0 for combination output Valid range is from 20 to 20 when DLT is set to LOG and always equals to zero when DLT is set to LIN IU ON or OFF ON or OFF For...

Страница 78: ...DCATHODE 155 NOT_CAPACITANCE_MANOMETER 156 NOT_PIRANI_OR_CTP 157 NOT_PR_OR_CM 158 NOT_MFC 159 NOT_VLV 160 UNRECOGNIZED_MSG 161 SET_CMD_LOCK 162 RLY_DIR_FIX_FOR_ION 163 INVALID_CHANNEL 164 DIFF_CM 165...

Страница 79: ...o Ch B1 AUTZ3 5 Autozero Ch B2 AUTZ4 6 Autozero Ch C1 AUTZ5 7 Autozero Ch C2 AUTZ6 8 Gas Type Ch A1 GT1 9 Nitrogen Argon Helium Custom HC only Local Setting Gas Type Ch A2 GT2 10 Gas Type Ch B1 GT3 11...

Страница 80: ...B2 CTL4 39 Ctrl Enable Ch C1 CTL5 40 Ctrl Enable Ch C2 CTL6 41 Fast Relay Ctrl Ch A1 FRC1 42 1E 7 2E 7 4E 7 8E 7 1E 6 2E 6 4E 6 8E 6 1E 5 2E 5 4E 5 8E 5 1E 4 Local Setting Fast Relay Ctrl Ch B1 FRC3...

Страница 81: ...Bit 3 Enable Clear Set point Relay 12 Bit 4 N A Bit 5 N A Bit 6 N A Bit 7 N A 2 1 Bit field Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Power CC HC PR Channel A1 Power CC HC PR Channel A2 Power C...

Страница 82: ...Factory Default Channel B2 Factory Default Channel C1 Factory Default Channel C2 N A N A 8 4 Float Relay Set point Pressure for Relay 1 12 4 Float Relay Set point Pressure for Relay 2 Flow Set point f...

Страница 83: ...6 24 1 Byte Status for Channel 1 1 NOGAUGE 2 NEGATIVE 3 CONTROL 4 HI 5 LO 6 OFF 7 AA 8 PROTECT 9 WAIT 10 RP_OFF 11 Degas 12 FAULT 13 OPEN for MFC only 14 CLOSE for MFC only 15 SET POINT for MFC only 1...

Страница 84: ...NEGATIVE 3 CONTROL 4 HI 5 LO 6 OFF 7 AA 8 PROTECT 9 WAIT 10 RP_OFF 11 Degas 12 FAULT 13 OPEN for MFC only 14 CLOSE for MFC only 15 SET POINT for MFC only 16 PID for MFC only 28 1 Byte Status for Chan...

Страница 85: ...nt Relay State Relay 9 1 Set point Relay State Relay 10 2 Set point Relay State Relay 11 3 Set point Relay State Relay 12 4 N A 5 N A 6 N A 7 N A 32 4 Float Set point Relay State Relay 1 36 4 Float Se...

Страница 86: ...module in the slot Typically 937B Controllers are shipped with customer specified sensor modules To change the controller configuration by removing and installing modules follow the steps shown below...

Страница 87: ...hat the controller power is OFF and the power cord is disconnected 2 Use a 1 Phillips screwdriver to remove the four 4 screws on the four corners of the rear panel of the AIO module 3 Place a small fl...

Страница 88: ...ips screwdriver to install and tighten the four 4 screws on the four corners of the rear panel of the module 10 3 Removing and Installing Profibus Control Module In the 937B Controller the slot labele...

Страница 89: ...n D Sub communications connector is located on the back panel of the AIO Power module 10 4 Mounting the Controller The 937B Controller was designed for both rack mounting and bench top use In both cas...

Страница 90: ...ions to other mounting configurations 10 5 AC Power Cord The Controller has a standard female IEC 60320 connector for connecting to a 100 240 VAC 50 60 Hz power source Use only a harmonized detachable...

Страница 91: ...current or filament voltage is needed Degassing is not needed Sensor tubes can often be cleaned and reused almost indefinitely The control circuit is simple and reliable having only one current loop a...

Страница 92: ...l cylindrical magnet which provides an axial field The cathode is isolated from the grounded metal housing The inverted magnetron geometry produces more stable signal output and also works well to low...

Страница 93: ...ocket head cap screws 10 and pull the back flange 13 free Note that these screws are silver plated for lubricity and should be used only once They may be re lubricated with a dry lubricant such as mol...

Страница 94: ...or chemically Do not touch any vacuum exposed part after cleaning unless wearing gloves Ultrasonic cleaning should use only high quality detergents compatible with aluminum e g ALCONOX Scrub surfaces...

Страница 95: ...ting a Cold Cathode Sensor MKS cold cathode sensors contain anode and cathode collector electrodes Test the sensor with an ohmmeter There should be no shorts between the electrodes or from the electro...

Страница 96: ...ng 1 on the ion current feed through pin when assembling or disassembling the sensor Leaf Spring High Voltage Feedthrough Pin Flathead Screw 2 Magnet Ion Current Feedthrough Pin Glass Insulator Locati...

Страница 97: ...hods described above should be followed with multiple rinses of deionized water Dry all internal components and the sensor body 9 in a clean oven set at 150 C The two ceramic spacers 4 and 7 are sligh...

Страница 98: ...he ion numbers are in proportion to the ambient gas pressure Electrons are accelerated through the structure by a potential difference between the hot emitting filament and a positively charged surrou...

Страница 99: ...an remove surface contamination on the grid and collector Severe contamination of the grid structure may require a replacement of the sensor Although the feed through insulators are shielded in some a...

Страница 100: ...maintained at a constant temperature during the measurement process Figure 11 7 Schematic of a Pirani Thermal Conductivity Sensor The amount of heat exchanged between the hot wire and a colder enviro...

Страница 101: ...1000 Torr 11 5 1 Cleaning the Series 345 Sensor Roughing pump oils and other fluids condensing or decomposing on the heated filament can contaminate the sensor This changes the emissivity of the filam...

Страница 102: ...or electronics subassembly from the end of the sensor 2 Check the resistance on the sensor s pins listed in the first column in Table 11 3 Test the sensor using an ohmmeter with less than 5 mA of curr...

Страница 103: ...is to be measured The other reference side contains an electrode assembly placed in a reference cavity see Figure 11 9 Absolute transducers have the reference side factory sealed under high vacuum 10...

Страница 104: ...essure control 100016609 Cable for Capacitance Manometer Type 722B 10 ft 3 0 m 100016951 25 ft 7 6 m 100016952 50 ft 15 2 m 100016953 Cable for Capacitance Manometer Type 626B 627D 10 ft 3 0 m 1000075...

Страница 105: ...ection Pirani 345 Pirani Sensor 10 ft 3 0 m 103170006SH 25 ft 7 6 m 103170007SH 50 ft 15 2 m 103170008SH 100 ft 30 5 m 103170017SH Custom to 500 ft 152 4 m 103170009SH Cable for 275 Convectron Sensor...

Страница 106: ...937B Controller Instruction Manual pg 106 Series 937B Vacuum System Controller Operation and Maintenance Manual Instruction Manual p n 100016467 Rev F August 2020...

Отзывы: