4
Operation
22
Series 275 Convectron Module with DeviceNet
Instruction Manual - 275502
4.2
Front Panel Indicators and Adjustments
The two LEDs on the front panel indicate the current status of the Mini-Convectron Module and the
DeviceNet network. Four potentiometers provide adjustments for setpoints, baud rate, and MAC ID
settings. The two LED status indicators are explained in Table 4-1 and Table 4-2; the four
potentiometers are explained in Section 4.2.3, 4.1.4, and 4.1.5.
Figure 4-2
Series 275 DeviceNet Mini-Convectron Front Panel
4.2.1
Module (MOD) LED Status
Table 4-1
Series 275 DeviceNet Mini-Convectron Module LED Status
LED
Status
Off
No Power to the module.
Green
Operating normally.
Orange
The module has an unrecoverable fault, and may need to be replaced.
Flashing Orange-Green The module is in self-test. Refer to the Identity Object in Volume II of the DeviceNet
specification.
Using the module to measure the pressure of flammable or explosive gases can
cause a fire or explosion resulting in severe property damage or personal injury.
Do not use the module to measure the pressure of flammable or explosive gases.
Содержание 275420-1-GQ-T-00011
Страница 2: ......
Страница 16: ...2 Introduction Specifications 16 Series 275 Convectron Module with DeviceNet Instruction Manual 275502...
Страница 26: ...4 Operation 26 Series 275 Convectron Module with DeviceNet Instruction Manual 275502 Notes...
Страница 31: ...5 DeviceNet Operation Series 275 Convectron Module with DeviceNet Instruction Manual 275502 31...
Страница 32: ...5 DeviceNet Operation 32 Series 275 Convectron Module with DeviceNet Instruction Manual 275502...
Страница 50: ......
Страница 51: ......