Standard Protocol
Chapter Four: Operation
50
Report Command Responses
Ry
Parameter
Responses
Units
R1
Digital Pressure Set Point
S xxx.x
Percent
R2
Gain
G xxx.x
Percent
R3
Lead
L xxx.x
Percent
R4
Analog Set Point
A xxx.x
Percent
R5
Pressure
P xxx.x
Percent
R6
Position
V xxx.x
Degrees
R8
Slipped ?
C x
0 = OK
1 = Slipped
R10
Set Point Zero
ZA xxx.x
Percent
R11
Pressure Zero
ZB xxx.x
Percent
R12
Set Point F.S.
FA xxx.x
Percent
Ry13
Pressure F.S.
FB xxx.x
Percent
Table 15: Report Command Responses
Operating Values Established By the “B” Command
Parameter
Value
Lead
4.0%
Gain
90.0%
Set Point
0.0%
Pressure Zero
0.0 Volts
Set Point Zero
0.0 Volts
Pressure Full Scale
10.0 Volts
Set Point Full Scale
10.0 Volts
Table 16: Operating Values Established By The “B” Command