Chapter Three: Overview
Internal Controls on the 153/1253 Controller
35
Explanation of the Dipswitch Settings
Dipswitch
OFF (Open)
ON (Closed)
8
Position Controller
Pressure Controller*
7
Digital Set Point
Analog Set Point*
6
Standard RS-232 Protocol
Terminal Protocol*
5
No Parity*
Even Parity
4
1200 Baud
9600 Baud*
3
CR Delimiter*
CR-LF Delimiter
2
Set Point entry (Sxxx.x)
Set Point entry (S1xxx.x)*
1
Reverse Control
Normal Control*
* Indicates default switch settings as shipped from factory
Table 10: Explanation of the Dipswitch Settings
Switch 8:
Selects the method of control. When OFF, the 153/1253 unit acts as a position
controller. When the switch is ON the valve acts as a pressure controller.
Switch 7:
This switch selects the source of the set point signal. When the switch is OFF, the
153/1253 controller expects to receive the set point signal via the RS-232 interface. When ON,
the 153/1253 controller expects the set point signal to be an external analog voltage on the
INPUT connector. You can override the analog set point by sending an RS-232 signal to the
153/1253 controller. Use the standard protocol “A” command to revert back to an analog set
point.
Switch 6:
Establishes the RS-232 protocol. When OFF, the protocol is standard. When ON,
the 153/1253 controller uses the portable terminal (PT-1) protocol.
Switch 5:
Toggles the parity setting. The OFF setting selects no parity. The ON setting
selects even parity.
Switch 4:
Sets the baud rate. When OFF, the baud rate is 1200. When ON, the baud rate is
9600.
Switch 3: S
elects the end-of-line delimiter. When OFF, the delimiter is a Carriage Return
(CR). When ON, the delimiter is a Carriage Line Feed (CRLF).
Switch 2:
Controls the RS-232 compatibility for the set point entry. When OFF, the set point
entry command is Sxxx.x. When ON, the set point entry is S1xxx.x. The extra 1 makes this
entry compatible with other MKS instruments (ex. Types 152, 153A, and 112).
Switch 1:
Selects the set point control action. When the switch is OFF, a zero to full scale set
point produces an open to close valve action (normal control). When ON, a zero to full scale set
point produces a closed to open valve action (reverse control).
Содержание 1253D
Страница 3: ...115714 P1 Rev D 3 99 MKS Type 153D and 1253D Throttle Valve Controllers...
Страница 8: ...Table of Contents vi...
Страница 10: ...List of Figures and Tables viii...
Страница 50: ...Valve Slippage Signal Chapter Three Overview 40 This page intentionally left blank...
Страница 64: ...General Information Chapter Five Maintenance 54 This page intentionally left blank...