background image

7

C

B

A

E

D

4.  Installing the refrigerant piping

4.3.  Refrigerant piping (Fig. 4-4)

Remove the service panel 

D

 (three screws) and the front piping cover 

A

 (two screws) 

and rear piping cover 

B

 (two screws).

1

  Perform refrigerant piping connections for the indoor/outdoor unit when the outdoor 

unit’s stop valve is completely closed.

2

  Vacuum-purge air from the indoor unit and the connection piping.

Evacuation

Evacuate with the valve of the outdoor unit closed and evacuate both the connection 
piping and the indoor unit from the service port provided on the valve of the outdoor 
unit using a vacuum pump. (Always evacuate from the service port of both the liquid 
pipe and the gas pipe.) After the vacuum reaches 650 Pa [abs] [0.0943 psi/5 Torr], 
continue evacuation for at least one hour or more. Then, stop the vacuum pump and 
leave it for 1 hour. Ensure the degree of vacuum has not increased. (If the degree 
of vacuum increase is larger than 130 Pa [0.01886 psi/1.0 Torr], water might have 
entered. Apply pressure to dry nitrogen gas up to 0.05 MPa [7.25 psi] and vacuum 
again. Repeat the evacuation process three or more times until the vacuum pressure 
is lost by 130 Pa or below.)
Finally, seal in with the liquid refrigerant through the liquid pipe, and adjust the gas 
pipe to obtain an appropriate amount of the refrigerant during operation. 

 

Never perform air purging using refrigerant.

3

  After connecting the refrigerant pipes, check the connected pipes and the indoor 

unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)

4

  Vacuumize the refrigerant lines through the service port of the liquid and gas stop 

valves. And then open the stop valves completely (for both the liquid and gas stop 
valves). This will completely connect the refrigerant lines of the indoor and outdoor 
units.

•  If the stop valves are left closed and the unit is operated, the compressor and 

control valves will be damaged.

•  Use a leak detector or soapy water to check for gas leaks at the pipe connec-

tion sections of the outdoor unit.

•  Do not use the refrigerant from the unit to purge air from the refrigerant 

lines.

•  After the valve work is completed, tighten the valve caps to the correct torque: 

20 to 25 N·m [14 to 18 ft·lbs] (200 to 250 kgf·cm).

  Failure to replace and tighten the caps may result in refrigerant leakage. In 

addition, do not damage the insides of the valve caps as they act as a seal to 
prevent refrigerant leakage.

5

 Use sealant to seal the ends of the thermal insulation around the pipe connection 

sections to prevent water from entering the thermal insulation.

Note:
<Triple Evacuation>

•  Evacuate the system to 4,000 microns from both service valves. System 

manifold gauges must not be used to measure vacuum. A micron gauge must 
be used at all times.
-  Break the vacuum with Nitrogen (N2) into the discharge service valve to 0 

PSIG.

•  Evacuate the system to 1,500 microns from the suction service valve. 

-  Break the vacuum with Nitrogen (N2) into the discharge service valve to 0 

PSIG.

•  Evacuate the system to 500 microns. System must hold the vacuum at 500 

microns for a minimum of 1 hour. 

•  Conduct a rise test for a minimum of 30 minutes.

4.4.  Refrigerant pipe airtight testing method

(1) Connect the testing tools.

•  Make sure the stop valves 

A

 

B

 are closed and do not open them.

•  Add pressure to the refrigerant lines through the service port 

C

 of the liquid 

stop valve 

and the gas stop valve 

B

.

(2) Do not add pressure to the specified pressure all at once; add pressure little by little.

1

 Pressurize to 0.5 MPa [73 PSIG], wait five minutes, and make sure the  

pressure does not decrease.

2

 Pressurize to 1.5 MPa [218 PSIG], wait five minutes, and make sure the pres-

sure does not decrease.

3

 Pressurize to 4.15 MPa [600 PSIG] and measure the surrounding temperature 

and refrigerant pressure.

(3) If the specified pressure holds for about one day and does not decrease, the pipes 

have passed the test and there are no leaks.

•  If the surrounding temperature changes by 1°C [1.8°F], the pressure will change 

by about 0.01 MPa [1.5 PSIG]. Make the necessary corrections.

(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the source 

of the gas leak.

4.5.  Stop valve opening method

(1) Gas side (Fig. 4-6)
Type A

1

  Remove the cap, then turn one-quarter rotation counter-clockwise with a flat-bladed 

screwdriver to complete open.

2

  Check that the valves are fully open, then return the cap to its original state and 

tighten it down.

Type B

1

  Remove the cap, pull the handle toward you and rotate 1/4 turn in a counterclock-

wise direction to open.

2

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

Fig. 4-5

Fig. 4-4

A

 Front piping cover

B

 Piping cover

C

 Stop valve

Service panel

E

 Bend radius : 100 mm - 150 mm

A

 Stop valve <Liquid side>

B

 Stop valve <Gas side>

C

 Service port

D

 Open/Close section

E

 Local pipe

F

 Sealed, same way for gas side

G

 Pipe cover

H

 Do not use a wrench here.

 

Refrigerant leakage may result.

I

 Use two wrenches here.

A

B

H

I

C
D

E

F

G

C

(1)

Fig. 4-6

E

G

G

A

B

C

D

F

A

B

J

D

E

G

Type A

Type B

Содержание PUMY-P NHMU

Страница 1: ...MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci n de la unidad interior antes de instalar la unidad de aire acondicionado PARA EL INSTALADO...

Страница 2: ...ards The use of any refrigerant other than that speci ed for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case this could lead to a serious impediment...

Страница 3: ...ure enters the refriger ant lines refrigeration oil deterioration may result Do not use a charging cylinder If a charging cylinder is used the composition of the refrigerant will change and the ef cie...

Страница 4: ...outlet guides for upward air ow 2 4 2 When installing multiple outdoor units Leave 10 mm 13 32 inch space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only...

Страница 5: ...d cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly installed unit may...

Страница 6: ...ze adjustment gauge can be used to con rm A measurements Warning When installing the unit securely connect the refrigerant pipes before start ing the compressor A Liquid pipe Gas pipe PUMY 9 52 3 8 15...

Страница 7: ...lant to seal the ends of the thermal insulation around the pipe connection sections to prevent water from entering the thermal insulation Note Triple Evacuation Evacuate the system to 4 000 microns fr...

Страница 8: ...nsmission lines of different systems are wired with the same multiplecore cable the resultant poor transmit ting and receiving will cause erroneous operations 6 Electrical work 7 Only the transmission...

Страница 9: ...e same group to the terminal block on the remote controller RC d Connect together terminals M1 M2 and terminal S on the terminal block for central control TB7 for the outdoor unit OC e The jumper conn...

Страница 10: ...hat generated overcurrent may include some amount of direct current Caution Some installation site may require attachment of an earth leakage breaker If no earth leakage breaker is installed it may ca...

Страница 11: ...er carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refriger...

Страница 12: ...rminales Asimismo no empalme nunca los cables al realizar el cableado a menos que se indique lo contrario en este documento El hecho de no seguir estas instrucciones puede provocar un sobrecalenta mie...

Страница 13: ...gua de postes de iluminaci n o de tel fono Si la unidad no est bien conectada a la l nea de tierra se puede producir una descarga el ctrica Utilice disyuntores interruptor de falta de tierra interrupt...

Страница 14: ...unidades correlativas Adem s se debe dejar el espacio indicado No utilice las gu as para salida de aire opcionales para corriente de aire hacia arriba 3 Obst culos s lo en la parte delantera Fig 2 10...

Страница 15: ...otros peligros Usar un refrigerante distinto al indicado para el sistema provocar un fallo mec nico un funcionamiento defectuoso del sistema o la aver a de la unidad En el peor de los casos podr a sup...

Страница 16: ...gerante R410A Para con rmar las medidas de A se puede utilizar el ajustador del tama o Atenci n Al instalar la unidad conecte rmemente las tuber as de refrigerante antes de poner en marcha el compreso...

Страница 17: ...s ya que funcionan como selladoras para evitar fugas de refrigerante 5 Utilice un sellador para proteger las conexiones de los tubos y los extremos del material aislante no se impregnen de agua Nota V...

Страница 18: ...las l neas de transmisi n de sistemas diferentes est n conectados con los mismos cables de varias almas la pobre transmisi n y recepci n resultante dar lugar a funciones err neas 6 Trabajo el ctrico 7...

Страница 19: ...itud de esta secci n L8 deber a incluirse en longitud m xima de c lculo y la longitud total 2 Controlador remoto MA Longitud mayor a trav s de las unidades exteriores Cable M NET L1 L2 L3 L4 y L1 L2 L...

Страница 20: ...iesgo de que se produzca calentamiento o un incendio Aseg rese de escoger un interruptor de protecci n de sobrecarga adecuado No olvide que la sobrecorriente generada puede contener peque as cantidade...

Страница 21: ...r y vuelva a colocar el tap n a cada v lvula de parada Notas 1 Nunca realice el vaciado si la cantidad de refrigerante del interior de la unidad interior es superior a la cantidad de refrigerante no c...

Страница 22: ...nt sans tension sur les bornes Ne jamais effectuer de jonction sur les c bles sauf en cas d indications contraires Le non respect de cette consigne peut entra ner une surchauffe ou un incendie Le couv...

Страница 23: ...te de l appareil peut provoquer un choc lectrique Utiliser des coupe circuits disjoncteur de fuite la terre interrupteur d isolement fusible B et disjoncteur bo tier moul la capacit sp ci e Si la capa...

Страница 24: ...pacer galement les appareils comme illustr Ne pas utiliser les guidages de sortie d air en option pour un d bit d air vers le haut 3 Obstacles uniquement l avant Fig 2 10 Lors de l utilisation d un gu...

Страница 25: ...frig rant diff rent de celui sp ci pour le climatiseur peut en tra ner des d faillances m caniques des dysfonctionnements du syst me ou une panne de l appareil Dans le pire des cas cela peut entra ne...

Страница 26: ...au tableau 1 pour l vasement des tuyaux de r frig rant R410A La jauge de r glage de la taille peut tre utilis e pour con rmer les mesures A Avertissement Pendant l installation de l appareil brancher...

Страница 27: ...de l isolation thermique autour des sections de raccordement des tuyaux a n d emp cher l eau de p n trer dans l isolation thermique Remarque Triple vacuation vacuez le syst me de 4 000 microns par le...

Страница 28: ...ts syst mes devaient tre reli es par le m me c ble ls multiples la transmission et la r ception seraient mauvaises ce qui conduirait un fonctionnement erron des appareils 6 Installations lectriques 7...

Страница 29: ...IC qui poss de l adresse la plus r cente au sein d un m me groupe au bloc terminal de la commande distance RC d Connecter les bornes M1 M2 et S des blocs terminaux TB7 pour le contr le central sur les...

Страница 30: ...ous d utiliser le correct interrupteur de protection contre la surintensit de courant Veuillez noter que la surintensit de courant g n r e peut comprendre une certaine quantit de courant direct Pr cau...

Страница 31: ...rr t Remarque 1 Ne jamais proc der au pompage si la quantit de r frig rant dans l appareil int rieur est sup rieure la quantit de r frig rant sans charge suppl mentaire Le pompage lorsque la quantit d...

Страница 32: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Отзывы: