background image

11

7.2. Test run

7.2.1.  Using remote controller 

Refer to the indoor unit installation manual.

•  Be sure to perform the test run for each indoor unit. Make sure each indoor 

unit operates properly following the installation manual attached to the unit.

•  If you perform the test run for all indoor units at once, you cannot detect any 

erroneous connection, if any, of the refrigerant pipes and the connecting 
wires.

*  The compressor operation is not available for 3 minutes at least after the 

power is supplied.

•  The compressor can emit noise just after turn on the power supply or in case 

of low outside air temperature.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor 
will not operate for 3 minutes to protect the air conditioner.

7.2.2.  Using SW3 in outdoor unit

Note:
In case of the test run from outdoor unit, all indoor units operate. Therefore, 
you can not detect any erroneous connection of refrigerant pipes and the 
connecting wires. If it aims at detection of any erroneous connection, be sure 
to carry out the test run from remote controller with reference to “7.2.1 Using 
remote controller”.

SW3-1

ON

Cooling operation

SW3-2

OFF

SW3-1

ON

Heating operation

SW3-2

ON

*  After performing the test run, set SW3-1 to OFF.
•  A few seconds after the compressor starts, a clanging noise may be heard from 

the inside of the outdoor unit. The noise is coming from the check valve due to the 
small difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW3-2 during 
the test run. (To change the test run operation mode during the test run, stop 
the test run by DIP switch SW3-1. After changing the test run operation mode, 
resume the test run by switch SW3-1.)

7. Test run

7.3.  Refrigerant collecting (Pump down)

Before removing air conditioners for transfer to another location, always close the 
stop valve (for both liquid and gas pipes) located at the outdoor unit, then remove 
the indoor and outdoor units. At this time, the refrigerant in the indoor unit will be dis-
charged. To minimize the refrigerant discharged, a pump down operation is required. 
This operation collects the refrigerant present inside the air conditioner and sends it 
into the heat exchanger located in the outdoor unit.

Pump down procedure

1

  Operate all indoor units in cooling mode and check that the operation mode has 

changed to “COOL”. (Set the units so that cooling operation mode is activated 
during the pump down operation (when the TEST RUN button is pressed).)

2

  Connect a gauge manifold valve (with pressure gauge) to the stop valve of the 

gas pipe, to enable measurement of refrigerant pressure.

3

  After setting the outdoor service switch SW3-2 to OFF, set the switch SW3-1 to 

ON. (The unit will start in cooling mode.)

4

  After the cooling operation has been carried out for approximately five minutes, 

set the outdoor service switch SW2-4 (pump down switch) from OFF to ON. 

5

  Close the stop valve on the liquid pipe, with the cooling operation still ON. (Pump 

down operation will start.)

6

  When the reading of the pressure gauge reaches 0 to 0.1 MPa [14.5 PSIG] or 

when approximately 5 minutes have elapsed following the start of the pump down 
operation, fully close the stop valve on the gas pipe and stop the air conditioner 
by setting the switch SW3-1 to OFF immediately.

7

  Set the outdoor service switch SW2-4 from ON to OFF.

8

  Remove the gauge manifold valve and put the cap back onto each stop valve.

Note:

1

  Never carry out pump down operation if the amount of refrigerant inside 

the indoor unit is larger than the amount of charge-less refrigerant.

 

Carrying out a pump down operation when the amount of refrigerant exceeds 
the amount of charge-less refrigerant will cause an extreme pressure rise 
and may result in an accident.

2

  Do not continue to operate for a long time with the switch SW2-4 set to 

ON.

 

Make sure to switch it to OFF after pump down is completed.

3

  Test run can be carried out when the test run switch SW3-1 is ON.  Switch 

SW3-2 is used to operating mode selection. (On: Heating, OFF: Cooling)

4

  Time required for a pump down operation is three to five minutes after the 

stop valve on the liquid pipe has been closed. (It depends on the ambient 
temperature and amount of refrigerant inside the indoor unit.)

5

  Ensure that the reading of the pressure gauge does not drop below 0 MPa 

(0 PSIG). If it drops 0 MPa [0 PSIG] (i.e. vacuum is created), air will be drawn 
into the unit if there are any loose connections.

6

  Even if the reading of the pressure gauge does not drop below 0 MPa [0 

PSIG], always stop the pump down operation within approximately five 
minutes after the stop valve on the liquid pipe has been fully closed.

 Warning:

When pumping down the refrigerant, stop the compressor before disconnect-
ing the refrigerant pipes. The compressor may burst if air etc. get into it.

7.1.  Before test run

 After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power supply 
or control wiring, wrong polarity, and no disconnection of one phase in the 
supply.

  Use a 500-volt M-ohm tester to check that the resistance between the power 

supply terminals and ground is at least 1 M

Ω

.

  Do not carry out this test on the control wiring (low voltage circuit) termi-

nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1 M

Ω

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended 
period, the insulation resistance will drop below 1 M

Ω

 due to refrigerant accumulating 

in the compressor. This is not a malfunction. Perform the following procedures.
1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 M

Ω

, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3.  After connecting the wires to the compressor, the compressor will start to warm 

up after power is supplied. After supplying power for the times indicated below, 
measure the insulation resistance again.

 

•  The insulation resistance drops due to accumulation of refrigerant in the com-

pressor. The resistance will rise above 1 M

Ω

 after the compressor is warmed 

up for four hours.

 

 

(The time necessary to warm up the compressor varies according to atmospheric 
conditions and refrigerant accumulation.)

 

•  To operate the compressor with refrigerant accumulated in the compressor, the 

compressor must be warmed up at least 12 hours to prevent breakdown.

4.  If the insulation resistance rises above 1 M

Ω

, the compressor is not faulty.

 Caution:

  The compressor will not operate unless the power supply phase connection 

is correct.

•  Turn on the power at least 12 hours before starting operation.

-  Starting operation immediately after turning on the main power switch can result 

in severe damage to internal parts. Keep the power switch turned on during the 
operational season.

  The followings must be checked as well.

•  The outdoor unit is not faulty. LED on the control board of the outdoor unit flash 

when the outdoor unit is faulty.

•  Both the gas and liquid stop valves are completely open.

Содержание PUMY-P NHMU

Страница 1: ...MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci n de la unidad interior antes de instalar la unidad de aire acondicionado PARA EL INSTALADO...

Страница 2: ...ards The use of any refrigerant other than that speci ed for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case this could lead to a serious impediment...

Страница 3: ...ure enters the refriger ant lines refrigeration oil deterioration may result Do not use a charging cylinder If a charging cylinder is used the composition of the refrigerant will change and the ef cie...

Страница 4: ...outlet guides for upward air ow 2 4 2 When installing multiple outdoor units Leave 10 mm 13 32 inch space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only...

Страница 5: ...d cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly installed unit may...

Страница 6: ...ze adjustment gauge can be used to con rm A measurements Warning When installing the unit securely connect the refrigerant pipes before start ing the compressor A Liquid pipe Gas pipe PUMY 9 52 3 8 15...

Страница 7: ...lant to seal the ends of the thermal insulation around the pipe connection sections to prevent water from entering the thermal insulation Note Triple Evacuation Evacuate the system to 4 000 microns fr...

Страница 8: ...nsmission lines of different systems are wired with the same multiplecore cable the resultant poor transmit ting and receiving will cause erroneous operations 6 Electrical work 7 Only the transmission...

Страница 9: ...e same group to the terminal block on the remote controller RC d Connect together terminals M1 M2 and terminal S on the terminal block for central control TB7 for the outdoor unit OC e The jumper conn...

Страница 10: ...hat generated overcurrent may include some amount of direct current Caution Some installation site may require attachment of an earth leakage breaker If no earth leakage breaker is installed it may ca...

Страница 11: ...er carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refriger...

Страница 12: ...rminales Asimismo no empalme nunca los cables al realizar el cableado a menos que se indique lo contrario en este documento El hecho de no seguir estas instrucciones puede provocar un sobrecalenta mie...

Страница 13: ...gua de postes de iluminaci n o de tel fono Si la unidad no est bien conectada a la l nea de tierra se puede producir una descarga el ctrica Utilice disyuntores interruptor de falta de tierra interrupt...

Страница 14: ...unidades correlativas Adem s se debe dejar el espacio indicado No utilice las gu as para salida de aire opcionales para corriente de aire hacia arriba 3 Obst culos s lo en la parte delantera Fig 2 10...

Страница 15: ...otros peligros Usar un refrigerante distinto al indicado para el sistema provocar un fallo mec nico un funcionamiento defectuoso del sistema o la aver a de la unidad En el peor de los casos podr a sup...

Страница 16: ...gerante R410A Para con rmar las medidas de A se puede utilizar el ajustador del tama o Atenci n Al instalar la unidad conecte rmemente las tuber as de refrigerante antes de poner en marcha el compreso...

Страница 17: ...s ya que funcionan como selladoras para evitar fugas de refrigerante 5 Utilice un sellador para proteger las conexiones de los tubos y los extremos del material aislante no se impregnen de agua Nota V...

Страница 18: ...las l neas de transmisi n de sistemas diferentes est n conectados con los mismos cables de varias almas la pobre transmisi n y recepci n resultante dar lugar a funciones err neas 6 Trabajo el ctrico 7...

Страница 19: ...itud de esta secci n L8 deber a incluirse en longitud m xima de c lculo y la longitud total 2 Controlador remoto MA Longitud mayor a trav s de las unidades exteriores Cable M NET L1 L2 L3 L4 y L1 L2 L...

Страница 20: ...iesgo de que se produzca calentamiento o un incendio Aseg rese de escoger un interruptor de protecci n de sobrecarga adecuado No olvide que la sobrecorriente generada puede contener peque as cantidade...

Страница 21: ...r y vuelva a colocar el tap n a cada v lvula de parada Notas 1 Nunca realice el vaciado si la cantidad de refrigerante del interior de la unidad interior es superior a la cantidad de refrigerante no c...

Страница 22: ...nt sans tension sur les bornes Ne jamais effectuer de jonction sur les c bles sauf en cas d indications contraires Le non respect de cette consigne peut entra ner une surchauffe ou un incendie Le couv...

Страница 23: ...te de l appareil peut provoquer un choc lectrique Utiliser des coupe circuits disjoncteur de fuite la terre interrupteur d isolement fusible B et disjoncteur bo tier moul la capacit sp ci e Si la capa...

Страница 24: ...pacer galement les appareils comme illustr Ne pas utiliser les guidages de sortie d air en option pour un d bit d air vers le haut 3 Obstacles uniquement l avant Fig 2 10 Lors de l utilisation d un gu...

Страница 25: ...frig rant diff rent de celui sp ci pour le climatiseur peut en tra ner des d faillances m caniques des dysfonctionnements du syst me ou une panne de l appareil Dans le pire des cas cela peut entra ne...

Страница 26: ...au tableau 1 pour l vasement des tuyaux de r frig rant R410A La jauge de r glage de la taille peut tre utilis e pour con rmer les mesures A Avertissement Pendant l installation de l appareil brancher...

Страница 27: ...de l isolation thermique autour des sections de raccordement des tuyaux a n d emp cher l eau de p n trer dans l isolation thermique Remarque Triple vacuation vacuez le syst me de 4 000 microns par le...

Страница 28: ...ts syst mes devaient tre reli es par le m me c ble ls multiples la transmission et la r ception seraient mauvaises ce qui conduirait un fonctionnement erron des appareils 6 Installations lectriques 7...

Страница 29: ...IC qui poss de l adresse la plus r cente au sein d un m me groupe au bloc terminal de la commande distance RC d Connecter les bornes M1 M2 et S des blocs terminaux TB7 pour le contr le central sur les...

Страница 30: ...ous d utiliser le correct interrupteur de protection contre la surintensit de courant Veuillez noter que la surintensit de courant g n r e peut comprendre une certaine quantit de courant direct Pr cau...

Страница 31: ...rr t Remarque 1 Ne jamais proc der au pompage si la quantit de r frig rant dans l appareil int rieur est sup rieure la quantit de r frig rant sans charge suppl mentaire Le pompage lorsque la quantit d...

Страница 32: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Отзывы: