1. Safety precautions

1.3.  Before electric work

 Caution:

•  Be sure to install circuit breakers. If not installed, electric shock may result.
•  For the power lines, use standard cables of sufficient capacity. Otherwise, a 

short circuit, overheating, or fire may result.

•  When installing the power lines, do not apply tension to the cables. If the 

connections are loosened, the cables can snap or break and overheating or 
fire may result.

1.4.  Before starting the test run

 Caution:

•  Turn on the main power switch more than 12 hours before starting operation. 

Starting operation just after turning on the power switch can severely damage 
the internal parts. Keep the main power switch turned on during the operation 
season.

•  Before starting operation, check that all panels, guards and other protective parts 

are correctly installed. Rotating, hot, or high voltage parts can cause injuries.

•  Be sure to ground the unit. Do not connect the ground wire to gas or water 

pipes, lighting rods, or telephone grounding lines. If the unit is not properly 
grounded, electric shock may result.

•  Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and 

molded case circuit breaker) with the specified capacity. If the circuit breaker 
capacity is larger than the specified capacity, breakdown or fire may result.

•  Do not touch any switch with wet hands. Electric shock may result.
•  Do not touch the refrigerant pipes with bare hands during operation. The 

refrigerant pipes are hot or cold depending on the condition of the flowing 
refrigerant. If you touch the pipes, burns or frostbite may result.

•  After stopping operation, be sure to wait at least five minutes before turning off 

the main power switch. Otherwise, water leakage or breakdown may result.

1.5.  Using R410A refrigerant air conditioners

 Caution:

•  Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, 

to connect the refrigerant pipes. Make sure the insides of the pipes are clean 
and do not contain any harmful contaminants such as sulfuric compounds, 
oxidants, debris, or dust. Use pipes with the specified thickness. (Refer to page 
5) Note the following if reusing existing pipes that carried R22 refrigerant.

-  Replace the existing flare nuts and flare the flared sections again.
-  Do not use thin pipes. (Refer to page 5)

•  Store the pipes to be used during installation indoors and keep both ends of 

the pipes sealed until just before brazing. (Leave elbow joints, etc. in their 
packaging.) If dust, debris, or moisture enters the refrigerant lines, oil dete-
rioration or compressor breakdown may result.

•  Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration 

oil applied to the flared sections. If mineral oil is mixed in the refrigeration 
oil, oil deterioration may result.

•  Do not use refrigerant other than R410A refrigerant. If another refrigerant is 

used, the chlorine will cause the oil to deteriorate.

•  Use the following tools specifically designed for use with R410A refrigerant. 

The following tools are necessary to use R410A refrigerant. Contact your 
nearest dealer for any questions.

Tools (for R410A)

Gauge manifold

Flare tool

Charge hose

Size adjustment gauge

Gas leak detector

Vacuum pump adapter

Torque wrench

Electronic refrigerant charging scale

•  Be sure to use the correct tools. If dust, debris, or moisture enters the refriger-

ant lines, refrigeration oil deterioration may result.

•  Do not use a charging cylinder. If a charging cylinder is used, the composition 

of the refrigerant will change and the efficiency will be lowered.

2. Installation location

2.1. Refrigerant pipe

Refer to Fig. 4-1.

2.2.  Choosing the outdoor unit installation location

•  Avoid locations exposed to sources of heat.
•  Select a location from which noise emitted by the unit will not inconvenience neighbors.
•  Select a location permitting easy wiring and pipe access to the power source and 

indoor unit.

•  Avoid locations where combustible gases may leak, be produced, flow, or accumulate.
•  Note that water may drain from the unit during operation.
•  Select a level location that can bear the weight and vibration of the unit.

•  Avoid locations where the unit can be covered by snow. In areas where heavy snow fall 

is anticipated, special precautions such as raising the installation location or installing a 
hood on the air intake must be taken to prevent the snow from blocking the air intake or 
blowing directly against it. This can reduce the airflow and a malfunction may result.

•  Avoid locations exposed to oil, steam, or sulfuric gas.
•  Use the transportation handles of the outdoor unit to transport the unit. If the unit 

is carried from the bottom, hands or fingers may be pinched.

2.3.  Outline dimensions (Outdoor unit) (Fig. 2-1)

Constraints on indoor unit installation

You should note that indoor units that can be connected to this outdoor unit are the 
following models. 
•  Indoor units with model numbers P06-P54 (PUMY-P36 : P06-P36) can be con-

nected. Refer to the table below for possible 1-8 (PUMY-P36 : 1-6) room, indoor 
unit combinations.

Verification

The rated capacity should be determined by observing the table below. The unit’s 
quantities are limited in 1 to 8 units. For the next step, make sure that the total rated 
capacity selected will stay in a range of 50% - 130% of the outdoor unit capacity.

•  PUMY-P36 

18,000 - 46,800 Btu/h 

•  PUMY-P48 

24,000 - 62,400 Btu/h

Indoor unit type

P06

P08

P12

P15

P18

P24

P30

P36

P48

P54

Rated capacity

(Cooling) (Btu/h)

6,000

8,000 12,000 15,000 18,000 24,000 30,000 36,000 48,000 54,000

Combinations in which the total capacity of indoor units exceeds the capacity of the 
outdoor unit will reduce the cooling capacity of each indoor unit below their rated 
cooling capacity. Thus, combine indoor units with an outdoor unit within the outdoor 
unit’s capacity, if possible.

(inch)

1.6.  Precautions for salt damage–resistant model  

(“-BS” model)

Although this product (only “-BS” model) has been designed to be resistant to salt 
damage, observe the following precautions to maintain the performance of the unit.
1. Avoid installing the unit in a location where it will be exposed directly to seawater 

or sea breeze.

2. If the cover panel may become covered with salt, be sure to install the unit in a 

location where the salt will be washed away by rainwater. (If a sunshade is installed, 
it may be difficult for rainwater to clean the panel.)

Fig. 2-1

3. To ensure that water does not collect in the base of the outdoor unit, make sure 

that the base is level, not at angle. Water collecting in the base of the outdoor unit 
could cause rust.

4. If the unit is installed in a coastal area, clean the unit with water regularly to remove 

any salt build-up.

5. If the unit is damaged during installation or maintenance, be sure to repair it.
6. Be sure to check the condition of the unit regularly.
7. Be sure to install the unit in a location with good drainage.

Содержание PUMY-P NHMU

Страница 1: ...MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci n de la unidad interior antes de instalar la unidad de aire acondicionado PARA EL INSTALADO...

Страница 2: ...ards The use of any refrigerant other than that speci ed for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case this could lead to a serious impediment...

Страница 3: ...ure enters the refriger ant lines refrigeration oil deterioration may result Do not use a charging cylinder If a charging cylinder is used the composition of the refrigerant will change and the ef cie...

Страница 4: ...outlet guides for upward air ow 2 4 2 When installing multiple outdoor units Leave 10 mm 13 32 inch space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only...

Страница 5: ...d cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly installed unit may...

Страница 6: ...ze adjustment gauge can be used to con rm A measurements Warning When installing the unit securely connect the refrigerant pipes before start ing the compressor A Liquid pipe Gas pipe PUMY 9 52 3 8 15...

Страница 7: ...lant to seal the ends of the thermal insulation around the pipe connection sections to prevent water from entering the thermal insulation Note Triple Evacuation Evacuate the system to 4 000 microns fr...

Страница 8: ...nsmission lines of different systems are wired with the same multiplecore cable the resultant poor transmit ting and receiving will cause erroneous operations 6 Electrical work 7 Only the transmission...

Страница 9: ...e same group to the terminal block on the remote controller RC d Connect together terminals M1 M2 and terminal S on the terminal block for central control TB7 for the outdoor unit OC e The jumper conn...

Страница 10: ...hat generated overcurrent may include some amount of direct current Caution Some installation site may require attachment of an earth leakage breaker If no earth leakage breaker is installed it may ca...

Страница 11: ...er carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refriger...

Страница 12: ...rminales Asimismo no empalme nunca los cables al realizar el cableado a menos que se indique lo contrario en este documento El hecho de no seguir estas instrucciones puede provocar un sobrecalenta mie...

Страница 13: ...gua de postes de iluminaci n o de tel fono Si la unidad no est bien conectada a la l nea de tierra se puede producir una descarga el ctrica Utilice disyuntores interruptor de falta de tierra interrupt...

Страница 14: ...unidades correlativas Adem s se debe dejar el espacio indicado No utilice las gu as para salida de aire opcionales para corriente de aire hacia arriba 3 Obst culos s lo en la parte delantera Fig 2 10...

Страница 15: ...otros peligros Usar un refrigerante distinto al indicado para el sistema provocar un fallo mec nico un funcionamiento defectuoso del sistema o la aver a de la unidad En el peor de los casos podr a sup...

Страница 16: ...gerante R410A Para con rmar las medidas de A se puede utilizar el ajustador del tama o Atenci n Al instalar la unidad conecte rmemente las tuber as de refrigerante antes de poner en marcha el compreso...

Страница 17: ...s ya que funcionan como selladoras para evitar fugas de refrigerante 5 Utilice un sellador para proteger las conexiones de los tubos y los extremos del material aislante no se impregnen de agua Nota V...

Страница 18: ...las l neas de transmisi n de sistemas diferentes est n conectados con los mismos cables de varias almas la pobre transmisi n y recepci n resultante dar lugar a funciones err neas 6 Trabajo el ctrico 7...

Страница 19: ...itud de esta secci n L8 deber a incluirse en longitud m xima de c lculo y la longitud total 2 Controlador remoto MA Longitud mayor a trav s de las unidades exteriores Cable M NET L1 L2 L3 L4 y L1 L2 L...

Страница 20: ...iesgo de que se produzca calentamiento o un incendio Aseg rese de escoger un interruptor de protecci n de sobrecarga adecuado No olvide que la sobrecorriente generada puede contener peque as cantidade...

Страница 21: ...r y vuelva a colocar el tap n a cada v lvula de parada Notas 1 Nunca realice el vaciado si la cantidad de refrigerante del interior de la unidad interior es superior a la cantidad de refrigerante no c...

Страница 22: ...nt sans tension sur les bornes Ne jamais effectuer de jonction sur les c bles sauf en cas d indications contraires Le non respect de cette consigne peut entra ner une surchauffe ou un incendie Le couv...

Страница 23: ...te de l appareil peut provoquer un choc lectrique Utiliser des coupe circuits disjoncteur de fuite la terre interrupteur d isolement fusible B et disjoncteur bo tier moul la capacit sp ci e Si la capa...

Страница 24: ...pacer galement les appareils comme illustr Ne pas utiliser les guidages de sortie d air en option pour un d bit d air vers le haut 3 Obstacles uniquement l avant Fig 2 10 Lors de l utilisation d un gu...

Страница 25: ...frig rant diff rent de celui sp ci pour le climatiseur peut en tra ner des d faillances m caniques des dysfonctionnements du syst me ou une panne de l appareil Dans le pire des cas cela peut entra ne...

Страница 26: ...au tableau 1 pour l vasement des tuyaux de r frig rant R410A La jauge de r glage de la taille peut tre utilis e pour con rmer les mesures A Avertissement Pendant l installation de l appareil brancher...

Страница 27: ...de l isolation thermique autour des sections de raccordement des tuyaux a n d emp cher l eau de p n trer dans l isolation thermique Remarque Triple vacuation vacuez le syst me de 4 000 microns par le...

Страница 28: ...ts syst mes devaient tre reli es par le m me c ble ls multiples la transmission et la r ception seraient mauvaises ce qui conduirait un fonctionnement erron des appareils 6 Installations lectriques 7...

Страница 29: ...IC qui poss de l adresse la plus r cente au sein d un m me groupe au bloc terminal de la commande distance RC d Connecter les bornes M1 M2 et S des blocs terminaux TB7 pour le contr le central sur les...

Страница 30: ...ous d utiliser le correct interrupteur de protection contre la surintensit de courant Veuillez noter que la surintensit de courant g n r e peut comprendre une certaine quantit de courant direct Pr cau...

Страница 31: ...rr t Remarque 1 Ne jamais proc der au pompage si la quantit de r frig rant dans l appareil int rieur est sup rieure la quantit de r frig rant sans charge suppl mentaire Le pompage lorsque la quantit d...

Страница 32: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Отзывы: