2. Installation location
3. Installing the indoor unit
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
PART NUMBER
ACCESSORY
QUANTITY
LOCATION OF
SETTING
35, 50
1
Mount board
1
Fix at the back of the
unit
2
Tapping screw 4
×
35
12
3
Felt tape
3
4
Band
3
5
Wireless remote controller
1
6
Remocon holder
1
7
Alkali batteries (size AAA)
2
8
Tapping screw 3.5
×
16
2
9
Block of cushion
1
3.2. Installing the wall mounting fixture (Fig. 3-2)
3.2.1. Setting the wall mounting fixture and piping positions
►
Using the wall mounting fixture, determine the unit’s installation position
and the locations of the piping holes to be drilled.
Warning:
Before drilling a hole in the wall, you must consult the building contractor.
■
PKA-RP·HAL
A
Mount board
1
B
Indoor unit
C
Bottom left rear pipe hole (ø65)
D
Bottom right rear pipe hole (ø65)
E
Knockout hole for left rear hole (70 × 310)
F
Bolt hole (4-ø9 hole)
G
Center measurement hole (ø2.5 hole)
H
Tapping hole (77-ø5.1 hole)
I
Hole centre
J
Align the scale with the line.
K
Insert scale.
3.2.2. Drilling the piping hole (Fig. 3-3)
►
Use a core drill to make a hole of 75-80 mm diameter in the wall in the
piping direction, at the position shown in the diagram to the left.
►
The hole should incline so that the outside opening is lower than the
inside opening.
►
Insert a sleeve (with a 75 mm diameter and purchased locally) through the
hole.
A
Sleeve
B
Hole
C
(Indoors)
D
Wall
E
(Outdoors)
Note:
The purpose of the hole’s inclination is to promote drain flow.
Fig. 2-1
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and
maintenance.
■
PKA-RP·HAL
(mm)
A
B
C
D
E
Min. 100.5
Min. 22.4
Min. 48
Min. 250
Min. 220
F
Air outlet: Do not place an obstacle within 1500 mm of the air outlet.
G
Floor surface
H
Furnishing
I
When the projection dimension of a curtain rail or the like from the wall exceeds 60 mm,
extra distance should be taken because the fan air current may create a short cycle.
J
1800 mm or greater from the floor surface (for high location mounting)
K
108 mm or greater with left or rear left piping and optional drain pump installation
L
550 mm or greater with optional drain pump installation
M
Minimum 7 mm: 265 mm or greater with optional drain pump installation
Fig. 3-1
■
PKA-RP·HAL
Fig. 3-2
(mm)
■
PKA-RP·HAL
Fig. 3-3
A
C
D
E
B
898
295
*
249
M
F
G
L
B
A
K
C
D
H
J
I
E
(mm)
1
2
3
4
5
6
7
8
9
58
2
232.5
231.5
372.3 356.3 327.5
291.5 265
225 200
125
70
15 0 15
70
125
200 225 238 265 291.5
327.5 356.3 372.3
278.3
238 213
174
0
115 140 167
180.3 193.5
20
41
66
91
116
166
0
16
28.5
53.5
78.5
103.5
128.5
153.5
178.5
241
253.5
100 m
RG79D479H02_en.indd 3
2012/10/09 (火) 午前 11:37:50