4.  Installing the refrigerant piping

4.4.1.  Storing in the piping space of the unit (Fig.4-4)

1. Wrap the supplied felt tape in the range of the refrigerant piping which will be 

housed within the piping space of the unit to prevent dripping.

2. Overlap the felt tape at one-half of the tape width.

3. Fasten the end portion of the wrapping with vinyl tape, etc.

Gas pipe

B

  Liquid pipe

C

  Indoor/outdoor connection cable

D

  Felt tape 

3

5.  Drainage piping work

5.1.  Drainage piping work (Fig. 5-1)

•  Drain pipes should have an inclination of 1/100 or more.

•  For extension of the drain pipe, use a soft hose (inner dia. 15 mm) available on 

the market or hard vinyl chloride pipe (VP-16/O.D. ø22 PVC TUBE).  Make sure 

that there is no water leakage from the connections.

•  Do not put the drain piping directly in a drainage ditch where sulphuric gas may 

be generated.

•  When piping has been completed, check that water flows from the end of the 

drain pipe.

 Caution:

The drain pipe should be installed according to this Installation Manual to 

ensure correct drainage. Thermal insulation of the drain pipes is necessary 

to prevent condensation. If the drain pipes are not properly installed and 

insulated, condensation may drip on the ceiling, floor or other possessions.

Inclined downwards

Must be lower than outlet point

Water leakage

Trapped drainage

Air

Wavy

The end of drain pipe is under water.

Drainage ditch

I

  5 cm or less between the end of drain pipe and the ground.

Drain hose

Soft PVC hose (Inside diameter 15 mm)  
or  
Hard PVC pipe (VP-16) 
* Bond with PVC type adhesive 

Preparing left and left rear piping (Fig. 5-2)

Remove the drain cap.

•  Remove the drain cap by holding the bit that sticks out at the end of the pipe and 

pulling.

Drain cap

Remove the drain hose.

•  Remove the drain hose by holding on to the base of the hose 

a

 (shown by 

arrow) and pulling towards yourself 

b

.

Insert the drain cap.

•  Insert a screwdriver etc into the hole at the end of the pipe and be sure to push 

to the base of the drain cap.

Insert the drain hose.

•  Push the drain hose until it is at the base of the drain box connection outlet.

•  Please make sure the drain hose hook is fastened properly over the extruding 

drain box connection outlet.

Hooks

 Storing in the piping space of the indoor unit (Fig. 5-3)

*  When the drain hose will be routed indoors, be sure to wrap it with commercially 

available insulation. 

*  Gather the drain hose and the refrigerant piping together and wrap them with the 

supplied felt tape 

3

*  Overlap the felt tape 

3

 at one-half of the tape width. 

*  Fasten the end portion of the wrapping with vinyl tape, etc. 

Gas pipe

Liquid pipe

Drain hose

Indoor/outdoor connection wiring 

Felt tape 

3

 Check of drainage (Fig. 5-4)

1. Open the front grille and remove the filter. 

2. Facing the fins of the heat exchanger, slowly fill with water. 

3. After the drainage check, attach the filter and close the grille. 

Fig. 5-4

Fig. 5-3

A

B

D

E

C

Fig. 5-1

A

B

C

E

D

C

F

C

G

H

I

J

K

Fig. 5-2

A

A

1

3

a

b

A

B

2

4

RG79D479H02_en.indd   7

2012/10/09 (火)   午前 11:37:54

Содержание Mr.Slim PKA-RP35HAL

Страница 1: ...begint MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto prima di installare il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unit esterna MANU...

Страница 2: ...changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage Whe...

Страница 3: ...am to the left The hole should incline so that the outside opening is lower than the inside opening Insert a sleeve with a 75 mm diameter and purchased locally through the hole A Sleeve B Hole C Indoo...

Страница 4: ...rking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Reference ma...

Страница 5: ...ve the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs on...

Страница 6: ...6 35 17 14 18 12 7 28 49 61 PKA RP HAL Fig 4 3 B A 4 2 Indoor unit Refrigerant and Drainage Piping Sizes Item Model PKA RP35 RP50HAL Refrigerant piping Liquid OD 6 35 1 4 Gas OD 12 7 1 2 Drainage pip...

Страница 7: ...r H Drainage ditch I 5 cm or less between the end of drain pipe and the ground J Drain hose K Soft PVC hose Inside diameter 15 mm or Hard PVC pipe VP 16 Bond with PVC type adhesive Preparing left and...

Страница 8: ...te control cord J Indoor outdoor connection cord K Hook L Ground wire connection portion Warning Never splice the power cable or the indoor outdoor connection cable otherwise it may result in a smoke...

Страница 9: ...ize must comply with the applicable local and national code 2 Power supply cords and Indoor unit Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 2...

Страница 10: ...door unit DIP switch settings when using separate indoor unit outdoor unit power supplies only ON OFF 1 2 SW8 3 There are three types of labels labels A B and C Affix the appropriate labels to the uni...

Страница 11: ...he min button twice continuously Pair No 0 blinks 3 Press the temp button to set the pair number you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for t...

Страница 12: ...ly 6 Complete function selection Direct the wireless remote controller toward the sensor of the indoor unit and press the button E Note Whenever changes are made to the function settings after install...

Страница 13: ...mode then check whether warm air is blown out from the unit 5 Press the FAN button and check whether fan speed changes 6 Press the VANE button and check whether the auto vane operates properly 7 Press...

Страница 14: ...U6 Compressor overcurrent interruption Abnormal of power module 10 U7 Abnormality of super heat due to low discharge temperature 11 U9 UH Abnormality such as overvoltage or voltage shortage and abnor...

Страница 15: ...ng phenomena takes place No signals from the remote controller are accepted OPE lamp is blinking The buzzer makes a short pipng sound Note Operation is not possible for about 30 seconds after cancella...

Страница 16: ...ime displayed is the number of hours the filter has been used since the filter reset was performed 4 Press the FILTER button 5 The data is displayed in C Airflow temperature display example Flashing W...

Страница 17: ...oducts Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations R...

Отзывы: