background image

14

7.  Test run

[Output pattern A]  Errors detected by indoor unit

Wireless remote controller 

Wired remote 

controller 

Symptom

Remark

Beeper sounds/OPERATION 

INDICATOR lamp flashes  

(Number of times)

Check code

1

P1

Inlet sensor error

2

P2

Pipe (TH2) sensor error

P9

Pipe (TH5) sensor error

3

E6, E7

Indoor/outdoor unit communication error

4

P4

Drain sensor error/Float switch connector open

5

P5

Drain pump error

PA

Forced compressor

6

P6

Freezing/Overheating safeguard operation

7

EE

Communication error between indoor and outdoor units

8

P8

Pipe temperature error

9

E4

Remote controller signal receiving error

10

11

12

Fb

Indoor unit control system error (memory error, etc.)

14

PL

Refrigerant circuit abnormal

No sound

E0, E3

Wired remote controller transmission error

No sound

E1, E2

Wired remote controller control board error

No sound

– – – –

No corresponding

[Output pattern B]  Errors detected by unit other than indoor unit (outdoor unit, etc.)

Wireless remote controller 

Wired remote 

controller 

Symptom

Remark

Beeper sounds/OPERATION 

INDICATOR lamp flashes 

(Number of times)

Check code

1

E9

Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)

For details, check the LED 

display of the outdoor controller 

board.

2

UP

Compressor overcurrent interruption

3

U3, U4

Open/short of outdoor unit thermistors

4

UF

Compressor overcurrent interruption (When compressor locked)

5

U2

Abnormal high discharging temperature/49C worked/insufficient refrigerant

6

U1, Ud

Abnormal high pressure (63H worked)/Overheating safeguard operation

7

U5

Abnormal temperature of heat sink

8

U8

Outdoor unit fan safeguard stop

9

U6

Compressor overcurrent interruption/Abnormal of power module

10

U7

Abnormality of super heat due to low discharge temperature

11

U9, UH

Abnormality such as overvoltage or voltage shortage and abnormal 

synchronous signal to main circuit/Current sensor error

12

13

14

Others

Other errors (Refer to the technical manual for the outdoor unit.)

*1  If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come 

on, there are no error records.

*2  If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal was received, the 

specified refrigerant address is incorrect.

OPERATION 

INDICATOR 

lamp flash 

pattern

Beep

Beep

Beep

Beep

Beep

Beep

Beep

Off

Approx. 2.5 sec.

On

Approx. 3 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

Off

Approx. 2.5 sec.

On

Approx. 3 sec.

On

0.5 sec.

On

0.5 sec.

· · · Repeated

Number of flashes/beeps in pattern indicates the check 

code in the following table (i.e., n=5 for “P5”)

Number of flashes/beeps in pattern indicates 

the check code in the following table 

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check 

starts

(Start signal 

received)

Beeper sounds

[Output pattern B]

OPERATION 

INDICATOR 

lamp flash 

pattern

Beep

Beep

Beep Beep

Beep

Beep

Beep

Off

Approx. 2.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

Off

Approx. 2.5 sec.

On

0.5 sec.

On

0.5 sec.

· · · Repeated

Number of flashes/beeps in pattern indicates the check 

code in the following table (i.e., n=5 for “P5”)

Number of flashes/beeps in pattern indicates 

the check code in the following table 

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check 

starts

(Start signal 

received)

Beeper sounds

•  Refer to the following tables for details on the check codes. (Wireless remote controller)

[Output pattern A]

RG79D479H02_en.indd   14

2012/10/09 (火)   午前 11:38:00

Содержание Mr.Slim PKA-RP35HAL

Страница 1: ...begint MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto prima di installare il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unit esterna MANU...

Страница 2: ...changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage Whe...

Страница 3: ...am to the left The hole should incline so that the outside opening is lower than the inside opening Insert a sleeve with a 75 mm diameter and purchased locally through the hole A Sleeve B Hole C Indoo...

Страница 4: ...rking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Reference ma...

Страница 5: ...ve the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs on...

Страница 6: ...6 35 17 14 18 12 7 28 49 61 PKA RP HAL Fig 4 3 B A 4 2 Indoor unit Refrigerant and Drainage Piping Sizes Item Model PKA RP35 RP50HAL Refrigerant piping Liquid OD 6 35 1 4 Gas OD 12 7 1 2 Drainage pip...

Страница 7: ...r H Drainage ditch I 5 cm or less between the end of drain pipe and the ground J Drain hose K Soft PVC hose Inside diameter 15 mm or Hard PVC pipe VP 16 Bond with PVC type adhesive Preparing left and...

Страница 8: ...te control cord J Indoor outdoor connection cord K Hook L Ground wire connection portion Warning Never splice the power cable or the indoor outdoor connection cable otherwise it may result in a smoke...

Страница 9: ...ize must comply with the applicable local and national code 2 Power supply cords and Indoor unit Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 2...

Страница 10: ...door unit DIP switch settings when using separate indoor unit outdoor unit power supplies only ON OFF 1 2 SW8 3 There are three types of labels labels A B and C Affix the appropriate labels to the uni...

Страница 11: ...he min button twice continuously Pair No 0 blinks 3 Press the temp button to set the pair number you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for t...

Страница 12: ...ly 6 Complete function selection Direct the wireless remote controller toward the sensor of the indoor unit and press the button E Note Whenever changes are made to the function settings after install...

Страница 13: ...mode then check whether warm air is blown out from the unit 5 Press the FAN button and check whether fan speed changes 6 Press the VANE button and check whether the auto vane operates properly 7 Press...

Страница 14: ...U6 Compressor overcurrent interruption Abnormal of power module 10 U7 Abnormality of super heat due to low discharge temperature 11 U9 UH Abnormality such as overvoltage or voltage shortage and abnor...

Страница 15: ...ng phenomena takes place No signals from the remote controller are accepted OPE lamp is blinking The buzzer makes a short pipng sound Note Operation is not possible for about 30 seconds after cancella...

Страница 16: ...ime displayed is the number of hours the filter has been used since the filter reset was performed 4 Press the FILTER button 5 The data is displayed in C Airflow temperature display example Flashing W...

Страница 17: ...oducts Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations R...

Отзывы: