4.  Installing the refrigerant piping

Flare cutting dimensions

Copper pipe O.D.  

(mm)

Flare dimensions  

øA dimensions (mm)

ø6.35

8.7 - 9.1

ø12.7

16.2 - 16.6

øA

Fig. 4-1

Fig. 4-2

(

)

(

)

4.1.  Connecting pipes (Fig. 4-1)

•  When commercially available copper pipes are used, wrap liquid and gas pipes 

with commercially available insulation materials (heat-resistant to 100 °C or 

more, thickness of 12 mm or more).

•  The indoor parts of the drain pipe should be wrapped with polyethylene foam 

insulation materials (specific gravity of 0.03, thickness of 9 mm or more).

•  Apply thin layer of refrigerant oil to pipe and joint seating surface before 

tightening flare nut.

•  Use two wrenches to tighten piping connections.

•  Use refrigerant piping insulation provided to insulate indoor unit connections. 

Insulate carefully.

B

 

Flare nut tightening torque

C

 

Do not apply refrigerating machine oil to the screw portions. 

 

(This will make the flare nuts more apt to loosen.)

D

 

Be certain to use the flare nuts that are attached to the main unit.  

(Use of commercially-available products may result in cracking.)

Copper pipe O.D.  

(mm)

Flare nut O.D.  

(mm)

Tightening torque  

(N·m)

ø6.35

17

14 - 18

ø12.7

28

49 - 61

 PKA-RP·HAL

Fig. 4-3

B

A

4.2.  Indoor unit

Refrigerant and Drainage Piping Sizes

Item

 

Model

PKA-RP35, RP50HAL

Refrigerant piping

Liquid

ODø6.35 (1/4")

Gas

ODø12.7 (1/2")

Drainage piping

ODø16

4.3.  Positioning refrigerant and drain piping (Fig. 4-2)

 PKA-RP·HAL

Gas pipe 

*  Indicates the condition with accessories mounted.

Liquid pipe

Drain hose (Effective length: 400)

Left-side piping knockout hole

Right-side piping knockout hole

Lower piping knockout hole

Mount board 

1

4.4.  Refrigerant piping (Fig. 4-3)

Indoor unit

1. Remove the flare nut and cap of the indoor unit.

2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil 

(available from your local supplier) to the flare sheet surface.

3. Quickly connect the on site cooling pipes to the unit. 

4. Wrap the pipe cover that is attached to the gas pipe and make sure that the 

connection join is not visible.

5. Wrap the pipe cover of the unit’s liquid pipe and make sure that it covers the 

insulation material of the on site liquid pipe.

6. The portion where the insulation material is joined is sealed by taping.

Site-side refrigerant piping

Unit side refrigerant piping

Fig. 4-2

 Warning:

When installing the unit, securely connect the refrigerant pipes before start-

ing the compressor.

90°±0.5°

45±2°

R0.4

 - R0.8

RG79D479H02_en.indd   6

2012/10/09 (火)   午前 11:37:52

Содержание Mr.Slim PKA-RP35HAL

Страница 1: ...begint MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto prima di installare il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unit esterna MANU...

Страница 2: ...changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage Whe...

Страница 3: ...am to the left The hole should incline so that the outside opening is lower than the inside opening Insert a sleeve with a 75 mm diameter and purchased locally through the hole A Sleeve B Hole C Indoo...

Страница 4: ...rking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Reference ma...

Страница 5: ...ve the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs on...

Страница 6: ...6 35 17 14 18 12 7 28 49 61 PKA RP HAL Fig 4 3 B A 4 2 Indoor unit Refrigerant and Drainage Piping Sizes Item Model PKA RP35 RP50HAL Refrigerant piping Liquid OD 6 35 1 4 Gas OD 12 7 1 2 Drainage pip...

Страница 7: ...r H Drainage ditch I 5 cm or less between the end of drain pipe and the ground J Drain hose K Soft PVC hose Inside diameter 15 mm or Hard PVC pipe VP 16 Bond with PVC type adhesive Preparing left and...

Страница 8: ...te control cord J Indoor outdoor connection cord K Hook L Ground wire connection portion Warning Never splice the power cable or the indoor outdoor connection cable otherwise it may result in a smoke...

Страница 9: ...ize must comply with the applicable local and national code 2 Power supply cords and Indoor unit Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 2...

Страница 10: ...door unit DIP switch settings when using separate indoor unit outdoor unit power supplies only ON OFF 1 2 SW8 3 There are three types of labels labels A B and C Affix the appropriate labels to the uni...

Страница 11: ...he min button twice continuously Pair No 0 blinks 3 Press the temp button to set the pair number you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for t...

Страница 12: ...ly 6 Complete function selection Direct the wireless remote controller toward the sensor of the indoor unit and press the button E Note Whenever changes are made to the function settings after install...

Страница 13: ...mode then check whether warm air is blown out from the unit 5 Press the FAN button and check whether fan speed changes 6 Press the VANE button and check whether the auto vane operates properly 7 Press...

Страница 14: ...U6 Compressor overcurrent interruption Abnormal of power module 10 U7 Abnormality of super heat due to low discharge temperature 11 U9 UH Abnormality such as overvoltage or voltage shortage and abnor...

Страница 15: ...ng phenomena takes place No signals from the remote controller are accepted OPE lamp is blinking The buzzer makes a short pipng sound Note Operation is not possible for about 30 seconds after cancella...

Страница 16: ...ime displayed is the number of hours the filter has been used since the filter reset was performed 4 Press the FILTER button 5 The data is displayed in C Airflow temperature display example Flashing W...

Страница 17: ...oducts Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations R...

Отзывы: