17
<Operation Control>
1
Specifications shared at all operation modes
The compressor and blower fan will operate for about 6 minutes after turning on the operation switch or
activating the compressor, regardless of humidity or temperature levels.
2
Humidity set operation
Compressor and blower fan operation will switch by current humidity and set temperature.
3
High, Low, Low Temp, Mildew Guard, Air Purifier
Compressor
ON
Rank
3
Rank 1
Rank 2
Rank
3
Rank 5
Rank 5
Rank 0
Rank 0
Rank 0
27
°
C
29
°
C
ON
OFF
Current humidity
– Set humidity
Decline in
current
humidity
+3%
–1%
34
°
C
36
°
C
+5%
+1%
Rise in current
humidity
Fan temperature table
Compressor
Mildew Guard
Low Temp
ON
ON
Rank
4
Rank
4
Rank 4
Rank 6
Rank
4
Rank 5
Rank 5
Rank
4
Air Purifier
OFF
Rank 1
Rank 1
Rank 1
Rank 1
Low
ON
Rank 1
Rank 2
Rank 5
Rank 1
High
ON
Rank 4
Rank 4
Rank 5
Rank 4
Fan temperature table
27
°
C
29
°
C
34
°
C
14
°
C
16
°
C
36
°
C
4
Mildew Guard mode
1.
Outline of Control
(a) Lowering the temperature once a day ‘suppresses’ mildew growth.
(b) The dehumidification time changes depending on how much the temperature was lowered (40%: 2 hours, 50%: 4 hours).
2. Under the following conditions, mildew guard will clear the time count and restart with initial settings.
Mildew guard starts with dehumidifier operations by turning ON the compressor and fan regardless of the present
humidity or time.
(a) The power is turned ON when mildew guard is selected (i.e.: power button is turned ON or ON timer time is reached).
(b) Mildew guard is selected with the MODE button.
(c) Mildew guard is reactivated by operating the air purifier button (Air purifier ON
→
OFF).
(d) Mildew guard is run for 24 hours.
3. While mildew guard is operating, the dehumidifier is deactivated under the following conditions.
(a) Current humidity below 35% detected followed by 2 hours of below 40%.
However, the accumulated time is cleared if the current humidity breaches 41% for 3 consecutive minutes during the count.
(b) Current humidity below 45% detected followed by 4 hours of below 50%.
However, the accumulated time is cleared if the current humidity breaches 51% for 3 consecutive minutes during the count.
4. After being deactivated in step 3, if the humidity level reaches 71%, the dehumidifier is automatically activated and runs
until the level drops below 65%. Below 65%, the dehumidifier remains deactivated until the humidity level again reaches
71% (limiter dehumidifier operation).
5. Mildew guard mode is disabled in the following cases.
(a) The mode button is used to activate Low Temp mode.
(b) The selection button is used to activate the previously set mode (EASY DEHUMIDIFYING/LAUNDRY).
(c) The air purifier button is used to activate AIR PURIFIER mode
2HR
2HR
4HR
4HR
45%
Elapsed time
35%
Elapsed time
Humidity level
Compressor
Blower
Mildew
Guard
ON
Below 45%
time count
start
Below 35%
time count
start
Below 35%
time count
stop
Dehumidifier
activated
Below 35%
time count
start
Dehumidifier
deactivated
Dehumidifier
deactivated
Dehumidifier
deactivated
Accumulated
time counts
reset
65%
45%
40%
35%
24HR
75%
ON
OFF
Below
45%
Below
35%
3 minutes
above 41%
elapse
Limit
71%
Limit
recovered 65%
Target part
Compressor
Airflow fan
Solenoid valve
Louvre
Operation
ON/OFF
Rank control
OFF
ON/OFF