4 SYSTEM CONFIGURATION
4.5 Rules of System Configuration and Examples of Reconfiguration
61
4
■
Number of remote I/O points
(
Page 48 Calculation of the number of remote I/O points)
■
Total number of I/O points and remote I/O points
(
Page 47 Limitation on the Number of Input/Output Points)
Check of limitation on current consumption
Check if power required for extension devices can be supplied from the CPU module and extension power supply module.
■
Check of power supply from the CPU module
(
Page 50 Power supply check from the CPU module (current consumption calculation))
Power supply capacity of the CPU module
Current consumption of extension devices
Network
No. of remote I/O points
AnyWireASLINK
64 points
Type
Model
Power supply capacity
5 V DC power supply
24 V DC power supply
CPU module
FX5UC-32MT/D
720 mA
500 mA
Type
Model
Current consumption
5 V DC power supply
24 V DC power supply
Expansion adapter
FX5-232ADP
30 mA
30 mA
Expansion adapter
FX5-485ADP
20 mA
30 mA
Input module
FX5-C16EX/D
100 mA
Output module
FX5-C16EYT/D
100 mA
100 mA
Output module
FX5-C16EYT/D
100 mA
100 mA
≤
384 points
Remote I/O points
64 points
OK
Maximum number of
Remote I/O points
≤
152 points
512 points
Number of input/output points
+
Remote I/O points
64 points
Total number of input/output points
= 216 points
Calculation result
OK
Max. number of
input/output points
350 mA
-
720 mA
CPU module
Current consumption
370 mA
=
Calculation result
OK
Capacity of 5 V DC
power supply
Total of current
consumed by extension
module
260 mA
-
500 mA
CPU module
Current consumption
240 mA
=
Calculation result
OK
Capacity of 24 V DC
power supply
Total of current
consumed by extension
module
Содержание MELSEC iQ-F FX5UC
Страница 1: ...MELSEC iQ F FX5UC User s Manual Hardware ...
Страница 2: ......
Страница 15: ...13 CONTENTS ...
Страница 183: ......