4 SYSTEM CONFIGURATION
4.3 Limitation on the Number of Input/Output Points
49
4
CC-Link IE field network Basic remote I/O
Remote I/O points that are used in CC-Link IE field network Basic are calculated as "number of occupied stations
×
64 points”.
CC-Link remote I/O
The number of remote I/O points to be used in CC-Link are calculated as "number of remote I/O stations × 32 points".
Even if using less than 32 remote I/O points, calculate as "number of remote I/O stations × 32 points."
AnyWireASLINK remote I/O
The number of I/O points set below is assigned to the remote I/O to be used with AnyWireASLINK.
• FX5-ASL-M: Set with the engineering tool parameters.
• FX3U-128ASL-M: Set with the rotary switch on the FX3U-128ASL-M main body.
For details, refer to the following manuals.
MELSEC iQ-F FX5 User's Manual (ASLINK)
FX3U-128ASL-M User's Manual
384 points
Actually used CC-Link IE field network Basic remote I/O points
stations
The total number of number of
occupied stations
64 points
=
(a)
64 points
Maximum number of CC-Link IE field
network Basic remote I/O points
(a) CC-Link IE field network
Basic remote I/O points
≥
384 points
Actually used CC-Link remote I/O points
station
=
(b)
×
32 points
• FX5-CCL-MS (master station)
256 points
• FX3U-16CCL-M
Maximum number of
CC-Link remote I/O points
(b) CC-Link remote
I/O points
The total number of the remote I/O
stations × 32 points
≥
384 points
AnyWireASLINK remote I/O
(c)
points
• FX5-ASL-M
128 points
• FX3U-128ASL-M
Maximum number of
AnyWireASLINK remote I/O
points
(c) Number of remote I/O points assigned to
AnyWireASLINK master