background image

APPX

Appendix 7  Terminal Module

169

A

FX-16E-TB/UL, FX-32E-TB/UL

*1 Replace this number with the one of the connected connector.

1

COM

3

4

5

6

0

2

7

1

3

0

2

4

5

6

7

COM

COM

COM

COM

COM

COM

COM

CN1

1

COM

3

4

5

6

0

2

7

1

3

0

2

4

5

6

7

COM

COM

COM

COM

COM

COM

COM

(19)

(20)

(17)

(18)

(15)

(16)

(13)

(14)

(11)

(12)

(9)

(10)

(7)

(8)

(5)

(6)

(3)

(4)

(1)

(2)

COM0

7
6
5
4
3
2
1
0

0

COM0

7
6

5
4

3
2

0

1

1

(19)

(20)

(17)

(18)

(15)

(16)

(13)

(14)

(11)

(12)

(9)

(10)

(7)

(8)

(5)

(6)

(3)

(4)

(1)

(2)

COM0

7
6
5
4
3
2
1
0

COM0

7
6

5
4

3
2

0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

FX-16E-TB/UL

FX-32E-TB/UL

*1

*1

*1



0 to 



7 (Smaller numbers)



0 to 



7 (Larger numbers)



0 to 



7 (Smaller numbers)



0 to 



7 (Larger numbers)

CN2

*1

Содержание MELSEC iQ-F FX5UC

Страница 1: ...MELSEC iQ F FX5UC User s Manual Hardware ...

Страница 2: ......

Страница 3: ...e Note that when an error occurs in a relay transistor or triac of an output circuit the output might stay on or off For output signals that may lead to serious accidents external circuits and mechanisms should be designed to ensure safe machinery operation in such a case Construct an interlock circuit in the program so that the whole system always operates on the safe side before executing the co...

Страница 4: ...power supplies of the CPU module and extension modules If a long time power failure or an abnormal voltage drop occurs the PLC stops and output is turned off When the power supply is restored it will automatically restart when the RUN STOP RESET switch is on RUN side WARNING Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do s...

Страница 5: ...h undue force will be applied to the PC board thereby causing nonconformities Install the product securely using a DIN rail Connect the expansion adapter securely to their designated connectors Loose connections may cause malfunctions Work carefully when using a screwdriver such as installation of the product Failure to do so may cause damage to the product or accidents Connect the extension cable...

Страница 6: ... in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the ends of stranded wires and make sure that there are no loose w...

Страница 7: ...ut off all phases of the power supply externally Failure to do so in the power ON status may cause electric shock Before modifying the program in operation forcible output running or stopping the PLC read through this manual carefully and ensure complete safety An operation error may damage the machinery or cause accidents Do not change the program in the PLC from two or more peripheral equipment ...

Страница 8: ...tor conversion adapter Extension modules bus conversion module and connector conversion module Battery CAUTION Construct an interlock circuit in the program so that the whole system always operates on the safe side before executing control for data change of the PLC in operation Read the manual thoroughly and ensure complete safety before executing other controls for program change parameter chang...

Страница 9: ...his manual content specification etc may be changed without a notice for improvement The information in this manual has been carefully checked and is believed to be accurate however if you notice a doubtful point an error etc please contact the nearest Mitsubishi Electric representative When doing so please provide the manual number given at the end of this manual CAUTION When transporting the PLC...

Страница 10: ...n Specifications 27 Built in Ethernet communication 27 Built in RS 485 communication 28 2 8 External Dimensions 28 CPU module 28 2 9 Terminal Layout 29 CHAPTER 3 PRODUCT LIST 31 3 1 Overall Configuration 31 3 2 CPU Module 32 3 3 Extension Module 33 I O module 33 Intelligent function module 36 Extension power supply module 38 Connector conversion module 38 Bus conversion module 39 3 4 Expansion Ada...

Страница 11: ...s in enclosure 64 Layout in enclosure 65 5 2 Examination for Installing Method in Enclosure 66 5 3 Procedures for Installing on and Detaching from DIN Rail 67 Preparation for installation 67 Installation of CPU module 67 Installation of extension modules extension cable type 68 Installation of terminal modules 68 Removal of CPU module 68 5 4 Procedures for Installing Directly with M4 Screws 69 Hol...

Страница 12: ...ses 109 Positioning function 109 Communication function 109 High speed counter 109 Interruption 112 Digital Switch 113 Input Matrix 115 Seven Segment with Latch 116 CHAPTER 7 OPERATION ADJUSTMENT 118 7 1 Preparation for Operation 118 Preliminary inspection 118 Procedure until operation 118 Connection with a personal computer 119 7 2 Operation and Test 120 Self diagnostic function 120 Monitoring an...

Страница 13: ...C directive CE Marking 136 Requirement for compliance with EMC directive 136 Requirement for Compliance with LVD directive 137 Caution for compliance with EC Directive 137 Appendix 3 Precautions for operating ambient temperature 139 Appendix 4 I O Module 140 Product configuration 140 Product list 140 Specifications 142 External dimensions and component names 150 Terminal layout 155 Appendix 5 Conn...

Страница 14: ...g of Batteries and Devices with Built in Batteries in EU Member States 175 Disposal precautions 175 Exportation precautions 175 Appendix 10Added and Changed Functions 176 INDEX 177 REVISIONS 178 WARRANTY 179 TRADEMARKS 180 ...

Страница 15: ...13 CONTENTS ...

Страница 16: ...n MELSEC iQ F FX5 User s Manual SLMP JY997D56001 Explains methods for the device that is communicating with the CPU module by SLMP to read and write the data of the CPU module MELSEC iQ F FX5 User s Manual CC Link IE JY997D64201 Describes CC Link IE field network module MELSEC iQ F FX5 User s Manual CC Link SH 081793ENG Describes CC Link system master intelligent device module MELSEC iQ F FX5 User...

Страница 17: ...h speed pulse input output modules Input module Generic term for Input modules extension cable type and Input modules extension connector type Input module extension cable type Generic term for FX5 8EX ES and FX5 16EX ES Input module extension connector type Generic term for FX5 C16EX D FX5 C16EX DS FX5 C32EX D and FX5 C32EX DS Output module Generic term for Output modules extension cable type and...

Страница 18: ...BSD NZ1MEM 8GBSD NZ1MEM 16GBSD L1MEM 2GBSD and L1MEM 4GBSD SD memory cards Abbreviation of Secure Digital Memory Card Device that stores data using flash memory Peripheral device Generic term for engineering tools and GOTs GOT Generic term for Mitsubishi Electric Graphic Operation Terminal GOT1000 and GOT2000 series Software packages Engineering tool The product name of the software package for th...

Страница 19: ...g Off Operating normally P RUN LED Indicates the program running status Lit Operating normally Flashing Paused Off Stopped or stop error BAT LED Indicates the battery status Flashing Battery error Off Operating normally Page 127 Checking with LEDs CARD LED Indicates whether an SD memory card can be used or not Lit Can be used or cannot be removed Flashing In preparation Off Not inserted or can be ...

Страница 20: ...ting the CPU module Page 121 Methods of running stopping and resetting RUN Runs the program STOP Stops the program RESET Resets the CPU module hold the switch on the RESET side for approximately 1 second No Name Description 1 Expansion adapter connector cover Cover for protecting the expansion adapter connector 2 Subsequent extension connector cover Cover for protecting the subsequent extension co...

Страница 21: ... that the tip of a tool does not damage the switch or case No Name Description 1 Battery cover Cover for protecting the battery connecting connector 2 Power connector for CPU module Connector for connecting power cables 3 RS 485 terminal resistor selector switch Switch for switching terminal resistance for built in RS 485 communication 3 2 1 ...

Страница 22: ...voltage up to 300 V is 2500 V 10 This index indicates the degree to which conductive material is generated in the environment in which the equipment is used Pollution level 2 is when only non conductive pollution occurs Temporary conductivity caused by condensation must be expected occasionally Dielectric withstand voltage test and insulation resistance test Perform dielectric withstand voltage te...

Страница 23: ...configuration connectable to the CPU module The value does not include the external 24 V DC power supply of extension devices The following shows the power failure detection time of the FX5UC CPU module Item Specifications Power supply voltage 24 V DC Voltage fluctuation range 20 15 Allowable instantaneous power failure time Operation can be continued upon occurrence of instantaneous power failure...

Страница 24: ...a response frequency of 50 to 200 kHz refer to Page 88 When a high speed pulse is captured FX5UC 64MT FX5UC 96MT X0 to X7 FX5UC 32MT X6 to X17 10 kHz FX5UC 64MT FX5UC 96MT X10 to X17 FX5UC 64MT FX5UC 96MT X20 and subsequent 0 1 0 05 kHz Pulse waveform Waveform T1 pulse width T2 rise fall time FX5UC 32MT X0 to X5 2 5 μs or more 1 25 μs or less FX5UC 64MT FX5UC 96MT X0 to X7 FX5UC 32MT X6 to X17 50 ...

Страница 25: ... PNP open collector transistor Input circuit insulation Photo coupler insulation Indication of input operation LED is lit when input is on DISP switch IN Input signal format FX5UC MT D FX5UC MT DSS Sink input wiring Source input wiring Item Specifications X COM 24 V DC Fuse 1 Input impedance 1 Photocoupler X COM0 Photocoupler 24 V DC 1 Input impedance 1 Fuse X COM0 Photocoupler 24 V DC Fuse 1 Inpu...

Страница 26: ... The total load current per common terminal should be the following value 8 output points common terminal 0 8 A or less 1 For details of the common refer to Page 29 Terminal Layout Y4 and subsequent 0 1 A point Open circuit leakage current 0 1 mA or less 30 V DC Voltage drop when ON Y0 to Y3 1 0 V or less Y4 and subsequent 1 5 V or less Response time Y0 to Y3 2 5 μs or less 10 mA or more 5 to 24 V...

Страница 27: ...al global Constant scan 0 2 to 2000 ms can be set in 0 1 ms increments Fixed cycle interrupt 1 to 60000 ms can be set in 1 ms increments Timer performance specifications 100 ms 10 ms 1 ms No of program executions 32 No of FB files 16 Up to 15 for user Operation specifications Execution type Standby type initial execution type scan execution type fixed cycle execution type event execution type Inte...

Страница 28: ...changed with parameter 1 Long counter LC 10 1024 points can be changed with parameter 1 Data register D 10 8000 points can be changed with parameter 1 Link register W 16 32768 points can be changed with parameter 1 Link special register SW 16 32768 points can be changed with parameter 1 No of system device points Special relay SM 10 10000 points fixed Special register SD 10 12000 points fixed Modu...

Страница 29: ...ample 0 0 0 0 127 0 0 0 etc 6 A straight cable can be used If a personal computer or GOT and CPU module are directly connected a cross cable can be used Item Specifications Data transmission speed 100 10 Mbps Communication mode Full duplex FDX Half duplex HDX 1 Interface RJ45 connector Transmission method Base band Maximum segment length The distance between hub and node 100 m Cascade connection 1...

Страница 30: ...ximum total extension distance 50 m Protocol type MELSOFT connection Non protocol communication MELSEC Communication protocol 3C 4C frame MODBUS RTU communication Predefined protocol support Inverter communication N N Network Parallel link Insulation method Not insulated Terminal resistors Built in OPEN 110 Ω 330 Ω Terminal block used European type terminal block Model W Mass weight FX5UC 32MT D F...

Страница 31: ...9 2 2 9 Terminal Layout Built in RS 485 terminal European type terminal block Built in Ethernet connector RDA RXD RDB RXD SDA TXD 5 poles SDB TXD SG GND Pin 1 2 3 4 5 6 7 8 Signal name TXD TXD RXD Not used Not used RXD Not used Not used 8 1 ...

Страница 32: ... Y36 Y37 V1 Notch Notch Input X0 X1 X2 X3 X4 X5 X6 X7 COM0 X10 X11 X12 X13 X14 X15 X16 X17 COM0 Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17 V0 Input X20 X21 X22 X23 X24 X25 X26 X27 COM X30 X31 X32 X33 X34 X35 X36 X37 COM Output Y20 Y21 Y22 Y23 Y24 Y25 Y26 Y27 COM1 Y30 Y31 Y32 Y33 Y34 Y35 Y36 Y37 COM1 Input X0 X1 X2 X3 X4 X5 X6 X7 COM X10 X11 X12 X13 X14 X15 X16 X17 COM Output...

Страница 33: ...5 16EYR ES FX5 16EYT ES FX5 16EYT ESS Network FX5 CCLIEF FX5 CCL MS FX5 ASL M Analog FX5 8AD FX5 4LC FX5 Intelligent function module Simple motion FX5 40SSC S FX5 80SSC S FX5 20PG P Positioning Expansion adapter FX5 232ADP FX5 485ADP Communication FX5 4AD ADP FX5 4DA ADP FX5 4AD PT ADP FX5 4AD TC ADP Analog CPU module FX5UC 32MT D FX5UC 32MT DSS FX5UC 64MT D FX5UC 64MT DSS FX5UC 96MT D FX5UC 96MT ...

Страница 34: ...V DC power supply 24 V DC power supply FX5UC 32MT D 32 points 16 points 16 points 24 V DC sink Transistor sink Connector 720 mA 500 mA FX5UC 32MT DSS 24 V DC sink source Transistor source FX5UC 64MT D 64 points 32 points 32 points 24 V DC sink Transistor sink Connector FX5UC 64MT DSS 24 V DC sink source Transistor source FX5UC 96MT D 96 points 48 points 48 points 24 V DC sink Transistor sink Conne...

Страница 35: ... DSS Transistor source output YR ES Relay output YT ES Transistor sink output YT ESS Transistor source output Input output module T D 24 V DC sink input Transistor sink output T DSS 24 V DC sink source input Transistor source output R ES 24 V DC sink source input relay output T ES 24 V DC sink source input transistor sink output T ESS 24 V DC sink source input transistor source output Powered inpu...

Страница 36: ...sink Connector 100 mA 65 mA FX5 C16EX DS 24 V DC sink source FX5 C32EX D 32 points 32 points 24 V DC sink Connector 120 mA 130 mA FX5 C32EX DS 24 V DC sink source Model Number of input output points Input type Output type Connection type Current consumption Total No of points No of input points No of output points 5 V DC power supply 24 V DC power supply FX5 8EX ES 8 points 8 points 24 V DC sink s...

Страница 37: ...rrent consumption Total No of points No of input points No of output points 5 V DC power supply 24 V DC power supply External 24 V DC power supply 24 V DC power supply for input circuits FX5 C32ET D 32 points 16 points 16 points 24 V DC sink Transistor sink Connector 120 mA 100 mA 65 mA FX5 C32ET DSS 24 V DC sink source Transistor source Model No of input output points Input type Output type Conne...

Страница 38: ...ut points No of output points 5 V DC power supply 24 V DC power supply FX5 16ET ES H 1 16 points 8 points 8 points 24 V DC Sink source Transistor sink Terminal block 100 mA 125 mA 82 mA 2 FX5 16ET ESS H 1 Transistor source Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply External 24 V DC power supply FX5 8AD 1 8 ch voltage input current...

Страница 39: ... 5 V DC power supply 24 V DC power supply External 24 V DC power supply FX5 CCLIEF 1 Intelligent device station for CC Link IE Field network 8 points 10 mA 230 mA FX5 CCL MS 1 Master station intelligent device station for CC Link Ver 2 00 and Ver 1 10 compatible 8 points 2 100 mA FX5 ASL M 1 4 Master for AnyWireASLINK 8 points 200 mA 100 mA 3 Model Function No of occupied input output points Curre...

Страница 40: ...fications of the extension power supply module refer to MELSEC iQ F FX5 C1PS 5V Hardware Manual 1 If the ambient temperature exceeds 40 use the extension power supply module at the following current values within the derating range Connector conversion module Connector conversion modules are used to connect FX5 extension module extension cable type in FX5UC systems Model Function No of occupied in...

Страница 41: ... extension cable and module of extension cable type except for extension power supply module Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply FX5 CNV BUSC Bus conversion from CPU module or extension modules extension connector type 8 points 150 mA FX5 CNV BUS Bus conversion from extension modules extension cable type or FX5 intelligent ...

Страница 42: ...nal 24 V DC power supply FX 16E TB Directly connected to the I O connector of a PLC 112 mA FX 32E TB 112 mA 16 points FX 16EX A1 TB 100 V AC input type 48 mA FX 16EYR TB Relay output type 80 mA FX 16EYT TB Transistor output type sink output 112 mA FX 16EYS TB Triac output type 112 mA FX 16E TB UL Directly connected to the I O connector of a PLC 112 mA FX 32E TB UL 112 mA 16 points FX 16EYR ES TB U...

Страница 43: ...n power supply module Y0 to Y17 Y20 to Y57 FX5 C32EYT D FX5 232ADP Configuration of a whole system CPU module Expansion adapter X20 to X57 FX5 C32EX D Remote I O Remote I O FX5 C32ET D Y60 to Y77 X60 to X77 Input output module Connector conversion module Intelligent module Intelligent module Intelligent module Expansion adapter Output module Input module FX5 extension module FX5 40SSC S Module No ...

Страница 44: ...om a CPU module powered input output module or extension power supply module The number of extension devices that can be connected must be determined from the power supply capacity of the CPU module or extension power supply module For details on the current consumption refer to Page 50 Limitation on Current Consumption 1 The power to the input circuit of the input module is supplied from the exte...

Страница 45: ...extension power supply module When connecting a bus conversion module in the same system connect the powered input output module directly after the extended extension cable This cannot be used with the FX3 extension module Model Limitation FX5 CCLIEF Only one module may be connected per system FX5 CCL MS One module can be connected to the system for each station type Master station 1 Intelligent d...

Страница 46: ...o 4 adapters can be connected Type Limitation Extension module Up to 16 modules can be connected to a system excluding extension power supply module and connector conversion module Extension power supply module Up to 2 modules can be connected to a system Connector conversion module Only 1 module can be connected to a system Extended extension cable Only 1 cable can be connected to a system Bus co...

Страница 47: ... function modules bus conversion module FX3 intelligent function modules Up to 8 modules can be connected Total No of FX3 intelligent function modules Up to 6 modules can be connected Type Limitations Total No of input module output module intelligent function modules and bus conversion modules Up to 10 modules can be connected Total No of intelligent function module and bus conversion modules Up ...

Страница 48: ...modules connected on the right side of the bus conversion module must be as follows Precautions FX5 extension modules cannot be connected on the right side of the bus conversion module Type Limitation Total No of I O modules intelligent function modules and bus conversion modules Up to 10 modules can be connected Total No of FX5 intelligent function modules bus conversion modules and FX3 intellige...

Страница 49: ...including input output occupied points Up to 256 points CPU module I O module Expansion adapter Connector conversion module CC Link master 1 AnyWireASLINK master 2 CC Link AnyWireASLINK system CC Link IE field network Basic system 2 Number of remote I O points Up to 384 points Remote I O station Remote I O station Remote I O station Remote I O station Number of input output points on whole system ...

Страница 50: ... then remote I O points of the intelligent function module are occupied When using CC Link master FX3U 16CCL M and AnyWireASLINK master FX3U 128ASL M together connect FX3U 128ASL M on the left side In the FX5UC CPU module FX3U 16CCL M parameters are set up by PLC program and will occupy up to 256 remote I O points Therefore the remote I O points of FX3U 128ASL M that is connected to the right side...

Страница 51: ... the rotary switch on the FX3U 128ASL M main body For details refer to the following manuals MELSEC iQ F FX5 User s Manual ASLINK FX3U 128ASL M User s Manual 384 points Actually used CC Link IE field network Basic remote I O points stations The total number of number of occupied stations 64 points a 64 points Maximum number of CC Link IE field network Basic remote I O points a CC Link IE field net...

Страница 52: ...f extension devices Page 33 Extension Module 3 Calculate the total current consumption of each power supply Type Model Power supply capacity 5 V DC power supply 24 V DC power supply CPU module FX5UC 32MT D 720 mA 500 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Expansion adapter FX5 232ADP 30 mA 30 mA Output module FX5 C32EYT D 120 mA 200 mA Input module FX5 C32EX D 1...

Страница 53: ...umption exceeds the power supply capacity of the CPU module Reconfigure the system adding extension power supply modules mA mA CPU module Total number of extension devices Current consumption 5 V DC power supply capacity mA 0 mA Calculation result 630 mA 720 mA 90 mA Ex mA mA CPU module Total number of extension devices Current consumption mA 0 mA Calculation result 230 mA 500 mA 270 mA 24 V DC po...

Страница 54: ... Intelligent function module 3 Calculate the total current consumption of each power supply Type Model Power supply capacity 5 V DC power supply 24 V DC power supply Powered input output module FX5 32ER DS 965 mA 310 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Input module FX5 16EX ES 100 mA 85 mA Output module FX5 16EYR ES 100 mA 125 mA Simple motion module FX5 40SS...

Страница 55: ...ulate following the procedure below 1 Check the power supply capacity of the extension power supply module used Page 38 Extension power supply module Type Model Power supply capacity 5 V DC power supply 24 V DC power supply Extension power supply module FX5 C1PS 5V 1200 mA 625 mA mA mA Powered input output module Current consumption mA 0 mA Calculation result Ex 460 mA 965 mA 505 mA Capacity of 5 ...

Страница 56: ...supply modules Type Model Current consumption 5 V DC power supply 24 V DC power supply Output module FX5 C32EYT D 120 mA 200 mA Connector conversion module FX5 CNV IFC Simple motion module FX5 40SSC S Input module FX5 16EX ES 100 mA Bus conversion module FX5 CNV BUS 150 mA Analog input FX3U 4AD 110 mA Power supply type Total current consumption 5 V DC power supply 480 mA 24 V DC power supply 200 m...

Страница 57: ...6 Connection to the bus conversion module connection with FX3 extension devices Type No of modules used Limitations Judgment Expansion adapter Communication 2 Up to 2 OK Type No of modules used Limitations Judgment Extension module 11 Connector conversion module is excluded Up to 16 Extension power supply modules connector conversion module are excluded OK Connector conversion module 1 Only 1 OK B...

Страница 58: ...e OK Model Limitations Judgment FX3U 128ASL M Only one module may be connected to the system Use together with the FX5 ASL M is not possible OK FX3U 64CCL Only one module may be connected to the system When using the FX5 CCL MS as the intelligent device station it cannot be used together with the FX5 CCL MS OK Type Model No of input output points No of occupied input output points CPU module FX5UC...

Страница 59: ...24 V DC power supply CPU module FX5UC 32MT D 720 mA 500 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Expansion adapter FX5 232ADP 30 mA 30 mA Expansion adapter FX5 485ADP 20 mA 30 mA Input module FX5 C16EX D 100 mA Output module FX5 C16EYT D 100 mA 100 mA Output module FX5 C16EYT D 100 mA 100 mA Output module FX5 C16EYT D 100 mA 100 mA Connector conversion module FX5 ...

Страница 60: ...nfiguration using an extension power supply module 1150 mA 720 mA CPU module Current consumption 430 mA Calculation result NG Capacity of 5 V DC power supply Total of current consumed by extension module 360 mA 500 mA CPU module Current consumption 140 mA Calculation result OK Capacity of 24 V DC power supply Total of current consumed by extension module FX5 C16EYT D FX5 C16EYT D FX5 C16EX D FX5UC...

Страница 61: ... Type No of modules used Limitations Judgment Expansion adapter Communication 2 Up to 2 OK Type No of modules used Limitations Judgment Extension module 11 Extension power supply modules connector conversion module are excluded Up to 16 Extension power supply modules connector conversion module are excluded OK Extension power supply module 1 Up to 2 OK Connector conversion module 1 Only 1 OK Bus c...

Страница 62: ...conversion module OK Model Limitations Judgment FX3U 128ASL M Only one module may be connected to the system Use together with the FX5 ASL M is not possible OK FX3U 64CCL Only one module may be connected to the system When using the FX5 CCL MS as the intelligent device station it cannot be used together with the FX5 CCL MS OK Type Model No of input output points No of occupied input output points ...

Страница 63: ...y capacity 5 V DC power supply 24 V DC power supply CPU module FX5UC 32MT D 720 mA 500 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Expansion adapter FX5 232ADP 30 mA 30 mA Expansion adapter FX5 485ADP 20 mA 30 mA Input module FX5 C16EX D 100 mA Output module FX5 C16EYT D 100 mA 100 mA Output module FX5 C16EYT D 100 mA 100 mA 384 points Remote I O points 64 points OK ...

Страница 64: ...tension power supply module FX5 C1PS 5V 1200 mA 625 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Output module FX5 C16EYT D 100 mA 100 mA Connector conversion module FX5 CNV IFC Simple motion module FX5 40SSC S Bus conversion module FX5 CNV BUS 150 mA Pulse output module FX3U 1PG 150 mA Analog input module FX3U 4AD 110 mA Temperature controller module FX3U 4LC 160 mA ...

Страница 65: ... of the assigned numbers must begin with 0 Module number of Extension modules The CPU module automatically assigns numbers 1 to 16 to intelligent function modules or bus conversion module as module numbers in order of distance from the CPU module Intelligent function modules or bus conversion module connected to the CPU module Module numbers are assigned to intelligent function modules in order of...

Страница 66: ...r in the vertical direction Always mount the PLC horizontally on the wall as shown in the following figure Spaces in enclosure Extension devices can be connected on the left and right sides of the CPU module of the PLC Keep a space of at least 50 mm between the module main body and other devices and structure If you intend to add extension devices keep necessary spaces on the left and right sides ...

Страница 67: ...ipment FX5UC CPU module FX5 C16EX FX5 C16EYT FX5 CNV IFC FX5 C16EYT FX5 232ADP 50mm FX5 CNV BC FX5 16EX Another equipment Extension module A 50 mm A A FX5UC CPU module For product dimensions or manual for various products refer to Appendix 4 I O Module Expansion adapter Input module Output module Input module Output module 50mm FX5UC CPU module Intelligent module Connector conversion module For pr...

Страница 68: ...nd direct installation The CPU module side can be installed on the DIN rail and the extension modules extended by the extended extension cable can be directly installed The PLC can be installed on a 35 mm wide DIN46277 rail The PLC can be easily moved and removed The PLC installation height is the same as the DIN rail The PLC can be installed directly in the enclosure with M4 screws For details on...

Страница 69: ...tilation slits before beginning the installation and wiring work For the affixing procedure refer to the instructions on the dust proof sheet Always remove the dust proof sheet when the installation and wiring work is completed Installation of CPU module Connect expansion adapters or extension modules extension connector type on the CPU module before mounting the PLC in the enclosure For the conne...

Страница 70: ... CPU Module and Extension Devices 1 Turn off all the power supplies connected to the CPU module extension modules or terminal modules 2 Fit the upper edge of the DIN rail mounting groove A in the right figure onto the DIN rail 3 Push the product against the DIN rail 1 Remove the connection cables including power cables and I O cables 2 Insert the tip of a flathead screwdriver into the hole of the ...

Страница 71: ...he table I O module Bus conversion module Intelligent function module For the mounting hole dimensions of intelligent function modules refer to user s manuals of each product Dimensions Model name Mounting hole pitch W Unit mm FX5 8EX ES FX5 8EYR ES FX5 8EYT ES FX5 8EYT ESS FX5 16EX ES FX5 16EYR ES FX5 16EYT ES FX5 16EYT ESS FX5 16ER ES FX5 16ET ES FX5 16ET ESS FX5 16ET ES H FX5 16ET ESS H Refer t...

Страница 72: ...Push in the DIN rail mounting hook A in the right figure of the extension module extension cable type If the DIN rail mounting hook is not pushed in the screw hole is covered and the extension module cannot be mounted This procedure may not be required depending on the model 3 Fit the extension module extension cable type B in the right figure to the holes and secure it with M4 screws C in the rig...

Страница 73: ...onnector cover A in the right figure 2 Slide the hook for coupling the expansion adapter of the CPU module B in the right figure 3 Connect the expansion adapter to the CPU module as shown in the right figure 4 Slide the hook for coupling the expansion adapter of the CPU module B in the right figure to fix the expansion adapter C in the right figure Connecting method B Expansion adapter Connecting ...

Страница 74: ...ply module can use either extension cable type or the extension connector type 1 Slide the hook for coupling the extension module A in the right figure of the existing module left side 2 Remove the subsequent extension connector cover B in the right figure 3 Connect an extension module as shown in the right figure 4 Slide the hook for coupling the extension module A in the right figure of the exis...

Страница 75: ...Cautions on mounting and removing extension cables Make sure that the pullout tab of extension cables do not touch the conductive parts of the module When removing the extension cable pull the pullout tab of the extension cable straight up 1 Remove the top cover B in the right figure of the existing module left side A in the right figure Only extension power supply module 2 Connect the extension c...

Страница 76: ...ion flathead screwdriver Slightly insert the tip of the screwdriver into part A shown in the right figure and the hook B in the right figure will come off 4 places 2 Connect the extended extension cable on the upstream side C in the right figure 3 Connect the extension cable on the downstream side D in the right figure 4 Pull the tab E in the right figure outside fit the upper cover F in the right...

Страница 77: ... only when crossover wiring to a subsequent module is performed FX5 C EX DS and FX5 C32ET DSS do not have power connectors and the power is supplied from using input connectors Thus removing the resin cover is not required Precautions To perform crossover wiring supply the power from the preceding module to the subsequent module The power cannot be supplied from the subsequent module to the preced...

Страница 78: ...the arrow Precautions If the power cable is removed by force the cable may break Connection of I O cables I O connectors Cable connection to I O connectors I O connectors conform to MIL C 83503 For I O cables refer to Page 77 Preparation of I O connectors and prepare them CPU module I O modules extension connector type a Example FX5UC 32MT D Push here with fingers Input X Output Y Example FX5UC 32...

Страница 79: ...of the terminal module and I O connectors For the connection with the terminal module refer to Page 78 WIRING Flat cables with tube On both ends 20 pin connectors are attached FX 16E 300CAB 3 m FX 16E 500CAB 5 m FX 16E 150CAB R 1 5 m Round multicore cables On both ends 20 pin connectors are attached FX 16E 300CAB R 3 m FX 16E 500CAB R 5 m Model and configuration of I O connectors Suitable wiring U...

Страница 80: ...ed wire to the terminal Page 81 Grounding 4 Wire input X terminal Connect sensors and switches to the terminals Page 84 Input Wiring 5 Wire output Y terminal Connect the load to terminals Page 94 Output Wiring 6 Wire the built in RS 485 communication terminal blocks and Ethernet communication connectors MELSEC iQ F FX5 User s Manual Serial Communication MELSEC iQ F FX5 User s Manual MODBUS Communi...

Страница 81: ...les with insulation sleeves are used Depending on the thickness of a wiring sheath used it may be difficult to insert the sheath into an insulating sleeve Refer to the external dimensions as a reference to select wires Reference Number of wires connected per terminal Wire size Tightening torque Solid wires stranded wire Wire ferrule with insulation sleeve Terminal block for built in RS 485 communi...

Страница 82: ...o a single terminal Reference For tightening terminals use a small commercially available screwdriver with a straight tip The recommended shape is shown in the figure on the right Precautions When a precision screwdriver with a small grip is used the specified tightening torque cannot be obtained Use the following screwdriver or equivalent product grip diameter 25 mm to obtain the tightening torqu...

Страница 83: ... possible so that the ground cable can be shortened Manufacturer Model Supported standard Crimp tool JST Mfg Co Ltd FV1 25 B3A UL Listed YA 1 JST Mfg Co Ltd Terminal φ3 2 6 3 mm or more φ3 2 Terminal screw Crimp terminal 6 2 mm or less 6 2 mm or less 6 3 mm or more Terminal Terminal screw Crimp terminal 6 8 mm or less 3 7 3 7 6 8 mm or less Terminal 3 7 6 0 mm or more 6 0 mm or more 3 7 Terminal s...

Страница 84: ...pply is used to them turn on the power supply at the same time with the CPU module or earlier than the CPU module When tuning off the power confirm the safety of the system and turn off the CPU module at the same time Some extension modules may not have power supply terminals FX5UC 32MT D FX5 C32EX D FX5 C32ET D FX5 16EX ES Class D grounding 1 Fuse MC MC PL Power ON Emergency stop 24 V DC MC MC FX...

Страница 85: ...er than the CPU module When tuning off the power confirm the safety of the system and turn off the CPU module at the same time Some extension modules may not have power supply terminals FX5UC 32MT DSS FX5 C32ET DSS Class D grounding 1 Fuse MC PL Power ON MC 24 V DC MC MC FX5 C32EYT DSS Power supply for loads connected to PLC output terminals For details of the emergency stop operation refer to DES...

Страница 86: ...input The connection in which the current flows from the input X terminal Page 90 Sink input wiring Source input The connection in which the current flows into the input X terminal Page 91 Source input wiring Inputs X of FX5UC MT DSS can be set to either sink input or source input However sink and source input modes cannot be mixed Sink input means a DC input signal with a current flowing from the...

Страница 87: ...t the input X is turned on by connecting 24 V DC with the COM terminal and connecting a no voltage contact or PNP open collector transistor output between the input terminal and 24 V DC to close the circuit At this time the LED corresponding to the DISP switch lights up FX5 C16EX DS does not have the DISP switch X0 to X17 of a CPU module can be used as RUN input terminals by setting parameters MEL...

Страница 88: ... designed to prevent malfunctions caused by chattering of the input contact and noise from input line Input has a response delay switching from ON to OFF and OFF to ON shown in the following table Item Specifications Input response time H W filter delay FX5UC 32MT X0 to X5 ON 2 5 μs or less OFF 2 5 μs or less FX5UC 64MT FX5UC 96MT X0 to X7 High speed pulse input output module X0 to X5 FX5UC 32MT X...

Страница 89: ...UC 64MT FX5UC 96MT X10 to X17 High speed pulse input output module X6 X7 FX5UC 64MT FX5UC 96MT X20 and subsequent 13 Input module Input output module Powered input output module Item Specifications Bleeder resistance Rb kΩ FX5UC 32MT X0 to X5 5Rp 14 Rp or less FX5UC 64MT FX5UC 96MT X0 to X7 High speed pulse input output module X0 to X5 FX5UC 32MT X6 to X17 4Rp 15 Rp or less FX5UC 64MT FX5UC 96MT X...

Страница 90: ...1 W or more bleeder resistance to the input terminal so that the sum of the load current of the open collector transistor output on the mating device and the input current of the CPU module is 20 mA or more The above mentioned restrictions are due to specifications of connecting device encoder etc Please adjust the cable length and load for connecting device Item Specifications Bleeder resistance ...

Страница 91: ...n accordance with Power Supply Wiring 3 For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance may be required FX5UC 32MT D FX5 C32EX D FX5 16EX ES FX5 CNV IFC COM COM 24 V DC S S 1 2 3 Fuse X0 X1 X0 X1 X0 X1 Power connector 3 wire sensor Input impedance Input connector Power connector Input connector 2 wire sensor Input terminal Class D grounding ...

Страница 92: ...roperly in accordance with Power Supply Wiring 3 For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance may be required FX5UC 32MT DSS FX5 C32EX DS COM0 X0 X1 COM0 X0 X1 24 V DC FX5 16EX ES S S 1 2 3 Fuse X0 X1 FX5 CNV IFC Power connector 3 wire sensor 2 wire sensor Input connector Input impedance Input connector Input terminal Class D grounding ...

Страница 93: ...Power Supply Wiring 3 For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance may be required FX5UC 32MT DSS FX5 C32EX DS COM0 X0 X1 COM0 24 V DC 1 2 3 Input terminal Fuse X0 X1 FX5 CNV IFC FX5 16EX ES S S X0 X1 Power connector Input connector Input connector Input impedance 3 wire sensor 2 wire sensor Class D grounding ...

Страница 94: ...umber with the one of the connected connector 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse COM Input number of PLC 3 wire sensor NPN Vacant terminal 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger n...

Страница 95: ... 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse COM0 1 3 wire sensor PNP Input number of PLC Vacant terminal 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 to 3 0 to 3 4 to 7 4 to 7 24 V DC 10 15 Fuse Fuse PLC input No Photocoupler power supply 100 V to 120 V AC ...

Страница 96: ...odule extension connector type and input output module extension connector type the transistor output type is a 8 point common output type Sink output common Source output common Output to make load current flow into the output Y terminal is called sink output Output to make load current flow out of the output Y terminal is called source output Sink output Source output The COM number terminals th...

Страница 97: ...o when the transistor is turned on or off differs depending on the output terminal used For specifications of each module refer to the following For output specifications of the CPU modules refer to Page 24 Output Specifications For output specifications of the I O modules refer to Page 146 Output specifications For output specifications of the terminal modules refer to Page 162 Output specificati...

Страница 98: ...es larger than the load current Contact protection circuit for inductive loads When an inductive load is connected connect a diode for commutation in parallel with the load as necessary The diode for commutation must comply with the following specifications Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external ...

Страница 99: ...ds Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load Lamp load Lamp loads generally generate rush current 10 to 15 times the stationary current Make sure that the rush current does not exceed the current corresponding to the maximum...

Страница 100: ...til the output contact is turned on and from when the coil is shut off until the output contact is turned off is approx 10 ms Output current At a circuit voltage of 240 V AC or less 250 V AC or less when the module does not comply with CE UL or cUL standards a resistance load of 2 A per point or an inductive load of 80 VA or less 100 V AC or 200 V AC can be driven For the life of the contact for s...

Страница 101: ...load Select a surge absorber with voltage rating that is suitable for the output used For other specifications refer to the following Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external interlock should be provided for interlocking along with an interlock in the PLC program as shown below In phase PLC output ...

Страница 102: ...rent Current of 0 3 A can flow per one output point However current of four output points should be 0 8 A average of 0 2 A per one point to suppress temperature rise When a load with a high rush current is frequently turned on or off the mean square current should be 0 2 A or less Open circuit leakage current C R absorbers are connected in parallel at the triac output terminal for turning off the ...

Страница 103: ...ow In phase PLC output contacts 1 should be used in an in phase manner C R absorbers are connected in parallel at the triac output circuit for turning off the triac When a minute current load of 0 4 VA or less 100 V AC or 1 6 VA or less 200 V AC is connected a surge absorber must be connected in parallel with the load Select a surge absorber with the rated voltage that is suitable for the output u...

Страница 104: ... output Sink output type 1 represents a vacant terminal 5 to 30 V DC Fuse Load Y0 COM0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 MC1 MC2 MC2 MC1 COM0 Inductive load Fuse Fuse Fuse Load Y0 COM0 Y1 Y2 Y3 COM0 FX5UC 32MT D FX5 C32EYT D Fuse Load Y0 Y1 Y2 Y3 FX5 16EYT ES COM0 FX5 CNV IFC 1 ...

Страница 105: ...e output type 1 represents a vacant terminal 5 to 30 V DC Load Y0 V0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 MC1 MC2 MC2 MC1 V0 Inductive load Load Y0 V0 Y1 Y2 Y3 V0 FX5UC 32MT DSS FX5 C32EYT DSS Load Y0 Y1 Y2 Y3 FX5 16EYT ESS V0 FX5 CNV IFC Fuse Fuse Fuse 1 ...

Страница 106: ... 6 Output Wiring Relay output 1 represents a vacant terminal 24 V DC Fuse Load Y0 COM0 Y1 COM0 FX5UC 32MT D Fuse COM0 Y0 Y1 Y2 Y3 FX5 8EYR ES COM1 Y4 Y5 Y6 Y7 Fuse AC power supply 100 to 240 V FX5 CNV IFC Load 1 Load ...

Страница 107: ...DSS 1 Replace this number with the one of the connected connector 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 Vacant terminal 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 COM0 24 V DC MC1 MC2 COM COM COM COM COM COM COM COM 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse Fuse Fuse 1 Output number of PLC 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 Vacant terminal 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 V0 24 V DC MC1 MC2 COM COM COM COM COM...

Страница 108: ...elay output contacts FX 16EYT TB Connectable models FX5UC MT D FX5 C EYT D FX5 C32ET D For external wiring precautions refer to Page 96 Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse 0 to 7 Smaller numbers 0 to 7 Larger numbers PLC output No Relay power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 C...

Страница 109: ... C EYT DSS FX5 C32ET DSS For external wiring precautions refer to Page 96 Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse PLC output No Photocoupler power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse PLC output ...

Страница 110: ... Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 U U U U U 24 V DC Surge absorbers are connected to each output Fuse Fuse Fuse Load Fuse PLC output No Photocoupler power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 U U U U U 24 V DC Surge absorber...

Страница 111: ...ction Blocks Positioning function For wiring examples for the positioning function refer to MELSEC iQ F FX5 User s Manual Positioning Control CPU module built in High speed pulse input output module Communication function For wiring of the built in RS 485 communication terminal blocks and communication adapters refer to the following MELSEC iQ F FX5 User s Manual Serial Communication MELSEC iQ F F...

Страница 112: ...put Operation mode CH1 CPU module or CH9 high speed pulse input output module 1 phase 1 input S W Invalid Invalid Normal mode FX5UC 32MT D COM X0 A phase B phase Z phase 0 V 24 V Rotary encoder Class D grounding Fuse FX5 16ET ES H FX5UC 32MT D 24 V DC FX5UC 32MT D COM 0 V 24 V Rotary encoder Class D grounding Fuse 24 V DC FX5 CNV IFC FX5 16ET ES H X0 S S 1 5 k 1 1 1 5 k A phase B phase Z phase FX5...

Страница 113: ...24 V DC X3 COM X2 FX5UC 32MT D FX5 16ET ES H FX5UC 32MT D 0 V 24 V Rotary encoder Fuse 24 V DC COM X3 X2 FX5 CNV IFC FX5 16ET ES H S S Class D grounding 1 Class D grounding 1 1 5 k 1 5 k A phase B phase Z phase A phase B phase Z phase 1 The grounding resistance should be 100 or less FX5UC 32MT DSS 0 V 24 V Rotary encoder Fuse 24 V DC X3 COM0 X2 FX5UC 32MT DSS Sink input wiring FX5 16ET ESS H FX5UC...

Страница 114: ... or less 1 The grounding resistance should be 100 Ω or less 3 wire sensor of PNP open collector transistor output 1 The grounding resistance should be 100 Ω or less Fuse 24 V DC X0 COM 3 wire type FX5UC 32MT D FX5UC 32MT D FX5 16ET ES H Fuse 24 V DC COM 3 wire type FX5UC 32MT D X0 FX5 CNV IFC FX5 16ET ES H S S Class D grounding 1 Class D grounding 1 1 5 k 1 5 k FX5UC 32MT DSS Fuse 24 V DC X0 COM0 ...

Страница 115: ...32MT D Source wiring The example is the wiring for the input output of the FX5UC 32MT DSS 1 The grounding resistance should be 100 Ω or less DSW SM400 X10 Y10 D100 K1 COM X10 X11 X12 X13 X15 X14 X16 X17 COM0 Y10 Y11 Y12 Y13 Sink input FX5UC 32MT D 1 2 4 8 103 102 101 100 103 102 101 100 Transistor output sink COM0 Fuse 24 V DC 1 Digital switch of BCD 0 1 A 50 V diode is necessary Class D grounding...

Страница 116: ...Blocks Example of program Example of wiring Sink wiring The example is the wiring for the input output of the FX5UC 32MT D Source wiring The example is the wiring for the input output of the FX5UC 32MT DSS 1 The grounding resistance should be 100 Ω or less BIN SM400 K2X10 D102 COM X10 X11 X12 X13 X15 X14 X16 X17 1 2 4 8 1 2 4 8 101 100 Fuse 24 V DC Class D grounding 1 FX5UC 32MT D COM0 X10 X11 X12...

Страница 117: ... Y11 Y12 Y13 Y14 Y15 Y16 Y17 M30 M31 M32 M33 M34 M35 M36 M37 M40 M41 M42 M43 M44 M45 M46 M47 M50 M51 M52 M53 M54 M55 M56 M57 Transistor output sink X11 X13 X15 X17 X12 X14 X16 X11 X13 X15 X17 X12 X14 X16 Fuse 24 V DC Class D grounding 1 COM0 Sink input FX5UC 32MT D 0 1 A 50 V diode is necessary When the input points X0 to X17 are used connect a pull up resistor 3 3 k 0 5 W COM0 X10 V0 X11 X12 X13 ...

Страница 118: ...ce wiring The example is the wiring for the input output of the FX5UC 32MT DSS 1 Use a 7 segment display with a latch and a built in BCD decoder SEGL SM400 D100 Y10 K1 103 102 101 100 1 2 4 8 103 102 101 100 1 2 4 Y10 COM0 Y11 Y12 Y13 Y14 Y15 Y16 Y17 8 Transistor output sink 1 COM0 FX5UC 32MT D Signal 7 segment display Y COM1 PLC 7 segment display used for sink wiring for transistor output Fuse In...

Страница 119: ...e is the wiring for the input output of the FX5UC 32MT DSS BCD SM400 D100 K2Y10 Y10 COM0 Y11 Y12 Y13 Y14 Y15 Y16 Y17 1 2 4 8 1 2 4 8 8 4 2 1 8 4 2 1 Signal 7 segment display Y COM1 PLC 7 segment display used for sink wiring for transistor output COM0 FX5UC 32MT D Transistor output sink Fuse Internal circuit Y10 V0 Y11 Y12 Y13 Y14 Y15 Y16 Y17 1 2 4 8 1 2 4 8 8 4 2 1 8 4 2 1 V0 FX5UC 32MT DSS Transi...

Страница 120: ...l Procedure until operation The procedure until operation is explained below 1 Turn on the power of the system Check the following items before turning on the power of the system When the CPU module with the factory default setting is powered on the ERR LED flashes because the module has no programs The power connector is connected correctly The power supply voltage is within the specified range T...

Страница 121: ...ersonal computer are shown below Ethernet connection Ethernet port direct connection GX Works3 settings For the FX5 CPU module the Ethernet adapter on the personal computer side used for the Ethernet port direct connection can be specified Click the CPU Module Direct Coupled Setting button on the Specify Connection Destination Connection window to display the CPU Module Direct Coupled Setting wind...

Страница 122: ... the RUN instruction Page 121 Running Stopping and Resetting If any error is detected the ERR LED flashes or lights up Monitoring and debugging The ON OFF status of PLC s devices current values or set values can be monitored or changed by using engineering tools For details refer to GX Works3 Operating Manual No Item Selection item Internal setting Input value 1 PC side I F Serial USB RS 232C COM ...

Страница 123: ...status of the CPU module can be changed externally with the RUN STOP RESET switch set to the RUN position The operation status of the CPU module can be set to the PAUSE status Remote operation can be performed by either of the following methods Using contacts MELSEC iQ F FX5 User s Manual Application Using engineering tools GX Works3 Operating Manual Using external devices using SLMP MELSEC iQ F F...

Страница 124: ...s normal Page 127 Checking with LEDs User s manuals for each module Item Inspection item Description 1 Ambient environment Operating ambient temperature The temperature in the panel should be 20 to 55 1 Operating ambient humidity The humidity in the panel should be 5 to 95 RH Working atmosphere Free from corrosive or flammable gas and excessive conductive dust 2 Power supply voltage Voltage within...

Страница 125: ... CPU module during shipment from the factory To use the battery attach it following the procedure below Parameter setting is required to back up the device memory and clock data using the battery Page 124 Setting an optional battery using the engineering tool Attachment procedure 1 Turn the power supply off 2 Remove the battery cover A in the figure below 3 Push the battery into the battery holder...

Страница 126: ... When the battery voltage is low the BAT LED on the panel flashes red while the power is on and SM51 SM8005 and SM52 SM8006 turn ON The memory can be retained for about one month after the LED turned on However the drop in battery voltage may not be detected immediately Prepare a new battery and replace the battery with new one promptly Standard life of FX3U 32BL 5 years at ambient temperature of ...

Страница 127: ...connect the battery connector B in the figure below from the old battery and remove the battery from the battery holder C in the figure below 4 Install the new battery Page 123 Battery attachment 5 Attach the battery cover After replacing the battery check whether the devices set by the latch and clock data are backed up correctly confirm safety and then run the PLC If the devices set by the latch...

Страница 128: ...when the battery voltage is the specified value or less The special relay turns OFF when the battery voltage returns is normal SM51 SM8006 The special relay turns ON when the battery voltage is the specified value or less The special relay status ON even when the battery voltage is normal SD8005 Battery voltage can be monitored SM52 SM8005 Battery low voltage Y1 is output when a battery low voltag...

Страница 129: ... the cause of the error and take corrective actions 9 2 Checking with LEDs Check the module status with LEDs as a means to perform the primary diagnosis Checking the PWR LED If the PWR LED is turned off check the following items If the PWR LED still does not turn on even after the items shown above are checked there may be a hardware issue Consult your local Mitsubishi Electric representative Chec...

Страница 130: ... flashes Set the CPU module to the STOP status and turn on the power supply again When the ERR LED turns off a watchdog timer error has probably occurred Take any of the following measures Review the program and avoid the maximum value SD524 SD525 of the scan time exceeding the setting value of the scan time monitoring time which was set with parameters Check that the input used for input interrup...

Страница 131: ...ing generated and its detailed information Information required for troubleshooting such as the current error details and cause of the error and action to be taken are displayed The incorrect parameter setting and program error location can also be identified by selecting the error and clicking the Error Jump button On the Module Information List tab the LED status and the switch status of the tar...

Страница 132: ... be displayed the error cause can be identified based on the errors The displayed information can also be saved in CSV file format Diagnostics Module diagnostics CPU Diagnostics Event History button Use the event history function to identify the cause of failure that occurred in facilities or devices For details on this function and collected information refer to the following MELSEC iQ F FX5 User...

Страница 133: ... Page 132 Canceling Errors Operation settings of the CPU module on occurrence of an intelligent function module error The operation of the CPU module on occurrence of an intelligent function module error can be set with an engineering tool Configure the settings with I O Assignment Setting in the system parameters Error status Program execution status Description Required action Major error Stop T...

Страница 134: ...s and buffer memory using the engineering tool is explained below Online Read from PLC 1 Click the Device Memory check box 2 Click Detail 3 Input character strings in Device Data Name and select the devices to back up 4 Select the Buffer Memory Intelligent Module No and input module number 5 Click OK and then click Execute to read the data from the PLC 9 6 Canceling Errors Only continuable errors ...

Страница 135: ...o check Action FX5UC MT D Remove the external wiring and short circuit the COM terminal and the input terminal Check that the input turns on with LEDs and peripheral devices When the input turns on Check that the input device does not have a built in diode or parallel resistance If so refer to Page 86 Precautions for connecting input devices When the input does not turn on Remove the external wiri...

Страница 136: ...ails on the boot operation refer to MELSEC iQ F FX5 User s Manual Application Boot operation Boot operation cannot be performed from the SD memory card If the boot operation cannot be performed even after the items shown above are checked there may be a hardware issue Consult your local Mitsubishi Electric representative Item to check Action Check if a password is not registered Authenticate a pas...

Страница 137: ...U module Check on the module front surface The year and month of production of the product can be checked from the manufacturer s serial number LOT on the front at the bottom of the CPU module FX5UC 32MT D 24VDC OUT 5 30VDC MAC 0 1A 5W MAX 1 5 1 0 0 0 1 Right side Example nameplate manufacturer s serial number 1510001 Actual product nameplate differs from the example shown above 5 1 1 0 0 0 Contro...

Страница 138: ... in industrial applications Product compatibility Type Programmable controller open type equipment Models FX5 manufactured from October 1st 2014 FX5 8EX ES FX5 8EYR ES FX5 8EYT ES FX5 8EYT ESS FX5 16EX ES FX5 16EYR ES FX5 16EYT ES FX5 16EYT ESS FX5 232ADP FX5 485ADP FX5 CNV BUS from January 1st 2015 FX5UC 32MT D FX5UC 32MT DSS FX5 C32EX D FX5 C32EYT D FX5 C32ET D FX5 C32EX DS FX5 C32EYT DSS FX5 C3...

Страница 139: ...uracy between 10 10 in very heavy industrial areas However Mitsubishi Electric suggests that if adequate EMC precautions are followed with general good EMC practice for the user s complete control system users should expect normal errors as specified in this manual Sensitive analog cables should not be laid in the same trunking or cable conduit as high voltage cabling Where possible users should r...

Страница 140: ...ket of a shielded twisted pair cable as shown below and ground as much of the exposed shield as possible to both sides of the cables Connect a ferrite core to both ends of the cable Ferrite core used in tests by Mitsubishi ZCAT2035 0930A manufactured by TDK Co The control cabinet must be conductive Ground the control cabinet with the thickest possible grounding cable To ensure that there is electr...

Страница 141: ...ing closing of the control panel or other reasons condensation may occur which may cause a fire fault or malfunction Furthermore use an air conditioner in dehumidifier mode to prevent condensation Related devices which cannot be used at an operating ambient temperature below 0 The following devices cannot be used at an operating ambient temperature below 0 Specifications when used at an operating ...

Страница 142: ...t Output Connection type Type No of points Common wiring system Type No of points Common wiring system Input extension sink and source input type FX5 8EX ES 24 V DC 8 Terminal block FX5 16EX ES 24 V DC 16 Terminal block Model Input Output Connection type Type No of points Common wiring system Type No of points Common wiring system Output extension sink output only FX5 C16EYT D Transistor 16 Connec...

Страница 143: ...put Output Connection type Type No of points Common wiring system Type No of points Common wiring system Input output extension sink and source input relay output only FX5 16ER ES 24 V DC 8 Relay 8 Terminal block Input output extension sink and source input sink output only FX5 16ET ES 24 V DC 8 Transistor 8 Terminal block Input output extension sink and source input source output only FX5 16ET ES...

Страница 144: ...C 8 Transistor 8 Terminal block Input output extension sink and source input source output only FX5 16ET ESS H 24 V DC 8 Transistor 8 Terminal block Item Specifications Voltage rating 24 V DC supplied from external power supply 5 V DC supplied from PLC Current consumption 5 V DC FX5 C16EX 100 mA FX5 C32EX 120 mA FX5 8EX ES 75 mA FX5 16EX ES 100 mA Current consumption 24 V DC FX5 C16EX 65 mA 1 FX5 ...

Страница 145: ...nt consumption 24 V DC FX5 C32ET Input 65 mA 1 Output 100 mA FX5 16E E 125 mA The current of the input circuit is included 2 Item Specifications Voltage rating 24 V DC Allowable supply voltage range 16 8 to 28 8 V DC Allowable instantaneous power failure time Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less Power fuse 250 V 3 15 A time lag fuse Rush curren...

Страница 146: ... ES 8 points FX5 16EX ES 16 points FX5 32E D 16 points FX5 16ER ES 8 points FX5 16ET E 8 points Connection type FX5 C EX FX5 C32ET Connector FX5 EX ES FX5 32E D FX5 16ER ES FX5 16ET E Terminal block M3 screws Input type FX5 C EX D FX5 C32ET D Sink FX5 C EX DS FX5 C32ET DSS FX5 EX ES FX5 32E D FX5 16ER ES FX5 16ET E Sink source Input signal voltage 24 V DC 20 15 Input signal current Other than FX5 ...

Страница 147: ... on With FX5 C32EX the lower number higher number order is switched with the DISP switch F L With FX5 C32ET the input output is switched with the DISP switch IN OUT Input circuit configuration FX5 C EX D FX5 C32ET D FX5 C EX DS FX5 C32ET DSS FX5 EX ES FX5 16ER ES FX5 16ET E FX5 32E D Item Specifications Photocoupler X COM 24 V DC Photocoupler Photocoupler Source input wiring X COM Sink input wirin...

Страница 148: ...h IN OUT Max load FX5 C EYT D FX5 C32ET D 0 1 A point The total load current of resistance loads per common terminal should be the following value 8 output points common terminal 0 8 A or less FX5 EYT ES FX5 16ET ES FX5 32ET DS FX5 16ET ES H 0 5 A point The total load current of resistance loads per common terminal should be the following value 4 output points common terminal 0 8 A or less 8 outpu...

Страница 149: ...tion of output operation LED is lit when output is on With FX5 C32EYT the lower number higher number order is switched with the DISP switch F L With FX5 C32ET the input output is switched with the DISP switch IN OUT Max load FX5 C EYT DSS FX5 C32ET DSS 0 1 A point The total load current of resistance loads per common terminal should be the following value 8 output points common terminal 0 8 A or l...

Страница 150: ... EYT ESS FX5 16ET ESS FX5 32ET DSS 0 2 ms or less 200 mA at 24 V DC FX5 16ET ESS H Y0 Y1 Y4 Y5 2 5 μs or less 10 mA at 5 V to 24 V DC Y2 Y3 Y6 Y7 0 2 ms or less 200 mA at 24 V DC Maximum frequency FX5 16ET ESS H Y0 Y1 Y4 Y5 200 kpps Voltage drop when ON 1 5 V or less Y0 Y1 Y4 and Y5 of FX5 16ET ESS H is 1 0 V or less Output circuit configuration FX5 C EYT DSS FX5 C32ET DSS FX5 EYT ESS FX5 16ET ESS...

Страница 151: ... CE UL or cUL standards Output circuit insulation Mechanical insulation Indication of output operation LED is lit when output is on Max load 2 A point The total load current of resistance loads per common terminal should be the following value 4 output points common terminal 8 A or less 8 output points common terminal 8 A or less Open circuit leakage current Min load 5 V DC 2 mA reference values R...

Страница 152: ...powered or not Lit Powered Off Not powered or hardware error 3 I O display LED Lit when input or output is on 4 I O connectors Connector for connecting input signal cables or output signal cables 5 DISP switch Switches the display of smaller and larger numbers of the input display LED or output display LED Smaller number F Larger number L 6 Extension connector Connector for connecting the extensio...

Страница 153: ...or for connecting the extension cable of an extension module Model W mm FX5 C32ET D FX5 C32ET DSS 20 1 No Name Description 1 Extension connector Connector connected to extend modules 2 PWR LED Indicates whether the input output modules are powered or not Lit Powered Off Not powered or hardware error 3 I O display LED Lit when input or output is on 4 Input connector Connector for connecting input s...

Страница 154: ...POWER LED Indicates whether the input modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab They are used when drawing out an extension cable 4 Extension cable Cable used to connect the extension module 5 Extension connector Connector for connecting the extension cable of an extension module Without cover W 8 83 80 mounting hole pitch 90 2 4 5 mountin...

Страница 155: ...t is on 5 Output display LED Lit when output is on 6 Extension connector cover for next module Cover for protecting the extension connector cover for next module 7 Extension connector for preceding module Connector for connecting the supplied extension cable that connects to the preceding module the CPU module side 8 Terminal block mounting screws Gradually loosen the left and right screws alterna...

Страница 156: ... is on 2 POWER LED Indicates whether the input modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab They are used when drawing out an extension cable 4 Extension cable Cable connected to extend modules 5 Extension connector Connector for connecting the extension cable of an extension module Without cover W 8 83 80 mounting hole pitch 90 2 4 5 mountin...

Страница 157: ... Y7 COM1 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM1 Notch Smaller numbers Larger numbers Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Input X0 X1 X2 X3 X4 X5 X6 X7 COM X0 X1 X2 X3 X4 X5 X6 X7 COM Notch Input X0 X1 X2 X3 X4 X5 X6 X7 COM0 X0 X1 X2 X3 X4 X5 X6 X7 COM0 Notch Input X0 X1 X2 X3 X4 X5 X6 X7 COM0 X0 X1 X2 X3 X4 X5 X6 X7 COM0 Input X0 X1 X2 X3 X4 X5 X6 X7 COM1 X0 X1 X2 X3 X4 Notch X5...

Страница 158: ... 5 6 7 V 1 X 0 C O M 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 S S X 0 S S 1 2 3 4 5 7 6 X 0 1 2 3 4 5 6 7 Smaller numbers Larger numbers Y 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 Smaller numbers Larger numbers C O M 0 C O M 1 Y 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 Smaller numbers Larger numbers V 0 V 1 X 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 V S S Y4 2 3 V1 1 Y0 V0 5 6 7 Y0 1 2 3 Y4 5 6 7 V2 V3 FX5 32ET DSS X0 S S 1 2 ...

Страница 159: ... are the same as those for the CPU module Page 20 Generic Specifications External color weight accessories Model W mm FX5 CNV IF 14 6 No Name Description 1 Extension connector for preceding module The extension connector that connects to the preceding module the CPU module side 2 Extension connector for next module Connector for connecting the extension connector of an extension module extension c...

Страница 160: ...iant with IEC61131 2 The SDHC memory card can be used only with devices with an SDHC logo or whose user s manual lists an SDHC logo Note that SDHC cards cannot be used with devices that support only SD specifications Turning off or resetting the CPU module or removing the SD memory card while the card is being accessed may corrupt the data in the SD memory card Always turn off or reset the CPU mod...

Страница 161: ...n When SM605 mount and remove memory card disabling flag is ON the CARD LED is not turned OFF even if the SD memory card stop switch is pressed If the CARD LED is not turned OFF turn ON SM606 instruction of forcibly stop using SD memory card so that the SD memory card cannot be used 1 Insert the SD memory card 1 straight into the SD memory card slot Make sure that the notch of the card is directed...

Страница 162: ...D FX5 C32ET D 24 V DC 48 mA FX 16EYR TB 16 Relay output type FX5UC MT D FX5 C EYT D FX5 C32ET D 24 V DC 80 mA FX 16EYT TB 16 Transistor output type sink 24 V DC 112 mA FX 16EYS TB 16 Triac output type Sink and source common input source output transistor output FX 16E TB UL 16 input points or 16 output points Directly connected to I O terminals of a PLC FX5UC MT DSS FX5 C EX DS FX5 C EYT DSS FX5 C...

Страница 163: ...60 Hz Input sensitivity ON 3 8 mA 80 V AC or more OFF 1 7 mA 30 V AC or less Input response time 1 25 to 30 ms Input signal format Voltage contact Input circuit insulation Photo coupler insulation Indication of input operation No input LED However the 24 V power LED display exists Power consumption 1 2 W 48 mA 24 V DC Input output configuration circuit Unsupported applications High speed counter i...

Страница 164: ...cuit Mechanical insulation Indication of output operation LED is lit when the power is supplied to relay coils Power consumption 1 92 W 80 mA 24 V DC Input output configuration circuit FX 16EYR TB FX 16EYR ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O func...

Страница 165: ...nsulation Indication of output operation LED is lit when the power is supplied to photo couplers Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit FX 16EYT TB FX 16EYT ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O function D HIOEN i...

Страница 166: ...e of output element 1 5 V Insulation of circuit Photo coupler insulation Indication of output operation LED is lit when the power is supplied to photo couplers Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of ...

Страница 167: ...n Indication of output operation LED is lit when the power is supplied to photo thyristors Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit FX 16EYS TB FX 16EYS ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O function D HIOEN instruc...

Страница 168: ...or connecting input signal cables or output signal cables for CN2 FX 32E TB and FX 32E TB UL only 3 POWER LED Indicates the conduction status FX 16EX A1 TB only Lit Powered Off Not powered or hardware error 4 Operation display LED Turns on when the output is on FX 16EYR TB FX 16EYR ES TB UL FX 16EYT TB FX 16EYT ES TB UL FX 16EYTESS TB UL FX 16EYS TB and FX 16EYS ES TB UL only 5 Terminal block for ...

Страница 169: ...5 6 7 COM COM Smaller numbers Larger numbers CN1 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Smaller numbers Larger numbers CN2 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Smaller numbers Larger numbers CN1 CN2 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM2 0 1 2 3 COM3 COM3 4 5 6 7 COM4 COM4 Smaller numbers Larger numbers 24 24 POWER 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM...

Страница 170: ...9 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM 7 6 3 2 1 0 COM 7 6 5 4 3 2 1 0 CN1 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM 7 6 5 4 3 2 1 0 0 COM 7 6 5 4 3 2 0 1 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 FX 16E TB FX 32E TB 1 1 1 0 to 7 Smaller numbers 0 to 7 Larger numbers 0 to 7 Smaller numbers 0 to 7 Larger numbers 5 4 1 C...

Страница 171: ... 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM0 7 6 5 4 3 2 1 0 0 COM0 7 6 5 4 3 2 0 1 1 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM0 7 6 5 4 3 2 1 0 COM0 7 6 5 4 3 2 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 FX 16E TB UL FX 32E TB UL 1 1 1 0 to 7 Smaller numbers 0 to 7 Larger numbers 0 to 7 Smaller numbers 0 to 7 Larger numbers CN2...

Страница 172: ... COM4 COM4 4 to 7 20 COM 6 7 5 4 3 2 1 0 COM 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 CN1 Photocoupler Photocoupler Photocoupler Photocoupler 0 to 3 0 to 3 4 to 7 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 0 to 7 Smaller numbers 0 to 7 Larger numbers 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM0 6 7 5 4 3 2 1 0 COM0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 1...

Страница 173: ...2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 4 5 6 7 1 1 3 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM0 6 7 5 4 3 2 1 0 COM0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3 3 k 3 3 k 3 3 k 3 3 k 2 2 2 2 0 to 7 Smalle...

Страница 174: ...V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3 3 k 3 3 k 3 3 k 3 3 k 0 to 7 Smaller numbers 0 to 7 Larger numbers 1 1 Photo coupler Photo coupler 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3...

Страница 175: ... 5 6 7 3 3 k 3 3 k U U U U U Surge absorbers are connected to each output 3 3 k 3 3 k 0 to 7 Smaller numbers 0 to 7 Larger numbers 1 1 Photo thyristor Photo thyristor Photo thyristor Photo thyristor Photo thyristor Photo thyristor 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 ...

Страница 176: ...ot include batteries when shipped from the factory Battery only spare parts and optional parts 1 Weight in packaging Precautions for transportation When transporting the product above follow IATA Dangerous Goods Regulations IMDG Code International Maritime Dangerous Goods Code and domestic transportation regulations in each country For details contact the transportation company to be used Model Ba...

Страница 177: ...ry Directive 2006 66 EC Article 20 Information for end users and Annex II Exportation precautions The new EU Battery Directive 2006 66 EC requires the following when marketing or exporting batteries and or devices with built in batteries to EU member states To print the symbol on batteries devices or their packaging To explain the symbol in the manuals of the products Labeling To market or export ...

Страница 178: ...ting Manual for details on the software version Add Change Function Supported CPU module firmware version Supported engineering tool software version Reference High speed input output module is supported 1 030 and above 1 025B and above Page 36 FX5 CCLIEF is supported 1 030 and above 1 025B and above Page 37 Event history is supported 1 040 and above 1 030G and above Page 130 FX5 80SSC S is suppor...

Страница 179: ... product certification label 18 I I O display LED 17 Input connector 17 Installation Location 64 Installing directly 69 M Memory capacity 25 N Nameplate 18 Number of input output points 42 O Operation status display LED 17 Output connector 18 P P RUN LED 17 Power connector for CPU module 19 PWR LED 17 R RD LED 17 Remote I O points 48 RS 485 terminal resistor selector switch 19 RUN STOP RESET switc...

Страница 180: ...d or modified parts RELEVANT MANUALS TERMS Section 2 1 2 6 3 1 3 3 3 9 Chapter 4 5 Section 6 5 6 6 6 7 8 2 Appendix2 3 4 October 2016 E Added models FX5 16ER ES FX5 16ET ES FX5 16ET ESS FX5 80SSC S FX5 4AD PT ADP FX5 4AD TC ADP Added or modified parts RELEVANT MANUALS TERMS Section 2 6 3 1 3 3 4 1 4 2 6 5 6 6 9 1 9 3 Appendix 2 4 6 10 April 2017 F Added models FX5 8AD FX5 4LC FX5 20PG P FX5 CCL MS...

Страница 181: ...tions in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies and applications in which a special quality assurance system is required such as for railway companies or public service purposes shall be excluded from the programmable controller applications In addition applications in which human life or property that could ...

Страница 182: ...ration Anywire and ANYWIREASLINK is a trademark of Anywire Corporation MODBUS is a registered trademark of Schneider Electric SA Phillips is a registered trademark of Phillips Screw Company SD logo and SDHC logo are trademarks or registered trademarks of SD 3C LLC The company name and the product name to be described in this manual are the registered trademarks or trademarks of each company ...

Страница 183: ......

Страница 184: ...0 JAPAN Specifications are subject to change without notice When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permission Manual number JY997D61401F Model FX5UC U HW E Model code 09R558 ...

Отзывы: