160
APPX
Appendix 7 Terminal Module
Appendix 7
Terminal Module
Product configuration
Product list
Sink input/sink output (transistor output)
• The following table shows driving current of FX-16E-TB(/UL) and FX-32E-TB(/UL) that depends on the connection
destination.
Terminal modules are used to convert connector-type I/O terminals
into terminal blocks. By using terminal blocks (built-in element
type) dedicated to input or output, capturing of AC input signals
and format conversion into the relay/transistor/triac output can be
performed.
Model
No. of input
points
No. of output
points
Function
Connection destination
Driving
current
■
Sink input/sink output (transistor output)
FX-16E-TB
16 input points or 16 output points
Directly connected to I/O terminals
of a PLC.
FX5UC-
MT/D, FX5-C
EX/D, FX5-
C
EYT/D, FX5-C32ET/D
Refer to the
following table.
FX-32E-TB
32 input points, 32 output points, or
16 input points and 16 output points
FX-16EX-A1-TB
16
100 V AC input type
FX5UC-
MT/D, FX5-C
EX/D, FX5-
C32ET/D
24 V DC 48 mA
FX-16EYR-TB
16
Relay output type
FX5UC-
MT/D, FX5-C
EYT/D,
FX5-C32ET/D
24 V DC 80 mA
FX-16EYT-TB
16
Transistor output type (sink)
24 V DC 112 mA
FX-16EYS-TB
16
Triac output type
■
Sink and source common input/source output (transistor output)
FX-16E-TB/UL
16 input points or 16 output points
Directly connected to I/O terminals
of a PLC.
FX5UC-
MT/DSS, FX5-C
EX/DS,
FX5-C
EYT/DSS, FX5-C32ET/DSS
Refer to the
following table.
FX-32E-TB/UL
32 input points, 32 output points, or
16 input points and 16 output points
FX-16EYR-ES-TB/UL
16
Relay output type
FX5UC-
MT/DSS, FX5-C
EYT/
DSS, FX5-C32ET/DSS
24 V DC 80 mA
FX-16EYT-ES-TB/UL
16
Transistor output type (sink)
24 V DC 112 mA
FX-16EYT-ESS-TB/UL
16
Transistor output type (source)
FX-16EYS-ES-TB/UL
16
Triac output type
Connection destination
Power supply voltage
Current consumption
■
Input connector
FX5UC-
MT/D, FX5-C
EX/D, FX5-C32ET/D
Not required
FX5UC-
MT/DSS, FX5-C
EX/DS, FX5-C32ET/DSS
24 V DC
112 mA/16 points
■
Output connector
FX5UC-
MT/D, FX5UC-
MT/DSS, FX5-C
EYT/D, FX5-C
EYT/DSS,
FX5-C32ET/D, FX5-C32ET/DSS
The power supply appropriate to the connected load is required.
Terminal module
Option cable or
user-created cable