54
4 SYSTEM CONFIGURATION
4.4 Limitation on Current Consumption
If the ambient temperature exceeds 40
, use the extension power supply module at the following current
values within the derating range.
2.
Check the current consumption of extension devices.
(
3.
Calculate the total current consumption of each power supply.
4.
Check if expansion to the extension power supply module is permitted.
• 5 V DC power supply
• 24 V DC power supply
If the calculation result is a negative value, the current consumption exceeds the power supply capacity of the extension
power supply module.
Reconfigure the system, adding extension power supply modules.
Type
Model
Current consumption
5 V DC power supply
24 V DC power supply
Output module
FX5-C32EYT/D
120 mA
200 mA
Connector conversion module
FX5-CNV-IFC
Simple motion module
FX5-40SSC-S
Input module
FX5-16EX/ES
100 mA
Bus conversion module
FX5-CNV-BUS
150 mA
Analog input
FX3U-4AD
110 mA
Power supply type
Total current consumption
5 V DC power supply
480 mA
24 V DC power supply
200 mA
1200
800
55
40
625
400
5 V DC
24 V DC
Output current [mA]
Derating curve
Ambient
temperature [
]
Ex.
Ex.
mA
mA
Total number of
extension devices
mA
0 mA
Extension power
supply module
5 V DC
power supply capacity
Current consumption
Calculation result
480 mA
1200 mA
720 mA
Ex.
-
≥
=
mA
mA
Total number of
extension devices
mA
0 mA
Extension power
supply module
24 V DC
power supply capacity
Current consumption
Calculation result
200 mA
625 mA
425 mA
Ex.
-
≥
=
Содержание MELSEC iQ-F FX5UC
Страница 1: ...MELSEC iQ F FX5UC User s Manual Hardware ...
Страница 2: ......
Страница 15: ...13 CONTENTS ...
Страница 183: ......